UPS2-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
8
Rows
8
Columns
54
.1.3.6.1.4.1.52.4.1.1.10.2.1
·
1 row entry
·
6 columns
A list of identification table entries. The number of entries is given by the value of upsNumUPSs.
An entry containing objects for a particular UPS.
Indexes
upsIndex
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsIndex
mandatory
A unique value which identifies a particular UPS.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.1 |
||||||||||||||||||
|
upsName
mandatory
The UPS's name. A maximum of 8 characters may be specified.
This object is initialized to the UPS's model name. |
OctetStringr/w Constraints: range: 0-8 |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.2 |
||||||||||||||||||
|
upsModelType
mandatory
The UPS's base model type.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.3 |
||||||||||||||||||
|
upsFwVersion
mandatory
The UPS's firmware version.
|
OctetString Constraints: range: 0-8 |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.4 |
||||||||||||||||||
|
upsSerialNumber
mandatory
The UPS's serial number as set at the factory.
|
OctetString Constraints: range: 0-16 |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.5 |
||||||||||||||||||
|
upsManufDate
mandatory
The UPS's date of manufacture in the format mm/dd/yy.
|
OctetString Constraints: range: 0-8 |
.1.3.6.1.4.1.52.4.1.1.10.2.1.1.6 |
.1.3.6.1.4.1.52.4.1.1.10.3.1
·
1 row entry
·
9 columns
A list of battery table entries. The number of entries is given by the value of upsNumUPSs.
An entry containing objects for a particular UPS.
Indexes
upsIndex
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsBatteryCapacity
mandatory
The UPS's remaining battery capacity expressed as a percent
of the fully charged condition. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this … |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.1 |
||||||||||||
|
upsBatteryVoltage
mandatory
The UPS's present battery voltage. The value of this object
is the actual voltage * 100 (that is, to determine the actual voltage, divide the value of this object by 100). |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.2 |
||||||||||||
|
upsBatteryTest
mandatory
This object may be written to initiate testing of the UPS's
battery packs. Reading this object will always return a 0. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.3 |
||||||||||||
|
upsBatteryTestResult
mandatory
The result of the last battery test performed.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.4 |
||||||||||||
|
upsRunTimeCalibration
mandatory
This object may be written to initiate or terminate the test
used to calibrate the returned run time value. This test will only run if battery capacity is 100%. Results of this test can be retrieved by upsEstimatedRu… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.5 |
||||||||||||
|
upsEstimatedRunTimeRemaining
mandatory
The UPS's estimated remaining run time in minutes. The UPS
may be queried when operating in the on-line, bypass, or on-battery modes of operation. The run time estimate is based on available battery capacity and outpu… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.6 |
||||||||||||
|
upsTransferCause
mandatory
The reason for the most recent transfer to on-battery
operation. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.7 |
||||||||||||
|
upsBatteryTestTime
mandatory
The frequency of execution of the UPS's automatic battery
test. The test may be run immediately upon startup, upon startup and every 7 days thereafter, upon startup and every 14 days thereafter, or never. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.8 |
||||||||||||
|
upsLowBatteryWarning
mandatory
The interval between activation of the UPS's low battery
alarm warnings and shutdown of the UPS. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.3.1.1.9 |
.1.3.6.1.4.1.52.4.1.1.10.4.1
·
1 row entry
·
6 columns
A list of input table entries. The number of entries is given by the value of upsNumUPSs.
An entry containing objects for a particular UPS.
Indexes
upsIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
upsInputUtilityVoltage
mandatory
The UPS's utility voltage version.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.1 |
||||||||
|
upsInputVoltage
mandatory
The UPS's measured utility input voltage. The value
of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.2 |
||||||||
|
upsInputFailureSensitivity
mandatory
The sensitivity of the UPS to rapid changes in utility
voltage (e.g., blackouts, spikes, or notches) or abnormal changes in utility frequency. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.3 |
||||||||
|
upsInputMaxVoltage
mandatory
The UPS's maximum input voltage recorded since this object
was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.4 |
||||||||
|
upsInputMinVoltage
mandatory
The UPS's minimum input voltage recorded since this object
was last read. The value of this object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.5 |
||||||||
|
upsInputFrequency
mandatory
The UPS's present internal operating frequency in Hz.
The value of this object is the actual frequency * 100 (that is, to determine the actual frequency, divide the value of this object by 100). |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.4.1.1.6 |
.1.3.6.1.4.1.52.4.1.1.10.5.1
·
1 row entry
·
3 columns
A list of output table entries. The number of entries is given by the value of upsNumUPSs.
An entry containing objects for a particular UPS.
Indexes
upsIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
upsOutputVoltage
mandatory
The measured UPS output voltage. The value of this
object is the actual voltage * 10 (that is, to determine the actual voltage, divide the value of this object by 10). |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.5.1.1.1 |
||||||||
|
upsOutputUtilityVoltage
mandatory
The UPS's current on-battery output voltage setting
(valid for 220/230/240 Vac version UPSs only). For other version UPSs, reading this object will always return a 0 and writing this object will have no effect. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.5.1.1.2 |
||||||||
|
upsOutputPower
mandatory
The UPS's output load represented as a percentage of full
rated load in Watts. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object by 1… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.5.1.1.3 |
.1.3.6.1.4.1.52.4.1.1.10.6.1
·
1 row entry
·
3 columns
A list of status table entries. The number of entries is given by the value of upsNumUPSs.
An entry containing objects for a particular UPS.
Indexes
upsIndex
| Column | Syntax | OID |
|---|---|---|
|
upsStatusOperational
mandatory
This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as follows: BIT 7: 1=replace battery condition BIT 6: 1=low battery condition BIT 5: 1=… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.1 |
|
upsStatusFault
mandatory
This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as follows: BIT 7: 1=UPS fault - internal temperature has exceeded nominal limits… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.2 |
|
upsStatusTemp
mandatory
The UPS's present internal operating temperature in degrees
Fahrenheit. The value of this object is the actual temperature * 10 (that is, to determine the actual temperature, divide the value of this object by 10). |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.6.1.1.3 |
.1.3.6.1.4.1.52.4.1.1.10.7.1
·
1 row entry
·
2 columns
A list of configuration table entries. The number of entries is given by the value of upsNumUPSs.
An entry containing objects for a particular UPS.
Indexes
upsIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
upsConfigAlarm
mandatory
The UPS's current audible alarm setting. The alarm
may be set to activate immediately upon utility failure and for low battery condition, to activate 30 seconds after utility failure and immediately upon low battery co… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.7.1.1.1 |
||||||||
|
upsConfigRestoreDefaults
mandatory
This object may be written to force the UPS to restore
the factory default settings for most of the UPS's customizable parameters. Reading this object will always return a 0. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.7.1.1.2 |
.1.3.6.1.4.1.52.4.1.1.10.8.1
·
1 row entry
·
16 columns
A list of external measurement table entries. The number of entries is the number of available UPSs to which External Measurement Units are attached.
An entry containing objects for a particular UPS.
Indexes
upsIndex
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
upsExtMeasFwVersion
mandatory
The External Measurement Unit's firmware version letter.
|
OctetString Constraints: range: 0-1 |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.1 |
||||||||
|
upsExtMeasTemp
mandatory
The local ambient temperature in degrees Fahrenheit as measured
by the External Measurement Unit. The value of this object is the actual temperature * 100 (that is, to determine the actual temperature, divide the value… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.2 |
||||||||
|
upsExtMeasHumidity
mandatory
The local ambient relative humidity in percent as measured
by the External Measurement Unit. The value of this object is the actual humidity * 10 (that is, to determine the actual humidity, divide the value of this obj… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.3 |
||||||||
|
upsExtMeasAlarmStatus
mandatory
This object contains 8 bits of information about the current
alarm status of the External Measurement Unit. The bits are encoded as follows: BIT 7: 1=Upper temperature limit exceeded BIT 6: 1=Lower tem… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.4 |
||||||||
|
upsExtMeasMaxTemp
mandatory
The upper temperature limit at which an alarm will be sent.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.5 |
||||||||
|
upsExtMeasMinTemp
mandatory
The lower temperature limit at which an alarm will be sent.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.6 |
||||||||
|
upsExtMeasMaxHumidity
mandatory
The upper humidity limit at which an alarm will be sent.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.7 |
||||||||
|
upsExtMeasMinHumidity
mandatory
The lower humidity limit at which an alarm will be sent.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.8 |
||||||||
|
upsExtMeasContact1AlarmControl
mandatory
The alarm enable state for the External Measurement Unit's
contact input channel #1. If enabled, an alarm will be sent when contact input channel #1 has changed to abnormal state. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.9 |
||||||||
|
upsExtMeasContact2AlarmControl
mandatory
The alarm enable state for the External Measurement Unit's
contact input channel #2. If enabled, an alarm will be sent when contact input channel #2 has changed to abnormal state. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.10 |
||||||||
|
upsExtMeasContact3AlarmControl
mandatory
The alarm enable state for the External Measurement Unit's
contact input channel #3. If enabled, an alarm will be sent when contact input channel #3 has changed to abnormal state. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.11 |
||||||||
|
upsExtMeasContact4AlarmControl
mandatory
The alarm enable state for the External Measurement Unit's
contact input channel #4. If enabled, an alarm will be sent when contact input channel #4 has changed to abnormal state. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.12 |
||||||||
|
upsExtMeasMaxTempAlarmControl
mandatory
The alarm enable state for the External Measurement Unit's
upper temperature limit. If enabled, an alarm will be sent when the ambient temperature rises above the upper temperature limit. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.13 |
||||||||
|
upsExtMeasMinTempAlarmControl
mandatory
The alarm enable state for the External Measurement Unit's
lower temperature limit. If enabled, an alarm will be sent when the ambient temperature falls below the lower temperature limit. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.14 |
||||||||
|
upsExtMeasMaxHumidityAlarmControl
mandatory
The alarm enable state for the External Measurement Unit's
upper humidity limit. If enabled, an alarm will be sent when the ambient relative humidity rises above the upper humidity limit. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.15 |
||||||||
|
upsExtMeasMinHumidityAlarmControl
mandatory
The alarm enable state for the External Measurement Unit's
lower humidity limit. If enabled, an alarm will be sent when the ambient relative humidity falls below the lower humidity limit. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.8.1.1.16 |
.1.3.6.1.4.1.52.4.1.1.10.9.1
·
1 row entry
·
9 columns
A list of additional functions table entries. The number of entries is the number of available UPSs which are capable of supporting these additional functions.
An entry containing objects for a particular UPS.
Indexes
upsIndex
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
upsAddlFuncsNumBatteryPacks
mandatory
The number of battery pack units connected to the UPS.
|
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.1 |
||||
|
upsAddlFuncsNumBadBatteryPacks
mandatory
The number of bad (faulty) battery pack units connected
to the UPS. |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.2 |
||||
|
upsAddlFuncsOutputCurrent
mandatory
The true rms load current drawn from the UPS. The value
of this object is the actual amperage * 100 (that is, to determine the actual amperage, divide the value of this object by 100). |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.3 |
||||
|
upsAddlFuncsOutputApparentPower
mandatory
The UPS's output load represented as a percentage of full rated
load in Volt-Amps. The value of this object is the actual percentage * 10 (that is, to determine the actual percentage, divide the value of this object … |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.4 |
||||
|
upsAddlFuncsStatusOperational
mandatory
This object contains 8 bits of information about the current
operational status of the UPS. The bits are encoded as follows: BIT 7: 1=UPS ready to power load upon return of normal line or upon… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.5 |
||||
|
upsAddlFuncsStatusFault
mandatory
This object contains 8 bits of information about the current
fault conditions of the UPS. The bits are encoded as follows: BIT 7: reserved for future use BIT 6: reserved for future use BIT 5: reserved… |
Integer32 Textual Convention: COPS-PR-SPPIInteger32 Integer32Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.6 |
||||
|
upsAddlFuncsConfigPassword
mandatory
The password that controls access to the UPS's LCD display.
A maximum of 4 characters may be entered. |
OctetStringr/w | .1.3.6.1.4.1.52.4.1.1.10.9.1.1.7 |
||||
|
upsAddlFuncsConfigDisable
mandatory
This object may be written to immediately shut down the
UPS, requiring a manual reset. Reading this object will always return a 0. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.8 |
||||
|
upsAddlFuncsConfigBypass
mandatory
This object may be written to cause the UPS to transfer
to or from the bypass mode. Reading this object will always return a 0. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.52.4.1.1.10.9.1.1.9 |