USHA-MIB
Monitored by Observium
Observium actively monitors this MIB
Observium uses this MIB in discovery or polling workflows on applicable devices.
Device identity
Sensors
Status
Explore Observium network monitoring
- Source file
USHA-MIB- Last revised
- Not declared
Imported Objects
| RFC-1212 | OBJECT-TYPE (no object page) |
| RFC-1215 | TRAP-TYPE (no object page) |
| RFC1155-SMI | Counter enterprises IpAddress |
| RFC1213-MIB | DisplayString |
| UPS-MIB | NonNegativeInteger PositiveInteger |
Objects (155)
26 directly used by Observium
Showing 155 of 155 objects
Object legend
Object type
Icons distinguish tables, entry rows, columns, scalars, and structural nodes.
SNMPv2-TCTruthValue
Syntax
Blue badges identify the value syntax. Connected badges read as defining module and convention.
IF-MIBifIndex
Table index
Green identifies an index object; yellow names its module when the index is defined elsewhere.
r/w
deprecated
obsolete
Access and status
r/w means read-write. Grey labels mark definitions retained for compatibility.
OBS ✓
Observium use
The indicator appears only when Observium directly references that object.
ifOperStatus
.1.3.6.1.2.1…
Names and OIDs
Object names link to their detail pages. Hover or focus a linked name or badge for available definition details.
.1.3.6.1.4.1.2468 | ||
.1.3.6.1.4.1.2468.1 | ||
.1.3.6.1.4.1.2468.1.6 | ||
.1.3.6.1.4.1.2468.1.6.1 | ||
.1.3.6.1.4.1.2468.1.6.1.1 | ||
.1.3.6.1.4.1.2468.1.6.1.1.1 | ||
invIdentGroupManufacturerOBS ✓mandatory | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.1.1 |
invIdentGroupModelOBS ✓mandatory | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.1.2 |
invIdentGroupInvFirmwareVersionOBS ✓mandatory | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.1.3 |
invIdentGroupAgentSoftwareVersionmandatory | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.1.4 |
invIdentGroupNamemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.1.5 |
invIdentGroupAttachedDevicesmandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.1.6 |
invIdentGroupInvSerialNumberOBS ✓mandatory | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.1.7 |
.1.3.6.1.4.1.2468.1.6.1.1.2 | ||
invDcInputSourceGroupStatusOBS ✓mandatory | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.2.1 |
invDcInputSourceGroupEstimatedChargeRemainingOBS ✓mandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.2.2 |
invDcInputSourceGroupVoltageOBS ✓mandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.2.3 |
invDcInputSourceGroupMandatoryOBS ✓mandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.2.4 |
invDcInputSourceGroupTemperatureOBS ✓mandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.2.5 |
.1.3.6.1.4.1.2468.1.6.1.1.3 | ||
invInputGroupLineBadsmandatory | RFC1155-SMICounter | .1.3.6.1.4.1.2468.1.6.1.1.3.1 |
invInputGroupNumLinesmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.3.2 |
invInputGroupTablemandatory | .1.3.6.1.4.1.2468.1.6.1.1.3.3 | |
invInputGroupEntrymandatory | .1.3.6.1.4.1.2468.1.6.1.1.3.3.1 | |
invInputGroupLineIndexmandatory | UPS-MIBPositiveInteger | .1.3.6.1.4.1.2468.1.6.1.1.3.3.1.1 |
invInputGroupFrequencyOBS ✓mandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.3.3.1.2 |
invInputGroupVoltageOBS ✓mandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.3.3.1.3 |
invInputGroupCurrentOBS ✓mandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.3.3.1.4 |
invInputGroupTruePowerOBS ✓mandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.3.3.1.5 |
invInputGroupVoltageMaxmandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.3.3.1.6 |
invInputGroupVoltageMinmandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.3.3.1.7 |
.1.3.6.1.4.1.2468.1.6.1.1.4 | ||
invOutputGroupSourceOBS ✓mandatory | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.4.1 |
invOutputGroupFrequencyOBS ✓mandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.4.2 |
invOutputGroupNumLinesmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.4.3 |
invOutputGroupTablemandatory | .1.3.6.1.4.1.2468.1.6.1.1.4.4 | |
invOutputGroupEntrymandatory | .1.3.6.1.4.1.2468.1.6.1.1.4.4.1 | |
invOutputGroupLineIndexmandatory | UPS-MIBPositiveInteger | .1.3.6.1.4.1.2468.1.6.1.1.4.4.1.1 |
invOutputGroupVoltageOBS ✓mandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.4.4.1.2 |
invOutputGroupCurrentOBS ✓mandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.4.4.1.3 |
invOutputGroupPowerOBS ✓mandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.4.4.1.4 |
invOutputGroupPercentLoadOBS ✓mandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.4.4.1.5 |
.1.3.6.1.4.1.2468.1.6.1.1.5 | ||
invControlInvShutdownDelaymandatoryr/w | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.5.1 |
invControlInvSleepTimemandatoryr/w | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.5.2 |
invControlInvOnOffControlmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.5.3 |
invControlShutdownParametersTablemandatory | .1.3.6.1.4.1.2468.1.6.1.1.5.4 | |
invControlShutdownParametersEntrymandatory | .1.3.6.1.4.1.2468.1.6.1.1.5.4.1 | |
invControlEventmandatory | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.5.4.1.1 |
invControlEventStatusmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.5.4.1.2 |
invControlDelaymandatoryr/w | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.5.4.1.3 |
invControlFirstWarningmandatoryr/w | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.5.4.1.4 |
invControlWarningIntervalmandatoryr/w | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.5.4.1.5 |
invControlWeeklyScheduleTablemandatory | .1.3.6.1.4.1.2468.1.6.1.1.5.5 | |
invControlWeeklyScheduleEntrymandatory | .1.3.6.1.4.1.2468.1.6.1.1.5.5.1 | |
invControlWeeklyIndexmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.5.5.1.1 |
invControlWeeklyShutdownDaymandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.5.5.1.2 |
invControlWeeklyShutdownTimemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.5.5.1.3 |
invControlWeeklyRestartDaymandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.5.5.1.4 |
invControlWeeklyRestartTimemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.5.5.1.5 |
invControlSpecialScheduleTablemandatory | .1.3.6.1.4.1.2468.1.6.1.1.5.6 | |
invControlSpecialScheduleEntrymandatory | .1.3.6.1.4.1.2468.1.6.1.1.5.6.1 | |
invControlSpecialIndexmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.5.6.1.1 |
invControlSpecialShutdownDaymandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.5.6.1.2 |
invControlSpecialShutdownTimemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.5.6.1.3 |
invControlSpecialRestartDaymandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.5.6.1.4 |
invControlSpecialRestartTimemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.5.6.1.5 |
.1.3.6.1.4.1.2468.1.6.1.1.6 | ||
invConfigGroupInputVoltagemandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.6.1 |
invConfigGroupInputFreqmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.6.2 |
invConfigGroupOutputVoltagemandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.6.3 |
invConfigGroupOutputFreqmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.6.4 |
invConfigGroupOutputVAmandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.6.5 |
invConfigGroupOutputPowermandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.6.6 |
invConfigGroupOverTemperatureSetPointmandatoryr/w | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.6.7 |
invConfigGroupOverLoadSetPointmandatoryr/w | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.6.8 |
.1.3.6.1.4.1.2468.1.6.1.1.7 | ||
invClientsConnectedNummandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.7.1 |
invDevicesTablemandatory | .1.3.6.1.4.1.2468.1.6.1.1.7.2 | |
invDevicesEntrymandatory | .1.3.6.1.4.1.2468.1.6.1.1.7.2.1 | |
indexOfDevicemandatory | UPS-MIBNonNegativeInteger | .1.3.6.1.4.1.2468.1.6.1.1.7.2.1.1 |
addrOfDevicemandatory | RFC1155-SMIIpAddress | .1.3.6.1.4.1.2468.1.6.1.1.7.2.1.2 |
nameOfDevicemandatory | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.7.2.1.3 |
timeOfConnectionmandatory | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.7.2.1.4 |
timeOfConnectionTimemandatory | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.7.2.1.5 |
timeOfConnectionTimeoutmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.7.2.1.6 |
.1.3.6.1.4.1.2468.1.6.1.1.8 | ||
agentConfigIpaddressmandatoryr/w | RFC1155-SMIIpAddress | .1.3.6.1.4.1.2468.1.6.1.1.8.1 |
agentConfigDhcpStatuemandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.8.10 |
agentConfigTftpStatuemandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.8.11 |
agentConfigResetToDefaultmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.8.12 |
agentConfigRestartmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.8.13 |
agentConfigClearAgentLogmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.8.14 |
agentConfigClearEventLogmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.8.15 |
agentConfigClearHistoryLogmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.8.16 |
agentConfigMibVersionmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.8.17 |
agentConfigTrapsReceiversTablemandatory | .1.3.6.1.4.1.2468.1.6.1.1.8.18 | |
agentConfigTrapsReceiversEntrymandatory | .1.3.6.1.4.1.2468.1.6.1.1.8.18.1 | |
trapsIndexmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.8.18.1.1 |
trapsReceiverAddrmandatoryr/w | RFC1155-SMIIpAddress | .1.3.6.1.4.1.2468.1.6.1.1.8.18.1.2 |
receiverCommunityStringmandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.8.18.1.3 |
receiverNmsTypemandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.8.18.1.4 |
receiverSeverityLevelmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.8.18.1.5 |
receiverDescriptionmandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.8.18.1.6 |
agentConfigGatewaymandatoryr/w | RFC1155-SMIIpAddress | .1.3.6.1.4.1.2468.1.6.1.1.8.2 |
agentConfigSubnetMaskmandatoryr/w | RFC1155-SMIIpAddress | .1.3.6.1.4.1.2468.1.6.1.1.8.3 |
agentConfigDatemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.8.4 |
agentConfigTimemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.8.5 |
agentConfigPrimaryTimeServermandatoryr/w | RFC1155-SMIIpAddress | .1.3.6.1.4.1.2468.1.6.1.1.8.6 |
agentConfigHistoryLogFrequencymandatoryr/w | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.8.7 |
agentConfigPollRatemandatoryr/w | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.8.8 |
agentConfigBaudRatemandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.8.9 |
.1.3.6.1.4.1.2468.1.6.1.1.9 | ||
envMonDevStatusTablemandatory | .1.3.6.1.4.1.2468.1.6.1.1.9.1 | |
envMonDevStatusmandatory | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1 | |
envMonDevStatusIndexmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.1 |
envMonDevStatusAppVermandatory | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.10 |
envMonDevStatusStateOBS ✓mandatory | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.2 |
envMonDevStatusTempOBS ✓mandatory | degCEnumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.3 |
envMonDevStatusHumiOBS ✓mandatory | 0.1%Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.4 |
envMonDevStatusTempAlarmOBS ✓mandatory | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.5 |
envMonDevStatusHumiAlarmOBS ✓mandatory | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.6 |
envMonDevStatusAlarm1OBS ✓mandatory | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.7 |
envMonDevStatusAlarm2OBS ✓mandatory | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.8 |
envMonDevStatusAddressmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.9.1.1.9 |
envMonDevCfgTablemandatory | .1.3.6.1.4.1.2468.1.6.1.1.9.2 | |
envMonDevCfgmandatory | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1 | |
envMonDevCfgIndexmandatory | Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.1 |
envMonDevCfgTempHighCriticalEnmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.10 |
envMonDevCfgTempLowCriticalEnmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.11 |
envMonDevCfgTempHighWarningmandatoryr/w | degCInteger32 | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.12 |
envMonDevCfgTempLowWarningmandatoryr/w | degCInteger32 | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.13 |
envMonDevCfgTempHighCriticalmandatoryr/w | degCInteger32 | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.14 |
envMonDevCfgTempLowCriticalmandatoryr/w | degCInteger32 | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.15 |
envMonDevCfgTempOffsetmandatoryr/w | degCEnumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.16 |
envMonDevCfgHumiHighWarningEnmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.17 |
envMonDevCfgHumiLowWarningEnmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.18 |
envMonDevCfgHumiHighCriticalEnmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.19 |
envMonDevCfgLTClosemandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.2 |
envMonDevCfgHumiLowCriticalEnmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.20 |
envMonDevCfgHumiHighWarningmandatoryr/w | 0.1%Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.21 |
envMonDevCfgHumiLowWarningmandatoryr/w | 0.1%Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.22 |
envMonDevCfgHumiHighCriticalmandatoryr/w | 0.1%Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.23 |
envMonDevCfgHumiLowCriticalmandatoryr/w | 0.1%Integer32 | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.24 |
envMonDevCfgHumiOffsetmandatoryr/w | %Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.25 |
envMonDevCfgAlarm1Setupmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.26 |
envMonDevCfgAlarm2Setupmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.27 |
envMonDevCfgTempNamemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.3 |
envMonDevCfgHumiNamemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.4 |
envMonDevCfgAlarm1Namemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.5 |
envMonDevCfgAlarm2Namemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.6 |
envMonDevCfgLocationNamemandatoryr/w | RFC1213-MIBDisplayString | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.7 |
envMonDevCfgTempHighWarningEnmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.8 |
envMonDevCfgTempLowWarningEnmandatoryr/w | Enumeration | .1.3.6.1.4.1.2468.1.6.1.1.9.2.1.9 |
.1.3.6.1.4.1.2468.1.6.1.2 |
Dependencies (9) 5 direct · 4 transitive Show tree and compile order Hide dependency details
Each imported module is resolved in the importing module's source directory first, then through the normal default-variant rules.
Dependency tree
Dependency-first compile order
- RFC-1212rfc
- RFC-1215rfc
- RFC1155-SMIrfc
- SNMPv2-SMIrfc
- SNMPv2-TCrfc
- IANAifType-MIBrfc
- RFC1213-MIBrfc
- SNMPv2-CONFrfc
- UPS-MIBrfc
- USHA-MIBingrasysselected
Notifications / Traps (109)
| Name | OID | Description |
|---|---|---|
.1.3.6.1.4.1.2468.1.6.1.2.0.1 |
INFORMATION: Utility power has been restore.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.10 |
INFORMATION: The testing is going on inverter.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.100 |
WARNING: Temperature High.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.101 |
INFORMATION: Return from Temperature High.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.102 |
WARNING: DC Input Source Over Temperature.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.103 |
INFORMATION: Return from DC Input Source Over Temperature.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.104 |
WARNING: Fan Maintain Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.105 |
INFORMATION: Return from Fan Maintain Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.106 |
WARNING: Bus Capacitance Maintain Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.107 |
INFORMATION: Return from Bus Capacitance Maintain Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.108 |
WARNING: System Over Capacity.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.109 |
INFORMATION: Return from System Over Capacity.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.11 |
INFORMATION: The inverter has enabled bypass.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.12 |
INFORMATION: The inverter is not on Bypass and return to normal status.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.13 |
SEVERE: Communication to the inverter has been lost.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.14 |
INFORMATION: Communication with the inverter has been established.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.15 |
WARNING: The inverter has been given shutdown command.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.16 |
INFORMATION: INV turn off.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.17 |
INFORMATION: INV has entered sleep mode.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.18 |
INFORMATION: The inverter woke up from sleep mode.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.19 |
INFORMATION: The inverter is reboot.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.2 |
WARNING: Utility power not available.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.20 |
INFORMATION: The inverter shutdown process had been cancelled.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.21 |
INFORMATION: The inverter internal temperature return to normal.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.22 |
SEVERE: The inverter temperature is too high.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.23 |
INFORMATION: The inverter load return from overload.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.24 |
SEVERE: The inverter is overload.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.25 |
WARNING: INV DC Input Source Module plug-in.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.26 |
WARNING: INV DC Input Source Module unplug.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.27 |
INFORMATION: The temperature of EMD back to normal from high warning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.28 |
WARNING: The temperature of EMD higher than set warning point.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.29 |
INFORMATION: The temperature of EMD back to normal from low warning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.3 |
INFORMATION: The inverter has return from a low inverter condition.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.30 |
WARNING: The temperature of EMD lower than set warning point.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.31 |
INFORMATION: The temperature of EMD back to warning from high critical.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.32 |
WARNING: The temperature of EMD higher than set critical point.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.33 |
INFORMATION: The temperature of EMD back to warning from low critical.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.34 |
WARNING: The temperature of EMD lower than set critical point.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.35 |
INFORMATION: The humidity of EMD back to normal from high warning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.36 |
WARNING: The humidity of EMD higher than set warning point.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.37 |
INFORMATION: The humidity of EMD back to normal from low warning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.38 |
WARNING: The humidity of EMD lower than set warning point.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.39 |
INFORMATION: The humidity of EMD back to warning from high critical.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.4 |
SEVERE: The inverter batteries are low and will soon be exhausted.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.40 |
WARNING: The humidity of EMD higher than set critical point.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.41 |
INFORMATION: The humidity of EMD back to warning from low critical.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.42 |
WARNING: The humidity of EMD lower than set critical point.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.43 |
INFORMATION: The status of emd alarm-1 back to normal from active.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.44 |
WARNING: The status of emd alarm-1 activated.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.45 |
INFORMATION: The status of emd alarm-2 back to normal from active.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.46 |
WARNING: The status of emd alarm-2 activated.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.47 |
INFORMATION: EMD Communication Success.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.48 |
WARNING: EMD Communication Lose.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.49 |
INFORMATION: EMD log clear.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.5 |
INFORMATION: The inverter is working fine.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.50 |
INFORMATION: EMD Update Success.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.51 |
WARNING: EMD Update Fail.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.52 |
WARNING: Internal warning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.53 |
INFORMATION: Return from Internal warning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.54 |
WARNING: EPO Active.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.55 |
INFORMATION: Return from EPO Active.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.56 |
WARNING: Module Unlock.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.57 |
INFORMATION: Return from Module Unlock.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.58 |
WARNING: Main 1 Neutral loss.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.59 |
INFORMATION: Return from Main 1 Neutral loss.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.6 |
SEVERE: The inverter is not working fine.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.60 |
WARNING: Main 1 phase error.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.61 |
INFORMATION: Return from Main 1 phase error.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.62 |
WARNING: Site fault.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.63 |
INFORMATION: Return from Site fault.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.64 |
WARNING: Bypass Abnormal.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.65 |
INFORMATION: Return from Bypass Abnormal.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.66 |
WARNING: Bypass Phase Error.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.67 |
INFORMATION: Return from Bypass Phase Error.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.68 |
WARNING: DC Input Source Open.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.69 |
INFORMATION: Return from DC Input Source Open.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.7 |
INFORMATION: The inverter is not on inverter power.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.70 |
WARNING: DC Input Source Over Charge.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.71 |
INFORMATION: Return from DC Input Source Over Charge.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.72 |
WARNING: DC Input Source Reverse.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.73 |
INFORMATION: Return from DC Input Source Reverse.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.74 |
WARNING: Overload forewarning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.75 |
INFORMATION: Return from Overload forewarning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.76 |
WARNING: Overload Warning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.77 |
INFORMATION: Return from Overload Warning.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.78 |
WARNING: Fan Lock.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.79 |
INFORMATION: Return from Fan Lock.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.8 |
WARNING: The inverter has switched to inverter backup power.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.80 |
WARNING: Maintain cover is open.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.81 |
INFORMATION: Return from Maintain cover is open.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.82 |
WARNING: Charger fault.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.83 |
INFORMATION: Return from Charger fault.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.84 |
WARNING: Module location error.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.85 |
INFORMATION: Return from Module location error.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.86 |
WARNING: Turn on abnormal.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.87 |
INFORMATION: Return from Turn on abnormal.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.88 |
WARNING: Redundancy loss.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.89 |
INFORMATION: Return from Redundancy loss.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.9 |
INFORMATION: The testing of INV is completed.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.90 |
WARNING: Hot Swap Actived.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.91 |
INFORMATION: Return from Hot Swap Actived.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.92 |
WARNING: DC Input Source Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.93 |
INFORMATION: Return from DC Input Source Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.94 |
WARNING: Inspection Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.95 |
INFORMATION: Return from Inspection Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.96 |
WARNING: Guarantee Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.97 |
INFORMATION: Return from Guarantee Inform.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.98 |
WARNING: Temperature Low.
|
|
.1.3.6.1.4.1.2468.1.6.1.2.0.99 |
INFORMATION: Return from Temperature Low.
|