VERTIV-IMD-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
12
Rows
12
Columns
117

pduMainTable

table
.1.3.6.1.4.1.21239.5.2.3.1 · 1 row entry · 12 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduMainTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::pduMainTable'
PDU general information
pduMainEntry row .1.3.6.1.4.1.21239.5.2.3.1.1
Entry in the pduMainTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.1.1.1
Serial Number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.3.1.1.2
PDU name (factory assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.1.1.3
PDU label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.1.1.4
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.3.1.1.5
Current meter type:
0 = Wye
1 = Delta
Enumeration
Enumerated Values:
0wye
1delta
.1.3.6.1.4.1.21239.5.2.3.1.1.6
Total Name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.1.1.7
Total Label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.1.1.8
PDU total real power
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.1.1.9
PDU total apparent power
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.1.1.10
PDU total power factor
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.1.1.11
PDU total accumulated energy in watt-hours
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.1.1.12
.1.3.6.1.4.1.21239.5.2.3.2 · 1 row entry · 15 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::pduPhaseTable'
PDU phases information
pduPhaseEntry row .1.3.6.1.4.1.21239.5.2.3.2.1
Entry in the pduPhaseTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.2.1.1
PDU phase name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.2.1.2
PDU phase label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.2.1.3
PDU phase voltage in tenths of a volt
decivolts (rms)Unsigned32
Constraints:
range: 0-3100
.1.3.6.1.4.1.21239.5.2.3.2.1.4
Highest RMS voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt
decivolts (rms)Unsigned32
Constraints:
range: 0-3100
.1.3.6.1.4.1.21239.5.2.3.2.1.5
Lowest RMS voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt
decivolts (rms)Unsigned32
Constraints:
range: 0-3100
.1.3.6.1.4.1.21239.5.2.3.2.1.6
Highest instantaneous voltage measured on this phase, since power-up or last reset. The value is given in tenths of a volt. This object may not exist on all platforms, due to hardware differences.
decivoltsUnsigned32
Constraints:
range: 0-4400
.1.3.6.1.4.1.21239.5.2.3.2.1.7
PDU phase current reading in hundreths of an amp.
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.2.1.8
Highest RMS current measured on this phase, since power-up or last reset. The value is given in hundreths of an amp.
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.2.1.9
Lowest RMS current measured on this phase, since power-up or last reset. The value is given in hundreths of an amp.
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.2.1.10
Highest instantaneous current measured on ths phase, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences.
centiampsUnsigned32
Constraints:
range: 0-15000
.1.3.6.1.4.1.21239.5.2.3.2.1.11
Real power for phase in watts
wattsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.2.1.12
Apparent power for phase in volt-amps
volt-ampsUnsigned32
Constraints:
range: 0-9999
.1.3.6.1.4.1.21239.5.2.3.2.1.13
Power factor for phase
%Unsigned32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.3.2.1.14
Accumulated energy for phase in watt-hours
watt-hoursUnsigned32
Constraints:
range: 0-9999000
.1.3.6.1.4.1.21239.5.2.3.2.1.15
.1.3.6.1.4.1.21239.5.2.3.3 · 1 row entry · 7 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduBreakerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::pduBreakerTable'
PDU breaker information
pduBreakerEntry row .1.3.6.1.4.1.21239.5.2.3.3.1
Entry in the pduBreakerTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.3.1.1
PDU breaker name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.3.1.2
PDU breaker label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.3.1.3
PDU breaker current reading in hundreths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.3.1.4
Highest RMS current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp.
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.3.1.5
Lowest RMS current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp.
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.3.1.6
Highest instantaneous current measured on this breaker, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences.
centiampsUnsigned32
Constraints:
range: 0-15000
.1.3.6.1.4.1.21239.5.2.3.3.1.7

pduLineTable

table
.1.3.6.1.4.1.21239.5.2.3.4 · 1 row entry · 7 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk pduLineTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::pduLineTable'
PDU line current information
pduLineEntry row .1.3.6.1.4.1.21239.5.2.3.4.1
Entry in the pduLineTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.3.4.1.1
PDU line name (factory-assigned)
OctetString
Constraints:
range: 1-25
.1.3.6.1.4.1.21239.5.2.3.4.1.2
PDU line label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.3.4.1.3
PDU line current reading in hundreths of an amp
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.4.1.4
Highest RMS current measured on this line, since power-up or last reset. The value is given in hundreths of an amp.
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.4.1.5
Lowest RMS current measured on this line, since power-up or last reset. The value is given in hundreths of an amp.
centiamps (rms)Unsigned32
Constraints:
range: 0-9900
.1.3.6.1.4.1.21239.5.2.3.4.1.6
Highest instantaneous current measured on this line, since power-up or last reset. The value is given in hundreths of an amp. This object may not exist on all platforms, due to hardware differences.
centiampsUnsigned32
Constraints:
range: 0-15000
.1.3.6.1.4.1.21239.5.2.3.4.1.7
.1.3.6.1.4.1.21239.5.2.4 · 1 row entry · 5 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk tempSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::tempSensorTable'
Remote Temperature (RT) sensor
tempSensorEntry row .1.3.6.1.4.1.21239.5.2.4.1
Entry in the tempSensorTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.4.1.1
Serial Number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.4.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.4.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.4.1.4
Temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.4.1.5
.1.3.6.1.4.1.21239.5.2.5 · 1 row entry · 8 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk airFlowSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::airFlowSensorTable'
Remote Airflow, Humidity, Temperature and Dewpoint (AFHT3) Sensor
airFlowSensorEntry row .1.3.6.1.4.1.21239.5.2.5.1
Entry in the airFlowSensorTable table: each entry contains an index and other sensor details
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.5.1.1
Serial Number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.5.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.5.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.5.1.4
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.5.1.5
Airflow reading. Still air will be less than 20, while rushing air will be around 100.
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.5.1.6
Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.5.1.7
Dewpoint reading in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.5.1.8
.1.3.6.1.4.1.21239.5.2.6 · 1 row entry · 7 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk dewPointSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::dewPointSensorTable'
Remote Dew Point sensor
dewPointSensorEntry row .1.3.6.1.4.1.21239.5.2.6.1
Entry in the dewPointSensorTable table: each entry contains an index and other sensor details
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.6.1.1
Serial Number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.6.1.2
User-defined label
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.6.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.6.1.4
Current reading for Temperature in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
decidegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.2.6.1.5
Humidity reading
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.6.1.6
Current reading for Dew-point in tenths of degrees. Units are given by temperatureUnits field in deviceInfo
decidegreesInteger32
Constraints:
range: -40-200
.1.3.6.1.4.1.21239.5.2.6.1.7
.1.3.6.1.4.1.21239.5.2.7 · 1 row entry · 7 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk ccatSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::ccatSensorTable'
Remote CCAT sensor
ccatSensorEntry row .1.3.6.1.4.1.21239.5.2.7.1
Entry in the ccatSensorTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.7.1.1
Serial Number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.7.1.2
User-defined label
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.7.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.7.1.4
CCAT sensor reading
Integer32
Constraints:
range: -100-5000
.1.3.6.1.4.1.21239.5.2.7.1.5
CCAT sensor type
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.7.1.6
CCAT sensor value description
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.7.1.7
.1.3.6.1.4.1.21239.5.2.8 · 1 row entry · 14 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk t3hdSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::t3hdSensorTable'
Remote Temperature x 3, Humidity and Dewpoint Sensor
t3hdSensorEntry row .1.3.6.1.4.1.21239.5.2.8.1
Entry in the t3hdSensorTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.8.1.1
Serial Number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.8.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.8.1.4
Internal label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.5
Internal temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.6
Internal Humidity
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.8.1.7
Internal dewpoint in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.8
External A status:
0 =Unavailable
1 =Available
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.8.1.9
External A label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.10
External A temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.11
External B status:
0 = Unavailable
1 = Available
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.8.1.12
External B label (user-defined)
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.8.1.13
External B temperature in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.8.1.14
.1.3.6.1.4.1.21239.5.2.9 · 1 row entry · 7 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk thdSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::thdSensorTable'
Remote Temperature, Humidity and Dewpoint (THD) Sensor
thdSensorEntry row .1.3.6.1.4.1.21239.5.2.9.1
Entry in the thdSensorTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.9.1.1
Serial Number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.9.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.9.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.9.1.4
Temperature value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.9.1.5
Humidity value
%Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.21239.5.2.9.1.6
Dewpoint value in tenths of a degree. Units are given by temperatureUnits field in deviceInfo.
decidegreesInteger32
Constraints:
range: -400-2540
.1.3.6.1.4.1.21239.5.2.9.1.7
.1.3.6.1.4.1.21239.5.2.10 · 1 row entry · 15 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk rpmSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::rpmSensorTable'
Remote Power Manager Sensor
rpmSensorEntry row .1.3.6.1.4.1.21239.5.2.10.1
Entry in the rpmSensorTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.10.1.1
Serial Number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.10.1.2
Friendly Name
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.10.1.3
Device availability
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.4
RPM Sensor Accumulated Energy
kWhSNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.5
RPM Sensor Voltage
Volts (rms)SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.6
RPM Sensor Voltage (Max)
Volts (rms)SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.7
RPM Sensor Voltage (Min)
Volts (rms)SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.8
RPM Sensor Voltage (Peak)
VoltsSNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.9
RPM Sensor Current reading in deciAmps
0.1 Amps (rms)SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.10
RPM Sensor Real Power
WattsSNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.11
RPM Sensor Apparent Power
Volt-AmpsSNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.12
RPM Sensor Power Factor
%SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.13
RPM Sensor Outlet 1 State: 0 = off, 1 = on
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.14
RPM Sensor Outlet 2 State:
0 = off
1 = on
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.10.1.15
.1.3.6.1.4.1.21239.5.2.11 · 1 row entry · 13 columns
Uses the geist variant from /opt/observium/mibs/geist.
Command help
Walk a2dSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'VERTIV-IMD-MIB' -M '/opt/observium/mibs/geist:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'VERTIV-IMD-MIB::a2dSensorTable'
Analog measurement (A2D) sensor (voltage, current, or dry-contact)
a2dSensorEntry row .1.3.6.1.4.1.21239.5.2.11.1
Entry in the a2dSensorTable table: each entry contains an index and other sensor details
Indexes
Column Syntax OID
Table entry index value
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.21239.5.2.11.1.1
Serial Number
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.21239.5.2.11.1.2
User-defined label
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.3
Device availability:
0 = Unavailable
1 = Available
2 = Partially Unavailable
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.21239.5.2.11.1.4
Analog measurement value, within either a user-defined or preset range, depending on a2dSensorMode.
Integer32
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.2.11.1.5
For current/voltage modes, the analog value is given as a string. In binary modes, the value is either a2dSensorLowLabel or a2dSensorHighLabel, based on a2dSensorValue.
OctetString
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.6
Binary modes have two states represented by the values 0 (low) or 1 (high). These correspond to a2dSensorLowLabel and a2dSensorHighLabel. Current and voltage modes provide a scaled value from a2dSensorMin to a2dSensorMa…
Enumerationr/w
Enumerated Values:
1door
2powerFailure
3flood
4wscLeak
5wscFault
6smoke
7ivsNegGnd
8ivsPosGnd
9customVoltage
10customBinary
11customCurrent
.1.3.6.1.4.1.21239.5.2.11.1.7
The units for the analog value. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value. Otherwise, the value is fixed, based on mode.
OctetStringr/w
Constraints:
range: 0-7
.1.3.6.1.4.1.21239.5.2.11.1.8
Minimum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value.…
Integer32r/w
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.2.11.1.9
Maximum analog value, given as an integer. The analog measurement is scaled to the range a2dSensorMin to a2dSensorMax. If a2dSensorMode is customVoltage(9) or customCurrent(11), then this field has a user-defined value.…
Integer32r/w
Constraints:
range: -1000000-1000000
.1.3.6.1.4.1.21239.5.2.11.1.10
Label for 0 (low) binary value. This field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value bas…
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.11
Label for 1 (high) binary value. The field is only applicable if a2dSensorMode is one of the binary modes. If a2dSensorMode is customBinary(10), then this field is user-defined. Otherwise, it has a pre-defined value bas…
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.12
Label for the analog measurement
OctetStringr/w
Constraints:
range: 0-25
.1.3.6.1.4.1.21239.5.2.11.1.13