STS_SEQUENZ-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
2
Rows
2
Columns
28
.1.3.6.1.4.1.16460.4.1.2.1
·
1 row entry
·
24 columns
Uses the eltek variant from
Command help
/opt/observium/mibs/eltek.
Walk inverter_Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'STS_SEQUENZ-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'STS_SEQUENZ-MIB::inverter_Table'
Table of CAN-nodes.
CAN-node entries.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
inv_Indexmandatory
NA
|
NAInteger32 Constraints: range: 1-16 |
.1.3.6.1.4.1.16460.4.1.2.1.1.0 |
|
inv_Nbrmandatory
Inverter Number,
Value: 1 ... 15 |
Integer32 Constraints: range: 0-15 |
.1.3.6.1.4.1.16460.4.1.2.1.1.1 |
|
inv_InCurrentmandatory
In-Current of the Inverter,
Value: todo |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.16460.4.1.2.1.1.2 |
|
inv_OutCurrentmandatory
Out-Current of the Inverter,
Value: todo |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.16460.4.1.2.1.1.3 |
|
inv_Temperaturemandatory
Temperature of the Inverter,
Value: todo |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.16460.4.1.2.1.1.4 |
|
inv_InputVoltagemandatory
Input Voltage of the Inverter,
Value: todo |
Integer32 Constraints: range: 0-65535 |
.1.3.6.1.4.1.16460.4.1.2.1.1.5 |
|
inv_STi_greatmandatory
Internal temperature high,
Value: 0= < limit 1= > limit |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.6 |
|
inv_Fanmandatory
Fan error,
Value: 0= no Error 1= error active |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.7 |
|
inv_RemoteOffCanmandatory
Far off via can-controll,
Value: 0= not off 1= far off is active |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.8 |
|
inv_UoutOffmandatory
State of Output voltage,
Value: 0= voltage is on 1= voltage shut down |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.9 |
|
inv_Bit_ShortCircuitmandatory
Short circuit is present,
Value: 0= normal operation 1= Short circuit |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.10 |
|
inv_Bit_OutputVoltagemandatory
State of the output voltage,
Value: 0= voltage off, error state 1= voltage ok,normal operation |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.11 |
|
inv_Bit_InputVoltLowmandatory
Input voltage reached lover limit,
Value: 0= normal operation 1= error present |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.12 |
|
inv_Bit_InputVoltHighmandatory
Input voltage reached upper limit,
Value: 0= normal operation 1= error present |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.13 |
|
inv_Bit_OutputVoltLowmandatory
Output voltage reached lower limit,
Value: 0= normal operation 1= error present |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.14 |
|
inv_Bit_OutputVoltHighmandatory
Output voltage reached upper limit,
Value: 0= normal operation 1= error present |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.15 |
|
inv_Bit_OutputCurrHighmandatory
Output current reached upper limit,
Value: 0= normal operation 1= error present |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.16 |
|
inv_Bit_RemoteOffmandatory
Inverter has shut-down,
Value: 0= normal operation 1= shut-down |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.17 |
|
inv_Bit_CentralAlarmmandatory
Central alarm has triggert,
Value: 0= normal operation 1= error present |
Integer32 Constraints: range: 0-1 |
.1.3.6.1.4.1.16460.4.1.2.1.1.18 |
|
inv_Typemandatory
Type description
|
RFC1213-MIBDisplayString Constraints: range: 0-16 |
.1.3.6.1.4.1.16460.4.1.2.1.1.19 |
|
inv_Mat_CDmandatory
Order number
|
RFC1213-MIBDisplayString Constraints: range: 0-16 |
.1.3.6.1.4.1.16460.4.1.2.1.1.20 |
|
inv_SerialNomandatory
Serial number
|
RFC1213-MIBDisplayString Constraints: range: 0-16 |
.1.3.6.1.4.1.16460.4.1.2.1.1.21 |
|
inv_HardwareVersionmandatory
Hardware version
|
RFC1213-MIBDisplayString Constraints: range: 0-8 |
.1.3.6.1.4.1.16460.4.1.2.1.1.22 |
|
inv_SoftwareVersionmandatory
Software Version
|
RFC1213-MIBDisplayString Constraints: range: 0-8 |
.1.3.6.1.4.1.16460.4.1.2.1.1.23 |
.1.3.6.1.4.1.16460.4.4.1
·
1 row entry
·
4 columns
Uses the eltek variant from
Command help
/opt/observium/mibs/eltek.
Walk historyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'STS_SEQUENZ-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'STS_SEQUENZ-MIB::historyTable'
Table of last 20 history events.
History values entries.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
histIndexmandatory
Index
|
NAInteger32 Constraints: range: 1-20 |
.1.3.6.1.4.1.16460.4.4.1.1.0 |
|
histIndmandatory
Index
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.16460.4.4.1.1.1 |
|
histDateTimemandatory
Date and time of event in UNIX notation
|
Integer32 Constraints: range: 0-400000000 |
.1.3.6.1.4.1.16460.4.4.1.1.2 |
|
histEventmandatory
History event
|
Integer32 Constraints: range: 1-65535 |
.1.3.6.1.4.1.16460.4.4.1.1.3 |