Sentry4-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
40
Rows
40
Columns
222
.1.3.6.1.4.1.1718.4.1.2.2 · 1 row entry · 19 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4UnitConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4UnitConfigTable'
Unit configuration table.
st4UnitConfigEntry row .1.3.6.1.4.1.1718.4.1.2.2.1
Configuration objects for a particular unit.
Indexes
Column Syntax OID
Unit index. A=1, B=2, C=3, D=4, E=5, F=6.
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.1718.4.1.2.2.1.1
The internal ID of the unit. Format=A.
OctetString
Constraints:
range: 1-1
.1.3.6.1.4.1.1718.4.1.2.2.1.2
The name of the unit.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.2.2.1.3
The product serial number of the unit.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.2.2.1.4
The model of the unit.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.2.2.1.5
The asset tag of the unit.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.2.2.1.6
The type of the unit.
Enumeration
Enumerated Values:
0primary
1link
2controller
3emcu
.1.3.6.1.4.1.1718.4.1.2.2.1.7
The capabilities of the unit.
Bits
Enumerated Values:
0dc
1phase3
2wye
3delta
.1.3.6.1.4.1.1718.4.1.2.2.1.8
The product manufacture date in YYYY-MM-DD (ISO 8601 format) of
the unit.
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.1718.4.1.2.2.1.9
The orientation of all displays in the unit.
Enumerationr/w
Enumerated Values:
0normal
1inverted
2auto
.1.3.6.1.4.1.1718.4.1.2.2.1.20
The sequencing order of all outlets in the unit.
Enumerationr/w
Enumerated Values:
0normal
1reversed
.1.3.6.1.4.1.1718.4.1.2.2.1.21
The display order in the user interfaces of all outlets in the
unit.
Enumerationr/w
Enumerated Values:
0normal
1reversed
.1.3.6.1.4.1.1718.4.1.2.2.1.22
The number of power input cords into the unit.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.2.2.1.30
The number of external temperature sensors supported by the unit.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.4.1.2.2.1.31
The number of external humidity sensors supported by the unit.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.4.1.2.2.1.32
The number of external water sensors supported by the unit.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.1718.4.1.2.2.1.33
The number of external contact closure sensors supported by the
unit.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.2.2.1.34
The number of analog-to-digital converter sensors supported by the
unit.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.1718.4.1.2.2.1.35
The number of fan sensors supported by the unit.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.2.2.1.36
.1.3.6.1.4.1.1718.4.1.2.3 · 1 row entry · 1 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4UnitMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4UnitMonitorTable'
Unit monitor table.
st4UnitMonitorEntry row .1.3.6.1.4.1.1718.4.1.2.3.1
Objects to monitor for a particular unit.
Indexes
Column Syntax OID
The status of the unit.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.2.3.1.1
.1.3.6.1.4.1.1718.4.1.2.4 · 1 row entry · 1 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4UnitEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4UnitEventConfigTable'
Unit event configuration table.
st4UnitEventConfigEntry row .1.3.6.1.4.1.1718.4.1.2.4.1
Event configuration objects for a particular unit.
Indexes
Column Syntax OID
The notification methods enabled for unit events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.2.4.1.1
.1.3.6.1.4.1.1718.4.1.3.2 · 1 row entry · 16 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4InputCordConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4InputCordConfigTable'
Input cord configuration table.
st4InputCordConfigEntry row .1.3.6.1.4.1.1718.4.1.3.2.1
Configuration objects for a particular input cord.
Column Syntax OID
Input cord index. A=1, B=2, C=3, D=4.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.1718.4.1.3.2.1.1
The internal ID of the input cord. Format=AA.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.3.2.1.2
The name of the input cord.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.3.2.1.3
The type of plug on the input cord, or socket for the input cord.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.3.2.1.6
The user-configured nominal voltage of the input cord in tenth
Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.3.2.1.7
The factory-set minimum allowed for the user-configured nominal
voltage of the input cord in Volts.
VoltsInteger32
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.3.2.1.8
The factory-set maximum allowed for the user-configured nominal
voltage of the input cord in Volts.
VoltsInteger32
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.3.2.1.9
The user-configured current capacity of the input cord in Amps.
AmpsInteger32r/w
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.3.2.1.10
The factory-set maximum allowed for the user-configured current
capacity of the input cord in Amps.
AmpsInteger32
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.3.2.1.11
The power capacity of the input cord in Volt-Amps. For DC
products, this is identical to power capacity in Watts.
Volt-AmpsInteger32
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.2.1.12
The user-configured estimated nominal power factor of the input
cord in hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.2.1.13
The number of current-carrying lines in the input cord.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.3.2.1.20
The number of active phases from the lines in the input cord.
Integer32
Constraints:
range: 0-6
.1.3.6.1.4.1.1718.4.1.3.2.1.21
The number of over-current protectors downstream from the input
cord.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.1718.4.1.3.2.1.22
The number of branches downstream from the input cord.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.1718.4.1.3.2.1.23
The number of outlets powered from the input cord.
Integer32
Constraints:
range: 0-128
.1.3.6.1.4.1.1718.4.1.3.2.1.24
.1.3.6.1.4.1.1718.4.1.3.3 · 1 row entry · 13 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4InputCordMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4InputCordMonitorTable'
Input cord monitor table.
st4InputCordMonitorEntry row .1.3.6.1.4.1.1718.4.1.3.3.1
Objects to monitor for a particular input cord.
Column Syntax OID
The on/off state of the input cord.
DeviceState
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.3.3.1.1
The status of the input cord.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.2
The measured active power of the input cord in Watts.
WattsInteger32
Constraints:
range: -1-50000
.1.3.6.1.4.1.1718.4.1.3.3.1.3
The status of the measured active power of the input cord.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.4
The measured apparent power of the input cord in Volt-Amps.
Volt-AmpsInteger32
Constraints:
range: -1-50000
.1.3.6.1.4.1.1718.4.1.3.3.1.5
The status of the measured apparent power of the input cord.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.6
The amount of the input cord power capacity used in tenth percent.
For AC products, this is the ratio of the apparent power to the
power capacity. For DC products, this is the ratio of the active
power to the power cap…
tenth percentInteger32
Constraints:
range: -1-1200
.1.3.6.1.4.1.1718.4.1.3.3.1.7
The measured power factor of the input cord in hundredths.
hundredthsInteger32
Constraints:
range: -1-100
.1.3.6.1.4.1.1718.4.1.3.3.1.8
The status of the measured power factor of the input cord.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.9
The total energy consumption of loads through the input cord in
tenth Kilowatt-Hours.
tenth Kilowatt-HoursInteger32
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.1718.4.1.3.3.1.10
The frequency of the input cord voltage in tenth Hertz.
tenth HertzInteger32
Constraints:
range: -1-1000
.1.3.6.1.4.1.1718.4.1.3.3.1.11
The current imbalance on the lines of the input cord in tenth
percent.
tenth percentInteger32
Constraints:
range: -1-2000
.1.3.6.1.4.1.1718.4.1.3.3.1.12
The status of the current imbalance on the lines of the input
cord.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.3.3.1.13
.1.3.6.1.4.1.1718.4.1.3.4 · 1 row entry · 13 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4InputCordEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4InputCordEventConfigTable'
Input cord event configuration table.
st4InputCordEventConfigEntry row .1.3.6.1.4.1.1718.4.1.3.4.1
Event configuration objects for a particular input cord.
Column Syntax OID
The notification methods enabled for input cord events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.3.4.1.1
The active power low alarm threshold of the input cord in Watts.
WattsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.2
The active power low warning threshold of the input cord in
Watts.
WattsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.3
The active power high warning threshold of the input cord in
Watts.
WattsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.4
The active power high alarm threshold of the input cord in Watts.
WattsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.5
The apparent power low alarm threshold of the input cord in
Volt-Amps.
Volt-AmpsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.6
The apparent power low warning threshold of the input cord in
Volt-Amps.
Volt-AmpsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.7
The apparent power high warning threshold of the input cord in
Volt-Amps.
Volt-AmpsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.8
The apparent power high alarm threshold of the input cord in
Volt-Amps.
Volt-AmpsInteger32r/w
Constraints:
range: 0-50000
.1.3.6.1.4.1.1718.4.1.3.4.1.9
The power factor low alarm threshold of the input cord in
hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.4.1.10
The power factor low warning threshold of the input cord in
hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.4.1.11
The 3 phase out-of-balance high warning threshold of the input
cord in percent.
percentInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.4.1.12
The 3 phase out-of-balance high alarm threshold of the input cord
in percent.
percentInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.3.4.1.13
.1.3.6.1.4.1.1718.4.1.4.2 · 1 row entry · 4 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4LineConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4LineConfigTable'
Line configuration table.
st4LineConfigEntry row .1.3.6.1.4.1.1718.4.1.4.2.1
Configuration objects for a particular line.
Column Syntax OID
Line index. L1=1, L2=2, L3=3, N=4.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.1718.4.1.4.2.1.1
The internal ID of the line. Format=AAN.
OctetString
Constraints:
range: 3-3
.1.3.6.1.4.1.1718.4.1.4.2.1.2
The system label assigned to the line for identification.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.4.2.1.4
The current capacity of the line in Amps.
AmpsInteger32
Constraints:
range: 0-600
.1.3.6.1.4.1.1718.4.1.4.2.1.6
.1.3.6.1.4.1.1718.4.1.4.3 · 1 row entry · 5 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4LineMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4LineMonitorTable'
Line monitor table.
st4LineMonitorEntry row .1.3.6.1.4.1.1718.4.1.4.3.1
Objects to monitor for a particular line.
Column Syntax OID
The on/off state of the line.
DeviceState
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.4.3.1.1
The status of the line.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.4.3.1.2
The measured current on the line in hundredth Amps.
hundredth AmpsInteger32
Constraints:
range: -1-60000
.1.3.6.1.4.1.1718.4.1.4.3.1.3
The status of the measured current on the line.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.4.3.1.4
The amount of the line current capacity used in tenth percent.
tenth percentInteger32
Constraints:
range: -1-1200
.1.3.6.1.4.1.1718.4.1.4.3.1.5
.1.3.6.1.4.1.1718.4.1.4.4 · 1 row entry · 5 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4LineEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4LineEventConfigTable'
Line event configuration table.
st4LineEventConfigEntry row .1.3.6.1.4.1.1718.4.1.4.4.1
Event configuration objects for a particular line.
Column Syntax OID
The notification methods enabled for line events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.4.4.1.1
The current low alarm threshold of the line in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.4.4.1.2
The current low warning threshold of the line in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.4.4.1.3
The current high warning threshold of the line in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.4.4.1.4
The current high alarm threshold of the line in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.4.4.1.5
.1.3.6.1.4.1.1718.4.1.5.2 · 1 row entry · 6 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4PhaseConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4PhaseConfigTable'
Phase configuration table.
st4PhaseConfigEntry row .1.3.6.1.4.1.1718.4.1.5.2.1
Configuration objects for a particular phase.
Column Syntax OID
Phase index. Three-phase AC Wye: L1-N=1, L2-N=2, L3-N=3;
Three-phase AC Delta: L1-L2=1, L2-L3=2, L3-L1=3; Single Phase:
L1-R=1; DC: L1-R=1; Three-phase AC Wye & Delta: L1-N=1, L2-N=2,
L3-N=3, L1-L2=4, L2-L3=5; L3-L1=6.
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.1718.4.1.5.2.1.1
The internal ID of the phase. Format=AAN.
OctetString
Constraints:
range: 3-3
.1.3.6.1.4.1.1718.4.1.5.2.1.2
The system label assigned to the phase for identification.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.5.2.1.4
The nominal voltage of the phase in tenth Volts.
tenth VoltsInteger32
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.2.1.6
The number of branches downstream from the phase.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.1718.4.1.5.2.1.20
The number of outlets powered from the phase.
Integer32
Constraints:
range: 0-128
.1.3.6.1.4.1.1718.4.1.5.2.1.21
.1.3.6.1.4.1.1718.4.1.5.3 · 1 row entry · 13 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4PhaseMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4PhaseMonitorTable'
Phase monitor table.
st4PhaseMonitorEntry row .1.3.6.1.4.1.1718.4.1.5.3.1
Objects to monitor for a particular phase.
Column Syntax OID
The on/off state of the phase.
DeviceState
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.5.3.1.1
The status of the phase.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.5.3.1.2
The measured voltage on the phase in tenth Volts.
tenth VoltsInteger32
Constraints:
range: -1-6000
.1.3.6.1.4.1.1718.4.1.5.3.1.3
The status of the measured voltage on the phase.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.5.3.1.4
The deviation from the nominal voltage on the phase in tenth
percent.
tenth percentInteger32
Constraints:
range: -1000-1000
.1.3.6.1.4.1.1718.4.1.5.3.1.5
The measured current on the phase in hundredth Amps.
hundredth AmpsInteger32
Constraints:
range: -1-30000
.1.3.6.1.4.1.1718.4.1.5.3.1.6
The measured crest factor of the current waveform on the phase in
tenths.
tenthsInteger32
Constraints:
range: -1-250
.1.3.6.1.4.1.1718.4.1.5.3.1.7
The measured active power on the phase in Watts.
WattsInteger32
Constraints:
range: -1-25000
.1.3.6.1.4.1.1718.4.1.5.3.1.8
The measured apparent power on the phase in Volt-Amps.
Volt-AmpsInteger32
Constraints:
range: -1-25000
.1.3.6.1.4.1.1718.4.1.5.3.1.9
The measured power factor on the phase in hundredths.
hundredthsInteger32
Constraints:
range: -1-100
.1.3.6.1.4.1.1718.4.1.5.3.1.10
The status of the measured power factor on the phase.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.5.3.1.11
The status of the measured reactance of the phase.
Enumeration
Enumerated Values:
0unknown
1capacitive
2inductive
3resistive
.1.3.6.1.4.1.1718.4.1.5.3.1.12
The total energy consumption of loads through the phase in tenth
Kilowatt-Hours.
tenth Kilowatt-HoursInteger32
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.1718.4.1.5.3.1.13
.1.3.6.1.4.1.1718.4.1.5.4 · 1 row entry · 7 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4PhaseEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4PhaseEventConfigTable'
Phase event configuration table.
st4PhaseEventConfigEntry row .1.3.6.1.4.1.1718.4.1.5.4.1
Event configuration objects for a particular phase.
Column Syntax OID
The notification methods enabled for phase events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.5.4.1.1
The current low alarm threshold of the phase in tenth Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.4.1.2
The current low warning threshold of the phase in tenth Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.4.1.3
The current high warning threshold of the phase in tenth Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.4.1.4
The current high alarm threshold of the phase in tenth Volts.
tenth VoltsInteger32r/w
Constraints:
range: 0-6000
.1.3.6.1.4.1.1718.4.1.5.4.1.5
The low power factor alarm threshold of the phase in hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.5.4.1.6
The low power factor warning threshold of the phase in
hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.5.4.1.7
.1.3.6.1.4.1.1718.4.1.6.2 · 1 row entry · 8 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4OcpConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4OcpConfigTable'
Over-current protector configuration table.
st4OcpConfigEntry row .1.3.6.1.4.1.1718.4.1.6.2.1
Configuration objects for a particular over-current protector.
Column Syntax OID
Over-current protector index.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.1718.4.1.6.2.1.1
The internal ID of the over-current protector. Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.6.2.1.2
The system label assigned to the over-current protector for
identification.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.6.2.1.4
The type of over-current protector.
Enumeration
Enumerated Values:
0fuse
1breaker
.1.3.6.1.4.1.1718.4.1.6.2.1.6
The user-configured current capacity of the over-current protector
in Amps.
AmpsInteger32r/w
Constraints:
range: 0-125
.1.3.6.1.4.1.1718.4.1.6.2.1.7
The factory-set maximum allowed for the user-configured current
capacity of the over-current protector in Amps.
AmpsInteger32
Constraints:
range: 0-125
.1.3.6.1.4.1.1718.4.1.6.2.1.8
The number of branches downstream from the over-current
protector.
Integer32
Constraints:
range: 0-12
.1.3.6.1.4.1.1718.4.1.6.2.1.20
The number of outlets powered from the over-current protector.
Integer32
Constraints:
range: 0-128
.1.3.6.1.4.1.1718.4.1.6.2.1.21
.1.3.6.1.4.1.1718.4.1.6.3 · 1 row entry · 1 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4OcpMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4OcpMonitorTable'
Over-current protector monitor table.
st4OcpMonitorEntry row .1.3.6.1.4.1.1718.4.1.6.3.1
Objects to monitor for a particular over-current protector.
Column Syntax OID
The status of the over-current protector.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.6.3.1.1
.1.3.6.1.4.1.1718.4.1.6.4 · 1 row entry · 1 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4OcpEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4OcpEventConfigTable'
Over-current protector event configuration table.
st4OcpEventConfigEntry row .1.3.6.1.4.1.1718.4.1.6.4.1
Event configuration objects for a particular over-current
protector.
Column Syntax OID
The notification methods enabled for over-current protector
events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.6.4.1.1
.1.3.6.1.4.1.1718.4.1.7.2 · 1 row entry · 7 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4BranchConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4BranchConfigTable'
Branch configuration table.
st4BranchConfigEntry row .1.3.6.1.4.1.1718.4.1.7.2.1
Configuration objects for a particular branch.
Column Syntax OID
Branch index.
Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.1718.4.1.7.2.1.1
The internal ID of the branch. Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.7.2.1.2
The system label assigned to the branch for identification.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.7.2.1.4
The current capacity of the branch in Amps.
AmpsInteger32
Constraints:
range: 0-125
.1.3.6.1.4.1.1718.4.1.7.2.1.6
The internal ID of the phase powering this branch.
Format=AAN.
OctetString
Constraints:
range: 3-3
.1.3.6.1.4.1.1718.4.1.7.2.1.20
The internal ID of the over-current protector powering this
outlet. Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.7.2.1.21
The number of outlets powered from the branch.
Integer32
Constraints:
range: 0-128
.1.3.6.1.4.1.1718.4.1.7.2.1.30
.1.3.6.1.4.1.1718.4.1.7.3 · 1 row entry · 5 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4BranchMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4BranchMonitorTable'
Branch monitor table.
st4BranchMonitorEntry row .1.3.6.1.4.1.1718.4.1.7.3.1
Objects to monitor for a particular branch.
Column Syntax OID
The on/off state of the branch.
DeviceState
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.7.3.1.1
The status of the branch.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.7.3.1.2
The measured current on the branch in hundredth Amps.
hundredth AmpsInteger32
Constraints:
range: -1-12500
.1.3.6.1.4.1.1718.4.1.7.3.1.3
The status of the measured current on the branch.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.7.3.1.4
The amount of the branch current capacity used in tenth percent.
tenth percentInteger32
Constraints:
range: -1-1200
.1.3.6.1.4.1.1718.4.1.7.3.1.5
.1.3.6.1.4.1.1718.4.1.7.4 · 1 row entry · 5 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4BranchEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4BranchEventConfigTable'
Branch event configuration table.
st4BranchEventConfigEntry row .1.3.6.1.4.1.1718.4.1.7.4.1
Event configuration objects for a particular branch.
Column Syntax OID
The notification methods enabled for branch events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.7.4.1.1
The current low alarm threshold of the branch in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.7.4.1.2
The current low warning threshold of the branch in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.7.4.1.3
The current high warning threshold of the branch in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.7.4.1.4
The current high alarm threshold of the branch in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.7.4.1.5
.1.3.6.1.4.1.1718.4.1.8.2 · 1 row entry · 13 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4OutletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4OutletConfigTable'
Outlet configuration table.
st4OutletConfigEntry row .1.3.6.1.4.1.1718.4.1.8.2.1
Configuration objects for a particular outlet.
Column Syntax OID
Outlet index.
Integer32
Constraints:
range: 1-128
.1.3.6.1.4.1.1718.4.1.8.2.1.1
The internal ID of the outlet. Format=AAN[N[N]].
OctetString
Constraints:
range: 3-5
.1.3.6.1.4.1.1718.4.1.8.2.1.2
The name of the outlet.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.8.2.1.3
The capabilities of the outlet.
Bits
Enumerated Values:
0switched
1pops
.1.3.6.1.4.1.1718.4.1.8.2.1.5
The socket type of the outlet.
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.8.2.1.6
The current capacity of the outlet in Amps.
AmpsInteger32
Constraints:
range: 0-125
.1.3.6.1.4.1.1718.4.1.8.2.1.7
The power capacity of the outlet in Volt-Amps. For DC products,
this is identical to power capacity in Watts.
Volt-AmpsInteger32
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.2.1.8
The manually-selected or automatically-detected socket adapter
of the outlet.
Enumerationr/w
Enumerated Values:
0none
1c13
2c19
.1.3.6.1.4.1.1718.4.1.8.2.1.9
The wakeup state of the outlet.
Enumerationr/w
Enumerated Values:
0on
1off
2last
.1.3.6.1.4.1.1718.4.1.8.2.1.20
The post-on delay of the outlet in seconds.
secondsInteger32r/w
Constraints:
range: 0-900
.1.3.6.1.4.1.1718.4.1.8.2.1.21
The internal ID of the phase powering this outlet.
Format=AAN.
OctetString
Constraints:
range: 3-3
.1.3.6.1.4.1.1718.4.1.8.2.1.30
The internal ID of the over-current protector powering this
outlet. Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.8.2.1.31
The internal ID of the branch powering this outlet.
Format=AAN[N].
OctetString
Constraints:
range: 3-4
.1.3.6.1.4.1.1718.4.1.8.2.1.32
.1.3.6.1.4.1.1718.4.1.8.3 · 1 row entry · 14 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4OutletMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4OutletMonitorTable'
Outlet monitor table.
st4OutletMonitorEntry row .1.3.6.1.4.1.1718.4.1.8.3.1
Objects to monitor for a particular outlet.
Column Syntax OID
The on/off state of the outlet.
DeviceState
Type Values:
0unknown
1on
2off
.1.3.6.1.4.1.1718.4.1.8.3.1.1
The status of the outlet.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.8.3.1.2
The measured current on the outlet in hundredth Amps.
hundredth AmpsInteger32
Constraints:
range: -1-12500
.1.3.6.1.4.1.1718.4.1.8.3.1.3
The status of the measured current on the outlet.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.8.3.1.4
The amount of the outlet current capacity used in tenth percent.
tenth percentInteger32
Constraints:
range: -1-1200
.1.3.6.1.4.1.1718.4.1.8.3.1.5
The measured voltage of the outlet in tenth Volts.
tenth VoltsInteger32
Constraints:
range: -1-6000
.1.3.6.1.4.1.1718.4.1.8.3.1.6
The measured active power of the outlet in Watts.
WattsInteger32
Constraints:
range: -1-10000
.1.3.6.1.4.1.1718.4.1.8.3.1.7
The status of the measured active power of the outlet.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.8.3.1.8
The measured apparent power of the outlet in Volt-Amps.
Volt-AmpsInteger32
Constraints:
range: -1-10000
.1.3.6.1.4.1.1718.4.1.8.3.1.9
The measured power factor of the outlet in hundredths.
hundredthsInteger32
Constraints:
range: -1-100
.1.3.6.1.4.1.1718.4.1.8.3.1.10
The status of the measured power factor of the outlet.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.8.3.1.11
The measured crest factor of the outlet in tenths.
tenthsInteger32
Constraints:
range: -1-250
.1.3.6.1.4.1.1718.4.1.8.3.1.12
The status of the measured reactance of the outlet.
Enumeration
Enumerated Values:
0unknown
1capacitive
2inductive
3resistive
.1.3.6.1.4.1.1718.4.1.8.3.1.13
The total energy consumption of the device plugged into the outlet
in Watt-Hours.
Watt-HoursInteger32
Constraints:
range: -1-2147483647
.1.3.6.1.4.1.1718.4.1.8.3.1.14
.1.3.6.1.4.1.1718.4.1.8.4 · 1 row entry · 11 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4OutletEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4OutletEventConfigTable'
Outlet event configuration table.
st4OutletEventConfigEntry row .1.3.6.1.4.1.1718.4.1.8.4.1
Event configuration objects for a particular outlet.
Column Syntax OID
The notification methods enabled for outlet events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.8.4.1.1
The current low alarm threshold of the outlet in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.8.4.1.2
The current low warning threshold of the outlet in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.8.4.1.3
The current high warning threshold of the outlet in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.8.4.1.4
The current high alarm threshold of the outlet in tenth Amps.
tenth AmpsInteger32r/w
Constraints:
range: 0-1250
.1.3.6.1.4.1.1718.4.1.8.4.1.5
The active power low alarm threshold of the outlet in Watts.
WattsInteger32r/w
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.4.1.6
The active power low warning threshold of the outlet in Watts.
WattsInteger32r/w
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.4.1.7
The active power high warning threshold of the outlet in Watts.
WattsInteger32r/w
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.4.1.8
The active power high alarm threshold of the outlet in Watts.
WattsInteger32r/w
Constraints:
range: 0-10000
.1.3.6.1.4.1.1718.4.1.8.4.1.9
The low power factor alarm threshold of the outlet in hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.8.4.1.10
The low power factor warning threshold of the outlet in
hundredths.
hundredthsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.8.4.1.11
.1.3.6.1.4.1.1718.4.1.8.5 · 1 row entry · 2 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4OutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4OutletControlTable'
Outlet control table.
st4OutletControlEntry row .1.3.6.1.4.1.1718.4.1.8.5.1
Objects for control of a particular outlet.
Column Syntax OID
The control state of the outlet.
Enumeration
Enumerated Values:
0notSet
1fixedOn
2idleOff
3idleOn
4wakeOff
5wakeOn
6ocpOff
7ocpOn
8pendOn
9pendOff
10off
11on
12reboot
13shutdown
14lockedOff
15lockedOn
16eventOff
17eventOn
18eventReboot
19eventShutdown
.1.3.6.1.4.1.1718.4.1.8.5.1.1
An action to change the control state of the outlet, or to queue
an action.
Enumerationr/w
Enumerated Values:
0none
1on
2off
3reboot
4queueOn
5queueOff
6queueReboot
.1.3.6.1.4.1.1718.4.1.8.5.1.2
.1.3.6.1.4.1.1718.4.1.9.2 · 1 row entry · 5 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4TempSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4TempSensorConfigTable'
Temperature sensor configuration table.
st4TempSensorConfigEntry row .1.3.6.1.4.1.1718.4.1.9.2.1
Configuration objects for a particular temperature sensor.
Column Syntax OID
Temperature sensor index.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.4.1.9.2.1.1
The internal ID of the temperature sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.9.2.1.2
The name of the temperature sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.9.2.1.3
The minimum temperature limit of the sensor in degrees, using the
scale selected by st4TempSensorScale.
degreesInteger32
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.2.1.4
The maximum temperature limit of the sensor in degrees, using the
scale selected by st4TempSensorScale.
degreesInteger32
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.2.1.5
.1.3.6.1.4.1.1718.4.1.9.3 · 1 row entry · 2 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4TempSensorMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4TempSensorMonitorTable'
Temperature sensor monitor table.
st4TempSensorMonitorEntry row .1.3.6.1.4.1.1718.4.1.9.3.1
Objects to monitor for a particular temperature sensor.
Column Syntax OID
The measured temperature on the sensor in tenth degrees using the
scale selected by st4TempSensorScale. -410 means the temperature
reading is invalid.
tenth degreesInteger32
Constraints:
range: -410-2540
.1.3.6.1.4.1.1718.4.1.9.3.1.1
The status of the temperature sensor.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.9.3.1.2
.1.3.6.1.4.1.1718.4.1.9.4 · 1 row entry · 5 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4TempSensorEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4TempSensorEventConfigTable'
Temperature sensor event configuration table.
st4TempSensorEventConfigEntry row .1.3.6.1.4.1.1718.4.1.9.4.1
Event configuration objects for a particular temperature sensor.
Column Syntax OID
The notification methods enabled for temperature sensor events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.9.4.1.1
The low alarm threshold of the temperature sensor in degrees.
degreesInteger32r/w
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.4.1.2
The low warning threshold of the temperature sensor in degrees.
degreesInteger32r/w
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.4.1.3
The high warning threshold of the temperature sensor in degrees.
degreesInteger32r/w
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.4.1.4
The high alarm threshold of the temperature sensor in degrees.
degreesInteger32r/w
Constraints:
range: -40-253
.1.3.6.1.4.1.1718.4.1.9.4.1.5
.1.3.6.1.4.1.1718.4.1.10.2 · 1 row entry · 3 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4HumidSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4HumidSensorConfigTable'
Humidity sensor configuration table.
st4HumidSensorConfigEntry row .1.3.6.1.4.1.1718.4.1.10.2.1
Configuration objects for a particular humidity sensor.
Column Syntax OID
Humidity sensor index.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.1718.4.1.10.2.1.1
The internal ID of the humidity sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.10.2.1.2
The name of the humidity sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.10.2.1.3
.1.3.6.1.4.1.1718.4.1.10.3 · 1 row entry · 2 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4HumidSensorMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4HumidSensorMonitorTable'
Humidity sensor monitor table.
st4HumidSensorMonitorEntry row .1.3.6.1.4.1.1718.4.1.10.3.1
Objects to monitor for a particular humidity sensor.
Column Syntax OID
The measured humidity on the sensor in percentage relative
humidity.
percentage relative humidityInteger32
Constraints:
range: -1-100
.1.3.6.1.4.1.1718.4.1.10.3.1.1
The status of the humidity sensor.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.10.3.1.2
.1.3.6.1.4.1.1718.4.1.10.4 · 1 row entry · 5 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4HumidSensorEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4HumidSensorEventConfigTable'
Humidity sensor event configuration table.
st4HumidSensorEventConfigEntry row .1.3.6.1.4.1.1718.4.1.10.4.1
Event configuration objects for a particular humidity sensor.
Column Syntax OID
The notification methods enabled for humidity sensor events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.10.4.1.1
The low alarm threshold of the humidity sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.10.4.1.2
The low warning threshold of the humidity sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.10.4.1.3
The high warning threshold of the humidity sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.10.4.1.4
The high alarm threshold of the humidity sensor in percentage
relative humidity.
percentage relative humidityInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.1718.4.1.10.4.1.5
.1.3.6.1.4.1.1718.4.1.11.2 · 1 row entry · 3 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4WaterSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4WaterSensorConfigTable'
Water sensor configuration table.
st4WaterSensorConfigEntry row .1.3.6.1.4.1.1718.4.1.11.2.1
Configuration objects for a particular water sensor.
Column Syntax OID
Water sensor index.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.1718.4.1.11.2.1.1
The internal ID of the water sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.11.2.1.2
The name of the water sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.11.2.1.3
.1.3.6.1.4.1.1718.4.1.11.3 · 1 row entry · 1 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4WaterSensorMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4WaterSensorMonitorTable'
Water sensor monitor table.
st4WaterSensorMonitorEntry row .1.3.6.1.4.1.1718.4.1.11.3.1
Objects to monitor for a particular water sensor.
Column Syntax OID
The status of the water sensor.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.11.3.1.1
.1.3.6.1.4.1.1718.4.1.11.4 · 1 row entry · 1 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4WaterSensorEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4WaterSensorEventConfigTable'
Water sensor event configuration table.
st4WaterSensorEventConfigEntry row .1.3.6.1.4.1.1718.4.1.11.4.1
Event configuration objects for a particular water sensor.
Column Syntax OID
The notification methods enabled for water sensor events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.11.4.1.1
.1.3.6.1.4.1.1718.4.1.12.2 · 1 row entry · 3 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4CcSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4CcSensorConfigTable'
Contact closure sensor configuration table.
st4CcSensorConfigEntry row .1.3.6.1.4.1.1718.4.1.12.2.1
Configuration objects for a particular contact closure sensor.
Column Syntax OID
Contact closure sensor index.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.12.2.1.1
The internal ID of the contact closure sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.12.2.1.2
The name of the contact closure sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.12.2.1.3
.1.3.6.1.4.1.1718.4.1.12.3 · 1 row entry · 1 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4CcSensorMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4CcSensorMonitorTable'
Contact closure sensor monitor table.
st4CcSensorMonitorEntry row .1.3.6.1.4.1.1718.4.1.12.3.1
Objects to monitor for a particular contact closure sensor.
Column Syntax OID
The status of the contact closure.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.12.3.1.1
.1.3.6.1.4.1.1718.4.1.12.4 · 1 row entry · 1 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4CcSensorEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4CcSensorEventConfigTable'
Contact closure sensor event configuration table.
st4CcSensorEventConfigEntry row .1.3.6.1.4.1.1718.4.1.12.4.1
Event configuration objects for a particular contact closure
sensor.
Column Syntax OID
The notification methods enabled for contact closure sensor
events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.12.4.1.1
.1.3.6.1.4.1.1718.4.1.13.2 · 1 row entry · 3 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4AdcSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4AdcSensorConfigTable'
Analog-to-digital converter sensor configuration table.
st4AdcSensorConfigEntry row .1.3.6.1.4.1.1718.4.1.13.2.1
Configuration objects for a particular analog-to-digital
converter sensor.
Column Syntax OID
Analog-to-digital converter sensor index.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.1718.4.1.13.2.1.1
The internal ID of the analog-to-digital converter sensor.
Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.13.2.1.2
The name of the analog-to-digital converter sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.13.2.1.3
.1.3.6.1.4.1.1718.4.1.13.3 · 1 row entry · 2 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4AdcSensorMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4AdcSensorMonitorTable'
Analog-to-digital converter sensor monitor table.
st4AdcSensorMonitorEntry row .1.3.6.1.4.1.1718.4.1.13.3.1
Objects to monitor for a particular analog-to-digital converter
sensor.
Column Syntax OID
The 8-bit value from the analog-to-digital converter sensor.
Integer32
Constraints:
range: -1-255
.1.3.6.1.4.1.1718.4.1.13.3.1.1
The status of the analog-to-digital converter sensor.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.13.3.1.2
.1.3.6.1.4.1.1718.4.1.13.4 · 1 row entry · 5 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4AdcSensorEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4AdcSensorEventConfigTable'
Analog-to-digital converter sensor event configuration table.
st4AdcSensorEventConfigEntry row .1.3.6.1.4.1.1718.4.1.13.4.1
Event configuration objects for a particular
analog-to-digital converter sensor.
Column Syntax OID
The notification methods enabled for analog-to-digital converter
sensor events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.13.4.1.1
The 8-bit value for the low alarm threshold of the
analog-to-digital converter sensor.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.4.1.13.4.1.2
The 8-bit value for the low warning threshold of the
analog-to-digital converter sensor.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.4.1.13.4.1.3
The 8-bit value for the high warning threshold of the
analog-to-digital converter sensor.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.4.1.13.4.1.4
The 8-bit value for the high alarm threshold of the
analog-to-digital converter sensor.
Integer32r/w
Constraints:
range: 0-255
.1.3.6.1.4.1.1718.4.1.13.4.1.5
.1.3.6.1.4.1.1718.4.1.14.2 · 1 row entry · 3 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4FanSensorConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4FanSensorConfigTable'
Fan sensor configuration table.
st4FanSensorConfigEntry row .1.3.6.1.4.1.1718.4.1.14.2.1
Configuration objects for a particular fan sensor.
Column Syntax OID
Fan sensor index.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.1718.4.1.14.2.1.1
The internal ID of the fan sensor. Format=AN.
OctetString
Constraints:
range: 2-2
.1.3.6.1.4.1.1718.4.1.14.2.1.2
The name of the fan sensor.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.1718.4.1.14.2.1.3
.1.3.6.1.4.1.1718.4.1.14.3 · 1 row entry · 2 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4FanSensorMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4FanSensorMonitorTable'
Fan sensor monitor table.
st4FanSensorMonitorEntry row .1.3.6.1.4.1.1718.4.1.14.3.1
Objects to monitor for a particular fan sensor.
Column Syntax OID
The measured fan speed of the sensor in rotations per minute.
rotations per minuteInteger32
Constraints:
range: -1-15300
.1.3.6.1.4.1.1718.4.1.14.3.1.1
The status of the fan sensor.
DeviceStatus
Type Values:
0normal
1disabled
2purged
5reading
6settle
7notFound
8lost
9readError
10noComm
11pwrError
12breakerTripped
13fuseBlown
14lowAlarm
15lowWarning
16highWarning
17highAlarm
18alarm
19underLimit
20overLimit
21nvmFail
22profileError
23conflict
.1.3.6.1.4.1.1718.4.1.14.3.1.2
.1.3.6.1.4.1.1718.4.1.14.4 · 1 row entry · 5 columns
Uses the sentry variant from /opt/observium/mibs/sentry.
Command help
Walk st4FanSensorEventConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Sentry4-MIB' -M '/opt/observium/mibs/sentry:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Sentry4-MIB::st4FanSensorEventConfigTable'
Fan sensor event configuration table.
st4FanSensorEventConfigEntry row .1.3.6.1.4.1.1718.4.1.14.4.1
Event configuration objects for a particular fan sensor.
Column Syntax OID
The notification methods enabled for fan sensor events.
EventNotificationMethodsr/w
Type Values:
0snmpTrap
1email
.1.3.6.1.4.1.1718.4.1.14.4.1.1
The low alarm threshold of the fan sensor in rotations per
minute.
rotations per minuteInteger32r/w
Constraints:
range: 0-15300
.1.3.6.1.4.1.1718.4.1.14.4.1.2
The low warning threshold of the fan sensor in rotations per
minute.
rotations per minuteInteger32r/w
Constraints:
range: 0-15300
.1.3.6.1.4.1.1718.4.1.14.4.1.3
The high warning threshold of the fan sensor in rotations per
minute.
rotations per minuteInteger32r/w
Constraints:
range: 0-15300
.1.3.6.1.4.1.1718.4.1.14.4.1.4
The high alarm threshold of the fan sensor in rotations per
minute.
rotations per minuteInteger32r/w
Constraints:
range: 0-15300
.1.3.6.1.4.1.1718.4.1.14.4.1.5