SYNSYS-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
1
Rows
1
Columns
5

outletTable

table
.1.3.6.1.4.1.21728.3.2.1 · 1 row entry · 5 columns
Uses the synaccess variant from /opt/observium/mibs/synaccess.
Command help
Walk outletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SYNSYS-MIB' -M '/opt/observium/mibs/synaccess:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SYNSYS-MIB::outletTable'
A table of outlet operation status.
outletEntry row .1.3.6.1.4.1.21728.3.2.1.1
Row definition for the system description table.
Indexes
Column Syntax OID
Index for the outlet table.
Integer32
Constraints:
range: 0-15
.1.3.6.1.4.1.21728.3.2.1.1.1
Outlet label. Read operation.
OctetString
Constraints:
range: 0-10
.1.3.6.1.4.1.21728.3.2.1.1.2
Outlet status. 1-On. 2-0ff.
Enumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.21728.3.2.1.1.3
Turn on/off or reboot an outlet.
Enumerationr/w
Enumerated Values:
0none
1on
2off
3reboot
.1.3.6.1.4.1.21728.3.2.1.1.4
TRMS AC current draw from an outlet in Amps. This obj is applicable to MPO-system with AC current sensor for each outlet.MPO-Measured Per Outlet.
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.21728.3.2.1.1.5