VERTIV-IMD-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
12
Rows
12
Columns
117
pduMainTable
table.1.3.6.1.4.1.21239.5.2.3.1
·
1 row entry
·
12 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk pduMainTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::pduMainTable'
PDU general information
Entry in the pduMainTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.3.1.1.1 |
||||
|
Serial Number
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.3.1.1.2 |
||||
|
PDU name (factory assigned)
|
OctetString Constraints: range: 1-25 |
.1.3.6.1.4.1.21239.5.2.3.1.1.3 |
||||
|
PDU label (user-defined)
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.3.1.1.4 |
||||
|
Device availability:
0 = Unavailable 1 = Available 2 = Partially Unavailable |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.3.1.1.5 |
||||
|
Current meter type:
0 = Wye 1 = Delta |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.21239.5.2.3.1.1.6 |
||||
|
Total Name (factory-assigned)
|
OctetString Constraints: range: 1-25 |
.1.3.6.1.4.1.21239.5.2.3.1.1.7 |
||||
|
Total Label (user-defined)
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.3.1.1.8 |
||||
|
PDU total real power
|
wattsUnsigned32 Constraints: range: 0-9999 |
.1.3.6.1.4.1.21239.5.2.3.1.1.9 |
||||
|
PDU total apparent power
|
volt-ampsUnsigned32 Constraints: range: 0-9999 |
.1.3.6.1.4.1.21239.5.2.3.1.1.10 |
||||
|
PDU total power factor
|
%Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.3.1.1.11 |
||||
|
PDU total accumulated energy in watt-hours
|
watt-hoursUnsigned32 Constraints: range: 0-9999000 |
.1.3.6.1.4.1.21239.5.2.3.1.1.12 |
pduPhaseTable
table.1.3.6.1.4.1.21239.5.2.3.2
·
1 row entry
·
15 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk pduPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::pduPhaseTable'
PDU phases information
Entry in the pduPhaseTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.3.2.1.1 |
|
PDU phase name (factory-assigned)
|
OctetString Constraints: range: 1-25 |
.1.3.6.1.4.1.21239.5.2.3.2.1.2 |
|
PDU phase label (user-defined)
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.3.2.1.3 |
|
PDU phase voltage in tenths of a volt
|
decivolts (rms)Unsigned32 Constraints: range: 0-3100 |
.1.3.6.1.4.1.21239.5.2.3.2.1.4 |
|
Highest RMS voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt
|
decivolts (rms)Unsigned32 Constraints: range: 0-3100 |
.1.3.6.1.4.1.21239.5.2.3.2.1.5 |
|
Lowest RMS voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt
|
decivolts (rms)Unsigned32 Constraints: range: 0-3100 |
.1.3.6.1.4.1.21239.5.2.3.2.1.6 |
|
Highest instantaneous voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt. This object may not exist on all platforms, due to hardware differences.
|
decivoltsUnsigned32 Constraints: range: 0-4400 |
.1.3.6.1.4.1.21239.5.2.3.2.1.7 |
|
PDU phase current reading in hundreths of an amp.
|
centiamps (rms)Unsigned32 Constraints: range: 0-9900 |
.1.3.6.1.4.1.21239.5.2.3.2.1.8 |
|
Highest RMS current measured on this phase, since power-up or last reset. The value is given in hundreths of an amp.
|
centiamps (rms)Unsigned32 Constraints: range: 0-9900 |
.1.3.6.1.4.1.21239.5.2.3.2.1.9 |
|
Lowest RMS current measured on this phase, since power-up or last reset. The value is given in hundreths of an amp.
|
centiamps (rms)Unsigned32 Constraints: range: 0-9900 |
.1.3.6.1.4.1.21239.5.2.3.2.1.10 |
|
Highest instantaneous current measured on ths phase, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences.
|
centiampsUnsigned32 Constraints: range: 0-15000 |
.1.3.6.1.4.1.21239.5.2.3.2.1.11 |
|
Real power for phase in watts
|
wattsUnsigned32 Constraints: range: 0-9999 |
.1.3.6.1.4.1.21239.5.2.3.2.1.12 |
|
Apparent power for phase in volt-amps
|
volt-ampsUnsigned32 Constraints: range: 0-9999 |
.1.3.6.1.4.1.21239.5.2.3.2.1.13 |
|
Power factor for phase
|
%Unsigned32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.3.2.1.14 |
|
Accumulated energy for phase in watt-hours
|
watt-hoursUnsigned32 Constraints: range: 0-9999000 |
.1.3.6.1.4.1.21239.5.2.3.2.1.15 |
pduBreakerTable
table.1.3.6.1.4.1.21239.5.2.3.3
·
1 row entry
·
7 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk pduBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::pduBreakerTable'
PDU breaker information
Entry in the pduBreakerTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.3.3.1.1 |
|
PDU breaker name (factory-assigned)
|
OctetString Constraints: range: 1-25 |
.1.3.6.1.4.1.21239.5.2.3.3.1.2 |
|
PDU breaker label (user-defined)
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.3.3.1.3 |
|
PDU breaker current reading in hundreths of an amp
|
centiamps (rms)Unsigned32 Constraints: range: 0-9900 |
.1.3.6.1.4.1.21239.5.2.3.3.1.4 |
|
Highest RMS current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp.
|
centiamps (rms)Unsigned32 Constraints: range: 0-9900 |
.1.3.6.1.4.1.21239.5.2.3.3.1.5 |
|
Lowest RMS current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp.
|
centiamps (rms)Unsigned32 Constraints: range: 0-9900 |
.1.3.6.1.4.1.21239.5.2.3.3.1.6 |
|
Highest instantaneous current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences.
|
centiampsUnsigned32 Constraints: range: 0-15000 |
.1.3.6.1.4.1.21239.5.2.3.3.1.7 |
pduLineTable
table.1.3.6.1.4.1.21239.5.2.3.4
·
1 row entry
·
7 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk pduLineTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::pduLineTable'
PDU line current information
Entry in the pduLineTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.3.4.1.1 |
|
PDU line name (factory-assigned)
|
OctetString Constraints: range: 1-25 |
.1.3.6.1.4.1.21239.5.2.3.4.1.2 |
|
PDU line label (user-defined)
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.3.4.1.3 |
|
PDU line current reading in hundreths of an amp
|
centiamps (rms)Unsigned32 Constraints: range: 0-9900 |
.1.3.6.1.4.1.21239.5.2.3.4.1.4 |
|
Highest RMS current measured on this line, since power-up or last reset. The value is given in hundreths of an amp.
|
centiamps (rms)Unsigned32 Constraints: range: 0-9900 |
.1.3.6.1.4.1.21239.5.2.3.4.1.5 |
|
Lowest RMS current measured on this line, since power-up or last reset. The value is given in hundreths of an amp.
|
centiamps (rms)Unsigned32 Constraints: range: 0-9900 |
.1.3.6.1.4.1.21239.5.2.3.4.1.6 |
|
Highest instantaneous current measured on this line, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences.
|
centiampsUnsigned32 Constraints: range: 0-15000 |
.1.3.6.1.4.1.21239.5.2.3.4.1.7 |
tempSensorTable
table.1.3.6.1.4.1.21239.5.2.4
·
1 row entry
·
5 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk tempSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::tempSensorTable'
Remote Temperature (RT) sensor
Entry in the tempSensorTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.4.1.1 |
|
Serial Number
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.4.1.2 |
|
User-defined label
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.4.1.3 |
|
Device availability:
0 = Unavailable 1 = Available 2 = Partially Unavailable |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.4.1.4 |
|
Temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
|
decidegreesInteger32 Constraints: range: -400-2540 |
.1.3.6.1.4.1.21239.5.2.4.1.5 |
airFlowSensorTable
table.1.3.6.1.4.1.21239.5.2.5
·
1 row entry
·
8 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk airFlowSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::airFlowSensorTable'
Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor
Entry in the airFlowSensorTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.5.1.1 |
|
Serial Number
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.5.1.2 |
|
User-defined label
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.5.1.3 |
|
Device availability:
0 = Unavailable 1 = Available 2 = Partially Unavailable |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.5.1.4 |
|
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
|
decidegreesInteger32 Constraints: range: -400-2540 |
.1.3.6.1.4.1.21239.5.2.5.1.5 |
|
Airflow reading. Still air will be less than 20, while rushing air will be around 100.
|
Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.5.1.6 |
|
Humidity reading
|
%Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.5.1.7 |
|
Dewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
|
decidegreesInteger32 Constraints: range: -400-2540 |
.1.3.6.1.4.1.21239.5.2.5.1.8 |
dewPointSensorTable
table.1.3.6.1.4.1.21239.5.2.6
·
1 row entry
·
7 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk dewPointSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::dewPointSensorTable'
Remote Dew Point sensor
Entry in the dewPointSensorTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.6.1.1 |
|
Serial Number
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.6.1.2 |
|
User-defined label
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.6.1.3 |
|
Device availability:
0 = Unavailable 1 = Available 2 = Partially Unavailable |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.6.1.4 |
|
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
|
decidegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.6.1.5 |
|
Humidity reading
|
%Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.6.1.6 |
|
Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
|
decidegreesInteger32 Constraints: range: -40-200 |
.1.3.6.1.4.1.21239.5.2.6.1.7 |
ccatSensorTable
table.1.3.6.1.4.1.21239.5.2.7
·
1 row entry
·
7 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk ccatSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::ccatSensorTable'
Remote CCAT sensor
Entry in the ccatSensorTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.7.1.1 |
|
Serial Number
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.7.1.2 |
|
User-defined label
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.7.1.3 |
|
Device availability:
0 = Unavailable 1 = Available 2 = Partially Unavailable |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.7.1.4 |
|
CCAT sensor reading
|
Integer32 Constraints: range: -100-5000 |
.1.3.6.1.4.1.21239.5.2.7.1.5 |
|
CCAT sensor type
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.7.1.6 |
|
CCAT sensor value description
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.7.1.7 |
t3hdSensorTable
table.1.3.6.1.4.1.21239.5.2.8
·
1 row entry
·
14 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk t3hdSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::t3hdSensorTable'
Remote Temperature x 3, Humidity and Dewpoint Sensor
Entry in the t3hdSensorTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.8.1.1 |
|
Serial Number
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.8.1.2 |
|
User-defined label
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.8.1.3 |
|
Device availability:
0 = Unavailable 1 = Available 2 = Partially Unavailable |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.8.1.4 |
|
Internal label (user-defined)
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.8.1.5 |
|
Internal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
|
decidegreesInteger32 Constraints: range: -400-2540 |
.1.3.6.1.4.1.21239.5.2.8.1.6 |
|
Internal Humidity
|
%Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.8.1.7 |
|
Internal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
|
decidegreesInteger32 Constraints: range: -400-2540 |
.1.3.6.1.4.1.21239.5.2.8.1.8 |
|
External A status:
0 =Unavailable 1 =Available |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.8.1.9 |
|
External A label (user-defined)
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.8.1.10 |
|
External A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
|
decidegreesInteger32 Constraints: range: -400-2540 |
.1.3.6.1.4.1.21239.5.2.8.1.11 |
|
External B status:
0 = Unavailable 1 = Available |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.8.1.12 |
|
External B label (user-defined)
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.8.1.13 |
|
External B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
|
decidegreesInteger32 Constraints: range: -400-2540 |
.1.3.6.1.4.1.21239.5.2.8.1.14 |
thdSensorTable
table.1.3.6.1.4.1.21239.5.2.9
·
1 row entry
·
7 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk thdSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::thdSensorTable'
Remote Temperature, Humidity and Dewpoint (THD) Sensor
Entry in the thdSensorTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.9.1.1 |
|
Serial Number
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.9.1.2 |
|
User-defined label
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.9.1.3 |
|
Device availability:
0 = Unavailable 1 = Available 2 = Partially Unavailable |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.9.1.4 |
|
Temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
|
decidegreesInteger32 Constraints: range: -400-2540 |
.1.3.6.1.4.1.21239.5.2.9.1.5 |
|
Humidity value
|
%Integer32 Constraints: range: 0-100 |
.1.3.6.1.4.1.21239.5.2.9.1.6 |
|
Dewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
|
decidegreesInteger32 Constraints: range: -400-2540 |
.1.3.6.1.4.1.21239.5.2.9.1.7 |
rpmSensorTable
table.1.3.6.1.4.1.21239.5.2.10
·
1 row entry
·
15 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk rpmSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::rpmSensorTable'
Remote Power Manager Sensor
Entry in the rpmSensorTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.10.1.1 |
|
Serial Number
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.10.1.2 |
|
Friendly Name
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.10.1.3 |
|
Device availability
0 = Unavailable 1 = Available 2 = Partially Unavailable |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.4 |
|
RPM Sensor Accumulated Energy
|
kWhSNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.5 |
|
RPM Sensor Voltage
|
Volts (rms)SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.6 |
|
RPM Sensor Voltage (Max)
|
Volts (rms)SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.7 |
|
RPM Sensor Voltage (Min)
|
Volts (rms)SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.8 |
|
RPM Sensor Voltage (Peak)
|
VoltsSNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.9 |
|
RPM Sensor Current reading in deciAmps
|
0.1 Amps (rms)SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.10 |
|
RPM Sensor Real Power
|
WattsSNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.11 |
|
RPM Sensor Apparent Power
|
Volt-AmpsSNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.12 |
|
RPM Sensor Power Factor
|
%SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.13 |
|
RPM Sensor Outlet 1 State: 0 = off, 1 = on
|
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.14 |
|
RPM Sensor Outlet 2 State:
0 = off 1 = on |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.10.1.15 |
a2dSensorTable
table.1.3.6.1.4.1.21239.5.2.11
·
1 row entry
·
13 columns
Uses the geist variant from
Command help
/opt/observium/mibs/geist.
Walk a2dSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::a2dSensorTable'
Analog measurement (A2D) sensor (voltage, current, or dry-contact)
Entry in the a2dSensorTable table: each entry contains an index and other sensor details
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Table entry index value
|
Integer32 Constraints: range: 1-100 |
.1.3.6.1.4.1.21239.5.2.11.1.1 |
||||||||||||||||||||||
|
Serial Number
|
SNMPv2-TCDisplayString Type Constraints: range: 0..255Description: Represents textual information taken from the NVT ASCII character set, as defined in pages 4, 10-11 of RFC 854. To summarize RFC 854, the NVT ASCII repertoire specifies: - the use of c… |
.1.3.6.1.4.1.21239.5.2.11.1.2 |
||||||||||||||||||||||
|
User-defined label
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.11.1.3 |
||||||||||||||||||||||
|
Device availability:
0 = Unavailable 1 = Available 2 = Partially Unavailable |
SNMPv2-SMIGauge32 Type Constraints: range: 0..4294967295 |
.1.3.6.1.4.1.21239.5.2.11.1.4 |
||||||||||||||||||||||
|
Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode.
|
Integer32 Constraints: range: -1000000-1000000 |
.1.3.6.1.4.1.21239.5.2.11.1.5 |
||||||||||||||||||||||
|
For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue.
|
OctetString Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.11.1.6 |
||||||||||||||||||||||
|
Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMa…
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.21239.5.2.11.1.7 |
||||||||||||||||||||||
|
The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode.
|
OctetStringr/w Constraints: range: 0-7 |
.1.3.6.1.4.1.21239.5.2.11.1.8 |
||||||||||||||||||||||
|
Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value.…
|
Integer32r/w Constraints: range: -1000000-1000000 |
.1.3.6.1.4.1.21239.5.2.11.1.9 |
||||||||||||||||||||||
|
Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value.…
|
Integer32r/w Constraints: range: -1000000-1000000 |
.1.3.6.1.4.1.21239.5.2.11.1.10 |
||||||||||||||||||||||
|
Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value bas…
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.11.1.11 |
||||||||||||||||||||||
|
Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value bas…
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.11.1.12 |
||||||||||||||||||||||
|
Label for the analog measurement
|
OctetStringr/w Constraints: range: 0-25 |
.1.3.6.1.4.1.21239.5.2.11.1.13 |