SP2-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
144
Rows
144
Columns
679
.1.3.6.1.4.1.12148.10.3.4 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsVoltageTable'
This table contains information about mains voltage monitor
mainsVoltageEntry row .1.3.6.1.4.1.12148.10.3.4.1
Column Syntax OID
mainsVoltageIndexIndex used for navigating the rows 1..12 of mainsVoltageTableInteger32
Constraints:
range: 1-12
.1.3.6.1.4.1.12148.10.3.4.1.1
mainsVoltageStatusThe status of the measured mains voltage.Enumeration.1.3.6.1.4.1.12148.10.3.4.1.2
mainsVoltageDescriptionA textual description of the mains voltage monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.3.4.1.3
mainsVoltageTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.4.1.4
mainsVoltageAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.3.4.1.5
mainsVoltageValueThe value of the measured mains voltage.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.6
mainsVoltageMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.7
mainsVoltageMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.8
mainsVoltageMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.9
mainsVoltageMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.10
.1.3.6.1.4.1.12148.10.3.5.2 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorsTable'
This table contains the number of voltage, current and frequency measurements in each AC Mains Monitor
mainsMonitorsEntry row .1.3.6.1.4.1.12148.10.3.5.2.1
Column Syntax OID
mainsMonitorIndexIndex used for navigating the rows of mainsMonitorsTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.3.5.2.1.1
mainsMonitorNumberOfVoltagesThe number of voltage measurements in the AC Mains MonitorInteger32
Constraints:
range: 0-3
.1.3.6.1.4.1.12148.10.3.5.2.1.2
mainsMonitorNumberOfCurrentsThe number of current measurements in the AC Mains MonitorInteger32
Constraints:
range: 0-3
.1.3.6.1.4.1.12148.10.3.5.2.1.3
mainsMonitorNumberOfFrequenciesThe number of frequency measurements in the AC Mains MonitorInteger32
Constraints:
range: 0-3
.1.3.6.1.4.1.12148.10.3.5.2.1.4
.1.3.6.1.4.1.12148.10.3.5.3 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorVoltageTable'
This table contains information about mains voltage in AC Mains Monitor
mainsMonitorVoltageEntry row .1.3.6.1.4.1.12148.10.3.5.3.1
Column Syntax OID
mainsMonitorPhaseIndexIndex used for navigating the rows 1..3 of mainsMonitorVolatgeTableInteger32
Constraints:
range: 1-3
.1.3.6.1.4.1.12148.10.3.5.3.1.1
mainsMonitorVoltageStatusThe status of the measured mains voltage in AC Mains Monitor.Enumeration.1.3.6.1.4.1.12148.10.3.5.3.1.2
mainsMonitorVoltageDescriptionA textual description of the mains voltage in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.3.1.3
mainsMonitorVoltageTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.3.1.4
mainsMonitorVoltageAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.3.5.3.1.5
mainsMonitorVoltageValueThe value of the measured mains voltage in AC Mains Monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.6
mainsMonitorVoltageMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.7
mainsMonitorVoltageMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.8
mainsMonitorVoltageMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.9
mainsMonitorVoltageMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.10
.1.3.6.1.4.1.12148.10.3.5.4 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorCurrentTable'
This table contains information about mains current in AC Mains Monitor
mainsMonitorCurrentEntry row .1.3.6.1.4.1.12148.10.3.5.4.1
Column Syntax OID
mainsMonitorCurrentStatusThe status of the measured mains current in AC Mains Monitor.Enumeration.1.3.6.1.4.1.12148.10.3.5.4.1.1
mainsMonitorCurrentDescriptionA textual description of the mains current in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.4.1.2
mainsMonitorCurrentTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.4.1.3
mainsMonitorCurrentAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.3.5.4.1.4
mainsMonitorCurrentValueThe value of the measured mains current in AC Mains Monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.4.1.5
mainsMonitorCurrentMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.4.1.6
mainsMonitorCurrentMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.4.1.7
.1.3.6.1.4.1.12148.10.3.5.5 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorFrequencyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorFrequencyTable'
This table contains information about mains frequency in AC Mains Monitor
mainsMonitorFrequencyEntry row .1.3.6.1.4.1.12148.10.3.5.5.1
Column Syntax OID
mainsMonitorFrequencyStatusThe status of the measured mains frequency in AC Mains Monitor.Enumeration.1.3.6.1.4.1.12148.10.3.5.5.1.1
mainsMonitorFrequencyDescriptionA textual description of the mains frequency in AC Mains Monitor. This is stored in the system
controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.3.5.5.1.2
mainsMonitorFrequencyTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.5.1.3
mainsMonitorFrequencyAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.3.5.5.1.4
mainsMonitorFrequencyValueThe value of the measured mains frequency in AC Mains Monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.5
mainsMonitorFrequencyMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.6
mainsMonitorFrequencyMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.7
mainsMonitorFrequencyMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.8
mainsMonitorFrequencyMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.9
.1.3.6.1.4.1.12148.10.3.5.6 · 1 row entry · 1 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorEnergyLogAccumulatedTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorEnergyLogAccumulatedTable'
This table contains the accumulated energy consumption measured in AC Mains Monitor
mainsMonitorEnergyLogAccumulatedEntry row .1.3.6.1.4.1.12148.10.3.5.6.1
Column Syntax OID
mainsMonitorEnergyLogAccumulatedThe accumulated energy consumption valueSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.6.1.1
.1.3.6.1.4.1.12148.10.3.5.8 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorEnergyLogLastHoursTable'
This table contains energy consumption values logged every hour in AC Mains Monitor.
Column Syntax OID
mainsMonitorEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of mainsMonitorEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.5.8.1.1
mainsMonitorEnergyLogLastHoursValueEnergy consumption value logged every hour in AC Mains Monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.8.1.2
.1.3.6.1.4.1.12148.10.3.5.10 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorEnergyLogLastDaysTable'
This table contains energy consumption values logged every day in AC Mains Monitor.
Column Syntax OID
mainsMonitorEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of mainsMonitorEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.5.10.1.1
mainsMonitorEnergyLogLastDaysValueEnergy consumption value logged every day in AC Mains Monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.10.1.2
.1.3.6.1.4.1.12148.10.3.5.12 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorEnergyLogLastWeeksTable'
This table contains energy consumption values logged every week in AC Mains Monitor.
Column Syntax OID
mainsMonitorEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of mainsMonitorEnergyLogLastWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.5.12.1.1
mainsMonitorEnergyLogLastWeeksValueEnergy consumption value logged every week in AC Mains Monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.12.1.2
.1.3.6.1.4.1.12148.10.3.5.13 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorActivePowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorActivePowerTable'
This table contains information about mains active power in AC Mains Monitor
mainsMonitorActivePowerEntry row .1.3.6.1.4.1.12148.10.3.5.13.1
Column Syntax OID
mainsMonitorActivePowerStatusThe status of the measured mains active power in AC Mains Monitor.Enumeration.1.3.6.1.4.1.12148.10.3.5.13.1.1
mainsMonitorActivePowerDescriptionA textual description of the mains active power in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.13.1.2
mainsMonitorActivePowerTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.13.1.3
mainsMonitorActivePowerAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.3.5.13.1.4
mainsMonitorActivePowerValueThe value of the measured mains active power in AC Mains Monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.13.1.5
mainsMonitorActivePowerMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.13.1.6
mainsMonitorActivePowerMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.13.1.7
.1.3.6.1.4.1.12148.10.3.5.14 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorReactivePowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorReactivePowerTable'
This table contains information about mains reactive power in AC Mains Monitor
mainsMonitorReactivePowerEntry row .1.3.6.1.4.1.12148.10.3.5.14.1
Column Syntax OID
mainsMonitorReactivePowerStatusThe status of the measured mains reactive power in AC Mains Monitor.Enumeration.1.3.6.1.4.1.12148.10.3.5.14.1.1
mainsMonitorReactivePowerDescriptionA textual description of the mains reactive power in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.14.1.2
mainsMonitorReactivePowerTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.14.1.3
mainsMonitorReactivePowerAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.3.5.14.1.4
mainsMonitorReactivePowerValueThe value of the measured mains reactive power in AC Mains Monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.14.1.5
mainsMonitorReactivePowerMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.14.1.6
mainsMonitorReactivePowerMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.14.1.7
.1.3.6.1.4.1.12148.10.3.5.15 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorApparentPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorApparentPowerTable'
This table contains information about mains apparent power in AC Mains Monitor
mainsMonitorApparentPowerEntry row .1.3.6.1.4.1.12148.10.3.5.15.1
Column Syntax OID
mainsMonitorApparentPowerStatusThe status of the measured mains apparent power in AC Mains Monitor.Enumeration.1.3.6.1.4.1.12148.10.3.5.15.1.1
mainsMonitorApparentPowerDescriptionA textual description of the mains apparent power in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.15.1.2
mainsMonitorApparentPowerTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.15.1.3
mainsMonitorApparentPowerAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.3.5.15.1.4
mainsMonitorApparentPowerValueThe value of the measured mains apparent power in AC Mains Monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.15.1.5
mainsMonitorApparentPowerMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.15.1.6
mainsMonitorApparentPowerMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.15.1.7
.1.3.6.1.4.1.12148.10.3.6.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsOutageLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsOutageLogDaysTable'
This table contains daily mains outage or running time log depending on the log mode.
mainsOutageLogDaysEntry row .1.3.6.1.4.1.12148.10.3.6.3.1
Column Syntax OID
mainsOutageLogDaysIndexIndex used for navigating the rows 1..52 of mainsOutageLogDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.6.3.1.1
mainsOutageLogDaysValueMains outage or running time value in minutes, logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.6.3.1.2
.1.3.6.1.4.1.12148.10.3.6.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsOutageLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsOutageLogWeeksTable'
This table contains weekly mains outage or running time log depending on the log mode.
mainsOutageLogWeeksEntry row .1.3.6.1.4.1.12148.10.3.6.5.1
Column Syntax OID
mainsOutageLogWeeksIndexIndex used for navigating the rows 1..52 of mainsOutageLogWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.6.5.1.1
mainsOutageLogWeeksValueMains outage or running time value in hours, logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.6.5.1.2
.1.3.6.1.4.1.12148.10.3.6.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsOutageLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsOutageLogMonthsTable'
This table contains monthly mains outage or running time log depending on the log mode.
mainsOutageLogMonthsEntry row .1.3.6.1.4.1.12148.10.3.6.7.1
Column Syntax OID
mainsOutageLogMonthsIndexIndex used for navigating the rows 1..52 of mainsOutageLogMonthsTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.6.7.1.1
mainsOutageLogMonthsValueMains outage or running time value in hours, logged every month.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.6.7.1.2
.1.3.6.1.4.1.12148.10.3.8 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupsTable'
This table contains the status of mains group and number of phases in each group.
mainsGroupsEntry row .1.3.6.1.4.1.12148.10.3.8.1
Indexes
Column Syntax OID
mainsGroupIndexIndex used for navigating the rows 1..10 of mainsGroupTableInteger32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.3.8.1.1
mainsGroupStatusThe status of mains group.Enumeration.1.3.6.1.4.1.12148.10.3.8.1.2
mainsGroupNumberOfPhasesThis value showing the number of phases of the mains group subsystem.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.8.1.3
.1.3.6.1.4.1.12148.10.3.9 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupMainsFailureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupMainsFailureTable'
This table contains information about mains failure monitor of mains group
mainsGroupMainsFailureEntry row .1.3.6.1.4.1.12148.10.3.9.1
Indexes
Column Syntax OID
mainsGroupMainsFailureStatusThis status value shows if the number of failed phases is higher than the defined alarm level for the mains groupEnumeration.1.3.6.1.4.1.12148.10.3.9.1.1
mainsGroupMainsFailureDescriptionA textual description of the mains group phase failure monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.3.9.1.2
mainsGroupMainsFailureTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.9.1.3
mainsGroupMainsFailureAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.3.9.1.4
mainsGroupMainsFailureValueThe detected number of failed phases in the mains group.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.9.1.5
mainsGroupMainsFailureMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.9.1.6
mainsGroupMainsFailureMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.9.1.7
.1.3.6.1.4.1.12148.10.3.10 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupVoltageTable'
This table contains information about mains voltage monitors for mains group
mainsGroupVoltageEntry row .1.3.6.1.4.1.12148.10.3.10.1
Column Syntax OID
mainsGroupVoltageIndexIndex used for navigating the rows 1..12 of mainsGroupVoltageTableInteger32
Constraints:
range: 1-12
.1.3.6.1.4.1.12148.10.3.10.1.1
mainsGroupVoltageStatusThe status of the measured mains voltage of the mains group.Enumeration.1.3.6.1.4.1.12148.10.3.10.1.2
mainsGroupVoltageDescriptionA textual description of the mains voltage monitor of the mains group. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.3.10.1.3
mainsGroupVoltageTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.4
mainsGroupVoltageAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.3.10.1.5
mainsGroupVoltageValueThe value of the measured mains voltage in the mains group.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.6
mainsGroupVoltageMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.7
mainsGroupVoltageMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.8
mainsGroupVoltageMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.9
mainsGroupVoltageMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.10
.1.3.6.1.4.1.12148.10.3.11 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupOutageLogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupOutageLogTable'
This table contains total mains outage of the mains group and number of entries in each log table.
mainsGroupOutageLogEntry row .1.3.6.1.4.1.12148.10.3.11.1
Indexes
Column Syntax OID
mainsGroupOutageTotalThis is the total mains outage time measured in hours in the mains group.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.11.1.1
mainsGroupOutageLogDaysNumberOfEntriesThis is the maximal number of entries stored in daily mains outage log.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.11.1.2
mainsGroupOutageLogWeeksNumberOfEntriesThis is the maximal number of entries stored in weekly mains outage time log.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.11.1.3
mainsGroupOutageLogMonthsNumberOfEntriesThis is the maximal number of entries stored in monthly mains outage time log.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.11.1.4
.1.3.6.1.4.1.12148.10.3.12 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupOutageLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupOutageLogDaysTable'
This table contains daily mains outage time log of mains group.
Column Syntax OID
mainsGroupOutageLogDaysIndexIndex used for navigating the rows 1..52 of mainsGroupOutageLogDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.12.1.1
mainsGroupOutageLogDaysValueMains outage time value in minutes of each mains group, logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.12.1.2
.1.3.6.1.4.1.12148.10.3.13 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupOutageLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupOutageLogWeeksTable'
This table contains weekly mains outage time log of mains group.
Column Syntax OID
mainsGroupOutageLogWeeksIndexIndex used for navigating the rows 1..52 of mainsGroupOutageLogWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.13.1.1
mainsGroupOutageLogWeeksValueMains outage time value in hours of each mains group, logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.13.1.2
.1.3.6.1.4.1.12148.10.3.14 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupOutageLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupOutageLogMonthsTable'
This table contains monthly mains outage time log of mains group.
Column Syntax OID
mainsGroupOutageLogMonthsIndexIndex used for navigating the rows 1..52 of mainsGroupOutageLogMonthsTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.14.1.1
mainsGroupOutageLogMonthsValueMains outage time value in hours of each mains group, logged every month.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.14.1.2
.1.3.6.1.4.1.12148.10.4.16 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorDailyRunSetupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorDailyRunSetupTable'
This table contains configurations of generator daily run.
generatorDailyRunSetupEntry row .1.3.6.1.4.1.12148.10.4.16.1
Column Syntax OID
generatorDailyRunDayIndexIndex used for navigating the rows 1..7 of generatorDailyRunSetupTableEnumeration.1.3.6.1.4.1.12148.10.4.16.1.1
generatorDailyRunStartHourGenerator daily starting time.Integer32r/w
Constraints:
range: 0-23
.1.3.6.1.4.1.12148.10.4.16.1.2
generatorDailyRunStopHourGenerator daily stopping time.Integer32r/w
Constraints:
range: 0-23
.1.3.6.1.4.1.12148.10.4.16.1.3
.1.3.6.1.4.1.12148.10.4.22 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorTankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorTankTable'
This table contains information about generator fuel tanks.
generatorTankEntry row .1.3.6.1.4.1.12148.10.4.22.1
Column Syntax OID
generatorTankIndexIndex used for navigating the rows 1..2 of generatorTankTableInteger32
Constraints:
range: 1-2
.1.3.6.1.4.1.12148.10.4.22.1.1
generatorTankStatusThe status of the measured fuel level in tank.Enumeration.1.3.6.1.4.1.12148.10.4.22.1.2
generatorTankDescriptionA textual description of the fuel level monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.4.22.1.3
generatorTankTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.4.22.1.4
generatorTankEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.4.22.1.5
generatorTankValueThe value of the measured fuel level.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.6
generatorTankMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.7
generatorTankMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.8
generatorTankMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.9
generatorTankMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.10
.1.3.6.1.4.1.12148.10.4.23.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorEnergyLogLastHoursTable'
This table contains hourly energy log of generator.
generatorEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.4.23.3.1
Column Syntax OID
generatorEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of generatorEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.23.3.1.1
generatorEnergyLogLastHoursValueEnergy value logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.23.3.1.2
.1.3.6.1.4.1.12148.10.4.23.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorEnergyLogLastDaysTable'
This table contains daily energy log of generator.
generatorEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.4.23.5.1
Column Syntax OID
generatorEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of generatorEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.23.5.1.1
generatorEnergyLogLastDaysValueEnergy value logged every daySNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.23.5.1.2
.1.3.6.1.4.1.12148.10.4.23.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorEnergyLogLastWeeksTable'
This table contains weekly energy log of generator.
generatorEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.4.23.7.1
Column Syntax OID
generatorEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of generatorEnergyLogLastWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.23.7.1.1
generatorEnergyLogLastWeeksValueEnergy value logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.23.7.1.2
.1.3.6.1.4.1.12148.10.4.24.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorRunHoursLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorRunHoursLogLastDaysTable'
generator running time in minutes
generatorRunHoursLogLastDaysEntry row .1.3.6.1.4.1.12148.10.4.24.3.1
Column Syntax OID
generatorRunHoursLogLastDaysIndexIndex used for navigating the rows 1..52 of generatorRunHoursLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.24.3.1.1
generatorRunHoursLogLastDaysValueGenerator running time in minutes, logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.24.3.1.2
.1.3.6.1.4.1.12148.10.4.24.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorRunHoursLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorRunHoursLogLastWeeksTable'
generator running time in hours
generatorRunHoursLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.4.24.5.1
Column Syntax OID
generatorRunHoursLogLastWeeksIndexIndex used for navigating the rows 1..52 of generatorRunHoursLogLastWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.24.5.1.1
generatorRunHoursLogLastWeeksValueGenerator running time in hours, logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.24.5.1.2
.1.3.6.1.4.1.12148.10.4.24.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorRunHoursLogLastMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorRunHoursLogLastMonthsTable'
generator running time in hours
Column Syntax OID
generatorRunHoursLogLastMonthsIndexIndex used for navigating the rows 1..52 of generatorRunHoursLogLastMonthsTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.24.7.1.1
generatorRunHoursLogLastMonthsValueGenerator running time in hours, logged every month.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.24.7.1.2
.1.3.6.1.4.1.12148.10.4.25.1 · 1 row entry · 1 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorFuelConsumptionTotalUsedTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorFuelConsumptionTotalUsedTable'
This table contains total fuel consumption for each tank.
generatorFuelConsumptionTotalUsedEntry row .1.3.6.1.4.1.12148.10.4.25.1.1
Column Syntax OID
generatorFuelConsumptionTotalUsedTotal fuel consumption value.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.25.1.1.1
.1.3.6.1.4.1.12148.10.4.25.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorFuelConsumptionLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorFuelConsumptionLogLastDaysTable'
This table contains generator daily fuel consumption log.
Column Syntax OID
generatorFuelConsumptionLogLastDaysIndexIndex used for navigating the rows 1..52 of generatorFuelConsumptionLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.25.3.1.1
generatorFuelConsumptionLogLastDaysValueGenerator fuel consumption value, logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.25.3.1.2
.1.3.6.1.4.1.12148.10.4.25.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorFuelConsumptionLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorFuelConsumptionLogLastWeeksTable'
This table contains generator weekly fuel consumption log.
Column Syntax OID
generatorFuelConsumptionLogLastWeeksIndexIndex used for navigating the rows 1..52 of generatorFuelConsumptionLogLastWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.25.5.1.1
generatorFuelConsumptionLogLastWeeksValueGenerator fuel consumption value, logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.25.5.1.2
.1.3.6.1.4.1.12148.10.4.25.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorFuelConsumptionLogLastMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorFuelConsumptionLogLastMonthsTable'
This table contains generator hourly fuel consumption log.
Column Syntax OID
generatorFuelConsumptionLogLastMonthsIndexIndex used for navigating the rows 1..52 of generatorFuelConsumptionLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.25.7.1.1
generatorFuelConsumptionLogLastMonthsValueGenerator fuel consumption value, logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.25.7.1.2
.1.3.6.1.4.1.12148.10.5.6 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierTable'
This table shows the information of each rectifier installed in the system.
rectifierEntry row .1.3.6.1.4.1.12148.10.5.6.1
Indexes
Column Syntax OID
rectifierIndexIndex used for navigating the rows 1..100 of rectifierTableInteger32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.5.6.1.1
rectifierStatusThe overall status of rectifier.Enumeration.1.3.6.1.4.1.12148.10.5.6.1.2
rectifierOutputCurrentValueThe output current value of rectifier.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.6.1.3
rectifierInputVoltageValueThe input voltage value of rectifier.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.6.1.4
rectifierTypeType of rectifierOctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.5.6.1.5
rectifierHwPartNumberHardware part number of rectifierOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.5.6.1.6
rectifierHwVersionHardware version number of rectifierOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.5.6.1.7
rectifierSwPartNumberPart number of secondary software in rectifierOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.5.6.1.8
rectifierSwVersionVersion number of secondary software in rectifierOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.5.6.1.9
rectifierSerialNumberSerial number of rectifierOctetString
Constraints:
range: 1-12
.1.3.6.1.4.1.12148.10.5.6.1.10
.1.3.6.1.4.1.12148.10.5.7.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifiersEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifiersEnergyLogLastHoursTable'
This table contains hourly energy log of rectifiers.
rectifiersEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.5.7.3.1
Column Syntax OID
rectifiersEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of rectifiersEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.7.3.1.1
rectifiersEnergyLogLastHoursValueEnergy value logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.7.3.1.2
.1.3.6.1.4.1.12148.10.5.7.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifiersEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifiersEnergyLogLastDaysTable'
This table contains daily energy log of rectifiers.
rectifiersEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.5.7.5.1
Column Syntax OID
rectifiersEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of rectifiersEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.7.5.1.1
rectifiersEnergyLogLastDaysValueEnergy value logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.7.5.1.2
.1.3.6.1.4.1.12148.10.5.7.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifiersEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifiersEnergyLogLastWeeksTable'
This table contains weekly energy log of rectifiers.
rectifiersEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.5.7.7.1
Column Syntax OID
rectifiersEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of rectifiersEnergyLogLastWeekTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.7.7.1.1
rectifiersEnergyLogLastWeeksValueEnergy value logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.7.7.1.2
.1.3.6.1.4.1.12148.10.5.9 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupsTable'
This table contains status and the number of installed rectifiers of each rectifier groups.
rectifierGroupsEntry row .1.3.6.1.4.1.12148.10.5.9.1
Column Syntax OID
rectifierGroupIndexIndex used for navigating the rows 1..10 of rectifierGroupsTableInteger32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.5.9.1.1
rectifierGroupStatusThe status of each rectifier group.Enumeration.1.3.6.1.4.1.12148.10.5.9.1.2
rectifierGroupNumberOfRectifiersNumber of installed rectifiers in each rectifier groupsInteger32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.12148.10.5.9.1.3
.1.3.6.1.4.1.12148.10.5.10 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupCurrentTable'
This table contains information about the total rectifier current of each rectifier groups, which is calculated 
by summing up current from each rectifier in a rectifier group.
rectifierGroupCurrentEntry row .1.3.6.1.4.1.12148.10.5.10.1
Column Syntax OID
rectifierGroupCurrentStatusThe status of the measured total rectifier current of the rectifier groupEnumeration.1.3.6.1.4.1.12148.10.5.10.1.1
rectifierGroupCurrentDescriptionA textual description of the total rectifier current monitor of a rectifier group. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.5.10.1.2
rectifierGroupCurrentTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.10.1.3
rectifierGroupCurrentAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.5.10.1.4
rectifierGroupCurrentValueThe value of the measured total rectifier current of each rectifier group.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.10.1.5
rectifierGroupCurrentMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.10.1.6
rectifierGroupCurrentMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.10.1.7
.1.3.6.1.4.1.12148.10.5.11 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupCapacityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupCapacityTable'
This table contains information about the used rectifier capacity of each rectifier group.
rectifierGroupCapacityEntry row .1.3.6.1.4.1.12148.10.5.11.1
Column Syntax OID
rectifierGroupCapacityStatusThe status of the measured used rectifier capacity of each rectifier groupEnumeration.1.3.6.1.4.1.12148.10.5.11.1.1
rectifierGroupCapacityDescriptionA textual description of the used rectifier capacity monitor of each rectifier group. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.5.11.1.2
rectifierGroupCapacityTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.11.1.3
rectifierGroupCapacityAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.5.11.1.4
rectifierGroupCapacityValueThe used rectifier capacity value presented in percentage of the total installed rectifier capacity of each rectifier group.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.11.1.5
rectifierGroupCapacityMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.11.1.6
rectifierGroupCapacityMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.11.1.7
.1.3.6.1.4.1.12148.10.5.12 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupErrorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupErrorTable'
This table contains information about the rectifier error monitor of each rectifier group.
rectifierGroupErrorEntry row .1.3.6.1.4.1.12148.10.5.12.1
Column Syntax OID
rectifierGroupErrorStatusThis status value shows if the number of failed units is higher than the defined alarm level.Enumeration.1.3.6.1.4.1.12148.10.5.12.1.1
rectifierGroupErrorDescriptionA textual description of the rectifier error monitor of each rectifier group. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.5.12.1.2
rectifierGroupErrorTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.12.1.3
rectifierGroupErrorAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.5.12.1.4
rectifierGroupErrorValueThe number of failed rectifiers of each rectifier group.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.12.1.5
rectifierGroupErrorMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.12.1.6
rectifierGroupErrorMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.12.1.7
.1.3.6.1.4.1.12148.10.5.13 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupRectifierTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupRectifierTable'
This table shows the information of each rectifier installed in each of the rectifier group in the system.
Column Syntax OID
rectifierGroupRectifierIndexIndex used for navigating the rows 1..100 of rectifierGroupRectifierTableInteger32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.5.13.1.1
rectifierGroupRectifierStatusThe overall status of rectifier.Enumeration.1.3.6.1.4.1.12148.10.5.13.1.2
rectifierGroupRectifierOutputCurrentValueThe output current value of rectifier.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.13.1.3
rectifierGroupRectifierInputVoltageValueThe input voltage value of rectifier.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.13.1.4
rectifierGroupRectifierTypeType of rectifierOctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.5.13.1.5
rectifierGroupRectifierHwPartNumberHardware part number of rectifierOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.5.13.1.6
rectifierGroupRectifierHwVersionHardware version number of rectifierOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.5.13.1.7
rectifierGroupRectifierSwPartNumberPart number of secondary software in rectifierOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.5.13.1.8
rectifierGroupRectifierSwVersionVersion number of secondary software in rectifierOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.5.13.1.9
.1.3.6.1.4.1.12148.10.5.14 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupEnergyLogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupEnergyLogTable'
This branch contains information about rectifiers' energy logs of each rectifier group.
rectifierGroupEnergyLogEntry row .1.3.6.1.4.1.12148.10.5.14.1
Column Syntax OID
rectifierGroupEnergyLogAccumulatedThis is the accumulated energy delivered from rectifiers of each rectifier group.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.14.1.1
rectifierGroupEnergyLogLastHoursNumberOfEntriesThis is the maximal number of entries stored in rectifier group hourly energy log.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.14.1.2
rectifierGroupEnergyLogLastDaysNumberOfEntriesThis is the maximal number of entries stored in rectifier group daily energy log.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.14.1.3
rectifierGroupEnergyLogLastWeeksNumberOfEntriesThis is the maximal number of entries stored in rectifier group weekly energy log.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.14.1.4
.1.3.6.1.4.1.12148.10.5.15 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupEnergyLogLastHoursTable'
This table contains hourly energy log of each rectifier group
Column Syntax OID
rectifierGroupEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of rectifierGroupEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.15.1.1
rectifierGroupEnergyLogLastHoursValueEnergy value logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.15.1.2
.1.3.6.1.4.1.12148.10.5.16 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupEnergyLogLastDaysTable'
This table contains daily energy log of each rectifier group
Column Syntax OID
rectifierGroupEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of rectifierGroupEnergyLogLasDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.16.1.1
rectifierGroupEnergyLogLastDaysValueEnergy value logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.16.1.2
.1.3.6.1.4.1.12148.10.5.17 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupEnergyLogLastWeeksTable'
This table contains weekly energy log of each rectifier group
Column Syntax OID
rectifierGroupEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of rectifierGroupEnergyLogLastWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.17.1.1
rectifierGroupEnergyLogLastWeeksValueEnergy value logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.17.1.2
.1.3.6.1.4.1.12148.10.5.19 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupTemperatureTable'
This table contains information about the highest rectifier temperature of each rectifier groups, which is calculated 
by summing up current from each rectifier in a rectifier group.
rectifierGroupTemperatureEntry row .1.3.6.1.4.1.12148.10.5.19.1
Column Syntax OID
rectifierGroupTemperatureStatusThe status of the measured highest rectifier temperature of the rectifier groupEnumeration.1.3.6.1.4.1.12148.10.5.19.1.1
rectifierGroupTemperatureDescriptionA textual description of the highest rectifier temperature monitor of a rectifier group. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.5.19.1.2
rectifierGroupTemperatureTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.3
rectifierGroupTemperatureAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.5.19.1.4
rectifierGroupTemperatureValueThe value of the measured highest rectifier temperature of each rectifier group.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.5
rectifierGroupTemperatureMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.6
rectifierGroupTemperatureMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.7
rectifierGroupTemperatureMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.8
rectifierGroupTemperatureMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.9
.1.3.6.1.4.1.12148.10.6.2 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcGroupsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcGroupsTable'
This table contains information about dcdc groups.
dcdcGroupsEntry row .1.3.6.1.4.1.12148.10.6.2.1
Indexes
Column Syntax OID
dcdcGroupIndexInteger32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.6.2.1.1
dcdcGroupStatusThe overall status of dcdc group.Enumeration.1.3.6.1.4.1.12148.10.6.2.1.2
dcdcGroupNumberOfDcdcConvertersNumber of installed dcdc converters.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.2.1.3
dcdcGroupOutputVoltageOutput voltage of dcdc convertersSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.2.1.4
dcdcNumberOfCurrentsNumber of dcdc currentsInteger32
Constraints:
range: 0-5
.1.3.6.1.4.1.12148.10.6.2.1.5
dcdcNumberOfCapacitiesNumber of dcdc capacitiesInteger32
Constraints:
range: 0-5
.1.3.6.1.4.1.12148.10.6.2.1.6
dcdcNumberOfAlarmsNumber of dcdc alarmsInteger32
Constraints:
range: 0-5
.1.3.6.1.4.1.12148.10.6.2.1.7
.1.3.6.1.4.1.12148.10.6.3 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcCurrentTable'
This table contains information about the total dcdc current.
dcdcCurrentEntry row .1.3.6.1.4.1.12148.10.6.3.1
Indexes
Column Syntax OID
dcdcCurrentStatusThe status of the measured total dcdc current.Enumeration.1.3.6.1.4.1.12148.10.6.3.1.1
dcdcCurrentDescriptionA textual description of the total dcdc current monitor. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.6.3.1.2
dcdcCurrentTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.6.3.1.3
dcdcCurrentAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.6.3.1.4
dcdcCurrentValueThe value of the measured total dcdc current.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.3.1.5
dcdcCurrentMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.3.1.6
dcdcCurrentMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.3.1.7
.1.3.6.1.4.1.12148.10.6.4 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcCapacityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcCapacityTable'
This table contains information about the used dcdc capacity.
dcdcCapacityEntry row .1.3.6.1.4.1.12148.10.6.4.1
Indexes
Column Syntax OID
dcdcCapacityStatusThe status of the measured used dcdc capacity.Enumeration.1.3.6.1.4.1.12148.10.6.4.1.1
dcdcCapacityDescriptionA textual description of the used dcdc capacity monitor. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.6.4.1.2
dcdcCapacityTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.6.4.1.3
dcdcCapacityAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.6.4.1.4
dcdcCapacityValueThe used dcdc capacity value presented in percentage of the total installed dcdc capacity.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.4.1.5
dcdcCapacityMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.4.1.6
dcdcCapacityMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.4.1.7

dcdcTable

table
.1.3.6.1.4.1.12148.10.6.5 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcTable'
This table shows the information of each dcdc converter installed in the system.
dcdcEntry row .1.3.6.1.4.1.12148.10.6.5.1
Column Syntax OID
dcdcIndexIndex used for navigating the rows 1..100 of dcdcTableInteger32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.6.5.1.1
dcdcStatusThe overall status of dcdc converterEnumeration.1.3.6.1.4.1.12148.10.6.5.1.2
dcdcOutputCurrentValueThe output current value of dcdc.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.5.1.3
dcdcInputVoltageValueThe input voltage value of dcdc.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.5.1.4
dcdcTypeType of dcdc converterOctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.6.5.1.5
dcdcHwPartNumberHardware part number of dcdc converterOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.6.5.1.6
dcdcHwVersionHardware version number of dcdc converterOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.6.5.1.7
dcdcSwPartNumberPart number of secondary software in dcdc converterOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.6.5.1.8
dcdcSwVersionVersion number of secondary software in dcdc converterOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.6.5.1.9
.1.3.6.1.4.1.12148.10.6.6 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcErrorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcErrorTable'
This table contains information about the dcdc error monitor.
dcdcErrorEntry row .1.3.6.1.4.1.12148.10.6.6.1
Indexes
Column Syntax OID
dcdcErrorStatusThis status value shows if the number of failed units is higher than the defined alarm level.Enumeration.1.3.6.1.4.1.12148.10.6.6.1.1
dcdcErrorDescriptionA textual description of the dcdc error monitor. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.6.6.1.2
dcdcErrorTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.6.6.1.3
dcdcErrorEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.6.6.1.4
dcdcErrorValueThe number of failed dcdc converters.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.6.1.5
dcdcErrorMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.6.1.6
dcdcErrorMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.6.1.7
.1.3.6.1.4.1.12148.10.7.6 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk solarChargerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::solarChargerTable'
This table shows the information of each solar charger installed in the system.
solarChargerEntry row .1.3.6.1.4.1.12148.10.7.6.1
Column Syntax OID
solarChargerIndexIndex used for navigating the rows 1..100 of solarChargerTableInteger32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.7.6.1.1
solarChargerStatusThe overall status of solar charger.Enumeration.1.3.6.1.4.1.12148.10.7.6.1.2
solarChargerOutputCurrentValueThe output current value of solar charger.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.6.1.3
solarChargerInputVoltageValueThe input voltage value of solar charger.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.6.1.4
solarChargerTypeType of solar chargerOctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.7.6.1.5
solarChargerHwPartNumberHardware part number of solar chargerOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.7.6.1.6
solarChargerHwVersionHardware version number of solar chargerOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.7.6.1.7
solarChargerSwPartNumberPart number of secondary software in solar chargerOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.7.6.1.8
solarChargerSwVersionVersion number of secondary software in solar chargerOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.7.6.1.9
.1.3.6.1.4.1.12148.10.7.7.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk solarChargersEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::solarChargersEnergyLogLastHoursTable'
This table contains hourly energy log of solar chargers.
Column Syntax OID
solarChargersEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of solarChargersEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.7.7.3.1.1
solarChargersEnergyLogLastHoursValueEnergy value logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.7.3.1.2
.1.3.6.1.4.1.12148.10.7.7.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk solarChargersEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::solarChargersEnergyLogLastDaysTable'
This table contains daily energy log of solar chargers.
Column Syntax OID
solarChargersEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of solarChargersEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.7.7.5.1.1
solarChargersEnergyLogLastDaysValueEnergy value logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.7.5.1.2
.1.3.6.1.4.1.12148.10.7.7.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk solarChargersEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::solarChargersEnergyLogLastWeeksTable'
This table contains weekly energy log of solar chargers.
Column Syntax OID
solarChargersEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of solarChargersEnergyLogLastWeekTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.7.7.7.1.1
solarChargersEnergyLogLastWeeksValueEnergy value logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.7.7.1.2
.1.3.6.1.4.1.12148.10.8.6 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk windChargerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::windChargerTable'
This table shows the information of each wind charger installed in the system.
windChargerEntry row .1.3.6.1.4.1.12148.10.8.6.1
Column Syntax OID
windChargerIndexIndex used for navigating the rows 1..100 of windChargerTableInteger32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.8.6.1.1
windChargerStatusThe overall status of wind charger.Enumeration.1.3.6.1.4.1.12148.10.8.6.1.2
windChargerOutputCurrentValueThe output current value of wind charger.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.6.1.3
windChargerInputVoltageValueThe input voltage value of wind charger.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.6.1.4
windChargerTypeType of wind chargerOctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.8.6.1.5
windChargerHwPartNumberHardware part number of wind chargerOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.8.6.1.6
windChargerHwVersionHardware version number of wind chargerOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.8.6.1.7
windChargerSwPartNumberPart number of secondary software in wind chargerOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.8.6.1.8
windChargerSwVersionVersion number of secondary software in wind chargerOctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.8.6.1.9
.1.3.6.1.4.1.12148.10.8.7.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk windChargersEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::windChargersEnergyLogLastHoursTable'
This table contains hourly energy log of wind chargers.
Column Syntax OID
windChargersEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of windChargersEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.8.7.3.1.1
windChargersEnergyLogLastHoursValueEnergy value logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.7.3.1.2
.1.3.6.1.4.1.12148.10.8.7.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk windChargersEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::windChargersEnergyLogLastDaysTable'
This table contains daily energy log of wind chargers.
Column Syntax OID
windChargersEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of windChargersEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.8.7.5.1.1
windChargersEnergyLogLastDaysValueEnergy value logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.7.5.1.2
.1.3.6.1.4.1.12148.10.8.7.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk windChargersEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::windChargersEnergyLogLastWeeksTable'
This table contains weekly energy log of wind chargers.
Column Syntax OID
windChargersEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of windChargersEnergyLogLastWeekTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.8.7.7.1.1
windChargersEnergyLogLastWeeksValueEnergy value logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.7.7.1.2
.1.3.6.1.4.1.12148.10.9.5 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadGroupTable'
This table contains information about load groups.
loadGroupEntry row .1.3.6.1.4.1.12148.10.9.5.1
Indexes
Column Syntax OID
loadGroupIndexIndex used for navigating the rows 1..8 of loadGroupTableInteger32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.9.5.1.1
loadGroupStatusThe status of load groupEnumeration.1.3.6.1.4.1.12148.10.9.5.1.2
loadNumberOfLVLDsNumber of LVLDs installed in load groupInteger32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.9.5.1.3
loadNumberOfVoltagesNumber of voltages in load groupInteger32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.9.5.1.4
.1.3.6.1.4.1.12148.10.9.6 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadLVLDTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadLVLDTable'
This table contains information about LVLDs
loadLVLDEntry row .1.3.6.1.4.1.12148.10.9.6.1
Column Syntax OID
loadLVLDIndexIndex used for navigating the rows 1..8 of loadLVLDTableInteger32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.9.6.1.1
loadLVLDStatusThe status of LVLDEnumeration.1.3.6.1.4.1.12148.10.9.6.1.2
loadLVLDDescriptionA textual description of the LVLD. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.9.6.1.3
loadLVLDTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.9.6.1.4
loadLVLDEnableThis value once enabled, the alarm condition of the LVLD will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.9.6.1.5
loadLVLDValueThe measured value of the LVLD.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.6.1.6
loadLVLDConnectVoltageThe load Contactor's Reconnect VoltageSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.6.1.7
loadLVLDDisconnectVoltageThe load Contactor's Disconnect VoltageSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.6.1.8
loadLVLDDisconnectDelayEnableEnable/disable LVLD disconnect delay.Enumerationr/w.1.3.6.1.4.1.12148.10.9.6.1.9
loadLVLDDisconnectDelayTimeLVLD disconnect delay time in minutes.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.6.1.10
.1.3.6.1.4.1.12148.10.9.7 · 1 row entry · 5 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadFuseTable'
This table contains information about load fuse
loadFuseEntry row .1.3.6.1.4.1.12148.10.9.7.1
Indexes
Column Syntax OID
loadFuseStatusThe status of load fuseEnumeration.1.3.6.1.4.1.12148.10.9.7.1.1
loadFuseDescriptionA textual description of the load fuse monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.9.7.1.2
loadFuseTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.9.7.1.3
loadFuseAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.9.7.1.4
loadFuseValueThe measured value of the load fuse.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.7.1.5
.1.3.6.1.4.1.12148.10.9.8.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadEnergyLogLastHoursTable'
loadEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.9.8.3.1
Column Syntax OID
loadEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of loadEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.9.8.3.1.1
loadEnergyLogLastHoursValueEnergy value logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.8.3.1.2
.1.3.6.1.4.1.12148.10.9.8.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadEnergyLogLastDaysTable'
loadEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.9.8.5.1
Column Syntax OID
loadEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of loadEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.9.8.5.1.1
loadEnergyLogLastDaysValueEnergy value logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.8.5.1.2
.1.3.6.1.4.1.12148.10.9.8.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadEnergyLogLastWeeksTable'
loadEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.9.8.7.1
Column Syntax OID
loadEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of loadEnergyLogLastWeekTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.9.8.7.1.1
loadEnergyLogLastWeeksValueEnergy value logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.8.7.1.2
.1.3.6.1.4.1.12148.10.9.9 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadVoltageTable'
This table contains information about voltages
loadVoltageEntry row .1.3.6.1.4.1.12148.10.9.9.1
Column Syntax OID
loadVoltageIndexIndex used for navigating the rows 1..3 of loadVoltageTableInteger32
Constraints:
range: 1-3
.1.3.6.1.4.1.12148.10.9.9.1.1
loadVoltageStatusThe status of voltageEnumeration.1.3.6.1.4.1.12148.10.9.9.1.2
loadVoltageDescriptionA textual description of the voltage. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.9.9.1.3
loadVoltageTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.9.9.1.4
loadVoltageEnableThis value once enabled, the alarm condition of the LVLD will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.9.9.1.5
loadVoltageValueThe measured value of the voltage.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.9.1.6
.1.3.6.1.4.1.12148.10.10.16.4 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryTestResultTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryTestResultTable'
This table contains the battery test results stored in controller.
batteryTestResultEntry row .1.3.6.1.4.1.12148.10.10.16.4.1
Column Syntax OID
batteryTestResultIndexA index pointing to one of ten possible battery test resultsInteger32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.10.16.4.1.1
batteryTestResultStartDateTimeThis is the time and date when the test started.SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.12148.10.10.16.4.1.2
batteryTestResultDurationThis is the test duration in minutes.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.3
batteryTestResultDischargedThis is the discharged Ah during test.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.4
batteryTestResultQualityThis is the calculated battery quality (SoH)in percentage.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.5
batteryTestResultEndVoltageThis is the test end voltage in volt.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.6
batteryTestResultTestResultThis is the test result.Enumeration.1.3.6.1.4.1.12148.10.10.16.4.1.7
batteryTestResultTerminationCriteriaThis is the test Termination Criteria.Enumeration.1.3.6.1.4.1.12148.10.10.16.4.1.8
batteryTestResultBatteryTemperatureThis is the battery temperatureSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.9
.1.3.6.1.4.1.12148.10.10.18.2 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankTable'
batteryBankEntry row .1.3.6.1.4.1.12148.10.10.18.2.1
Column Syntax OID
batteryBankIndexIndex used for navigating the rows 1..8 of batteryBankTableInteger32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.10.18.2.1.1
batteryBankStatusThe overall status of battery bankEnumeration.1.3.6.1.4.1.12148.10.10.18.2.1.2
batteryBankNumberOfTemperaturesNumber of temperature measurements in battery bank.Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.18.2.1.3
batteryBankNumberOfCurrentsNumber of current measurements in battery bank.Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.18.2.1.4
batteryBankNumberOfFusesNumber of fuses installed in battery bank.Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.18.2.1.5
batteryBankNumberOfSymmetriesNumber of symmetry measurements available in battery bank.Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.18.2.1.6
.1.3.6.1.4.1.12148.10.10.18.3 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankTemperatureTable'
batteryBankTemperatureEntry row .1.3.6.1.4.1.12148.10.10.18.3.1
Column Syntax OID
batteryTemperatureIndexThis index denotes which row in the temperature input table.
The size of the table is defined by the batteryBankNumberOfTemp
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.18.3.1.1
batteryTemperatureStatusThe status of battery temperature monitorEnumeration.1.3.6.1.4.1.12148.10.10.18.3.1.2
batteryTemperatureDescriptionA textual description of the battery temperature monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.18.3.1.3
batteryTemperatureTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.18.3.1.4
batteryTemperatureAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.10.18.3.1.5
batteryTemperatureValueThe measured battery temperature.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.6
batteryTemperatureMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.7
batteryTemperatureMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.8
batteryTemperatureMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.9
batteryTemperatureMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.10
.1.3.6.1.4.1.12148.10.10.18.4 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankCurrentTable'
batteryBankCurrentEntry row .1.3.6.1.4.1.12148.10.10.18.4.1
Column Syntax OID
batteryCurrentIndexThis index denotes which row in the current input table.
The size of the table is defined by the system
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.18.4.1.1
batteryCurrentStatusThe status of battery current monitorEnumeration.1.3.6.1.4.1.12148.10.10.18.4.1.2
batteryCurrentDescriptionA textual description of the battery current monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.18.4.1.3
batteryCurrentTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.18.4.1.4
batteryCurrentAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.10.18.4.1.5
batteryCurrentValueThe measured battery currentSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.6
batteryCurrentMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.7
batteryCurrentMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.8
batteryCurrentMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.9
batteryCurrentMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.10
.1.3.6.1.4.1.12148.10.10.18.5 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankFuseTable'
batteryBankFuseEntry row .1.3.6.1.4.1.12148.10.10.18.5.1
Column Syntax OID
batteryFuseIndexThis index denotes which row in the fuse table.
The size of the table is defined by the system
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.18.5.1.1
batteryFuseStatusThe status of battery fuse monitorEnumeration.1.3.6.1.4.1.12148.10.10.18.5.1.2
batteryFuseDescriptionA textual description of the battery fuse monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.18.5.1.3
batteryFuseTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.18.5.1.4
batteryFuseAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.10.18.5.1.5
batteryFuseValueThe measured value of battery fuse input.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.5.1.6
.1.3.6.1.4.1.12148.10.10.18.6 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankSymmetryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankSymmetryTable'
batteryBankSymmetryEntry row .1.3.6.1.4.1.12148.10.10.18.6.1
Column Syntax OID
batteryBankSymmetryIndexThis index denotes which row in the symmetry input table.
The size of the table is defined by the batteryMonitorNumberOfSymmetries
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.10.18.6.1.1
batteryBankSymmetryStatusThe status of battery symmetry monitorEnumeration.1.3.6.1.4.1.12148.10.10.18.6.1.2
batteryBankSymmetryDescriptionA textual description of the battery monitor symmetry. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.18.6.1.3
batteryBankSymmetryTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.18.6.1.4
batteryBankSymmetryAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.10.18.6.1.5
batteryBankSymmetryMeasureValueThe measured battery symmetry voltage in battery monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.6.1.6
batteryBankSymmetryDeltaValueThe measured battery symmetry delta voltage in battery monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.6.1.7
batteryBankSymmetryMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.6.1.8
batteryBankSymmetryMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.6.1.9
.1.3.6.1.4.1.12148.10.10.19.2 · 1 row entry · 5 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorsTable'
batteryMonitorsEntry row .1.3.6.1.4.1.12148.10.10.19.2.1
Column Syntax OID
batteryMonitorIndexIndex used for navigating the rows 1..8 of batteryMonitorsTableInteger32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.10.19.2.1.1
batteryMonitorNumberOfTemperaturesThe number of temperature measurements in battery monitor.Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.19.2.1.2
batteryMonitorNumberOfCurrentsThe number of current measurements in battery monitor.Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.19.2.1.3
batteryMonitorNumberOfFusesThe number of fuse measurements in battery monitor.Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.19.2.1.4
batteryMonitorNumberOfSymmetriesThe number of symmetry measurements in battery monitor.Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.19.2.1.5
.1.3.6.1.4.1.12148.10.10.19.3 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorTemperatureTable'
Column Syntax OID
batteryMonitorTemperatureIndexThis index denotes which row in the temperature input table.
The size of the table is defined by the batteryMonitorNumberOfTemperatures
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.19.3.1.1
batteryMonitorTemperatureStatusThe status of battery temperature monitorEnumeration.1.3.6.1.4.1.12148.10.10.19.3.1.2
batteryMonitorTemperatureDescriptionA textual description of the battery monitor temperature. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.19.3.1.3
batteryMonitorTemperatureTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.19.3.1.4
batteryMonitorTemperatureAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.10.19.3.1.5
batteryMonitorTemperatureValueThe measured battery temperature in battery monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.6
batteryMonitorTemperatureMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.7
batteryMonitorTemperatureMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.8
batteryMonitorTemperatureMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.9
batteryMonitorTemperatureMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.10
.1.3.6.1.4.1.12148.10.10.19.4 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorCurrentTable'
batteryMonitorCurrentEntry row .1.3.6.1.4.1.12148.10.10.19.4.1
Column Syntax OID
batteryMonitorCurrentIndexThis index denotes which row in the current input table.
The size of the table is defined by the batteryMonitorNumberOfCurrents
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.19.4.1.1
batteryMonitorCurrentStatusThe status of battery current monitorEnumeration.1.3.6.1.4.1.12148.10.10.19.4.1.2
batteryMonitorCurrentDescriptionA textual description of the battery monitor current. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.19.4.1.3
batteryMonitorCurrentTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.19.4.1.4
batteryMonitorCurrentAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.10.19.4.1.5
batteryMonitorCurrentValueThe measured battery current in battery monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.6
batteryMonitorCurrentMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.7
batteryMonitorCurrentMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.8
batteryMonitorCurrentMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.9
batteryMonitorCurrentMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.10
.1.3.6.1.4.1.12148.10.10.19.5 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorFuseTable'
batteryMonitorFuseEntry row .1.3.6.1.4.1.12148.10.10.19.5.1
Column Syntax OID
batteryMonitorFuseIndexThis index denotes which row in the fuse table.
The size of the table is defined by the batteryMonitorNumberOfFuses
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.19.5.1.1
batteryMonitorFuseStatusThe status of battery fuse monitorEnumeration.1.3.6.1.4.1.12148.10.10.19.5.1.2
batteryMonitorFuseDescriptionA textual description of the battery monitor fuse. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.19.5.1.3
batteryMonitorFuseTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.19.5.1.4
batteryMonitorFuseAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.10.19.5.1.5
batteryMonitorFuseValueThe measured value of battery fuse in battery monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.5.1.6
.1.3.6.1.4.1.12148.10.10.19.6 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorSymmetryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorSymmetryTable'
Column Syntax OID
batteryMonitorSymmetryIndexThis index denotes which row in the symmetry input table.
The size of the table is defined by the batteryMonitorNumberOfSymmetries
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.10.19.6.1.1
batteryMonitorSymmetryStatusThe status of battery symmetry monitorEnumeration.1.3.6.1.4.1.12148.10.10.19.6.1.2
batteryMonitorSymmetryDescriptionA textual description of the battery monitor symmetry. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.19.6.1.3
batteryMonitorSymmetryTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.19.6.1.4
batteryMonitorSymmetryAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.10.19.6.1.5
batteryMonitorSymmetryMeasureValueThe measured battery symmetry voltage in battery monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.6.1.6
batteryMonitorSymmetryDeltaValueThe measured battery symmetry delta voltage in battery monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.6.1.7
batteryMonitorSymmetryMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.6.1.8
batteryMonitorSymmetryMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.6.1.9
.1.3.6.1.4.1.12148.10.10.20.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryEnergyLogLastHoursTable'
This table contains hourly energy log of battery.
batteryEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.10.20.3.1
Column Syntax OID
batteryEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of batteryEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.20.3.1.1
batteryEnergyLogLastHoursValueEnergy value logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.20.3.1.2
.1.3.6.1.4.1.12148.10.10.20.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryEnergyLogLastDaysTable'
This table contains daily energy log of battery.
batteryEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.10.20.5.1
Column Syntax OID
batteryEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of batteryEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.20.5.1.1
batteryEnergyLogLastDaysValueEnergy value logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.20.5.1.2
.1.3.6.1.4.1.12148.10.10.20.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryEnergyLogLastWeeksTable'
This table contains weekly energy log of battery.
batteryEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.10.20.7.1
Column Syntax OID
batteryEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of batteryEnergyLogLastWeekTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.20.7.1.1
batteryEnergyLogLastWeeksValueEnergy value logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.20.7.1.2
.1.3.6.1.4.1.12148.10.10.21.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryCycleLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryCycleLogDaysTable'
This table contains daily battery discharge cycle log.
batteryCycleLogDaysEntry row .1.3.6.1.4.1.12148.10.10.21.3.1
Column Syntax OID
batteryCycleLogDaysIndexIndex used for navigating the rows 1..52 of batteryCycleLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.21.3.1.1
batteryCycleLogDaysValueNumber of discharge cycles logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.21.3.1.2
.1.3.6.1.4.1.12148.10.10.21.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryCycleLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryCycleLogWeeksTable'
This table contains weekly battery discharge cycle log.
batteryCycleLogWeeksEntry row .1.3.6.1.4.1.12148.10.10.21.5.1
Column Syntax OID
batteryCycleLogWeeksIndexIndex used for navigating the rows 1..52 of batteryCycleLogLastWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.21.5.1.1
batteryCycleLogWeeksValueNumber of discharge cycles logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.21.5.1.2
.1.3.6.1.4.1.12148.10.10.21.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryCycleLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryCycleLogMonthsTable'
This table contains monthly battery discharge cycle log.
batteryCycleLogMonthsEntry row .1.3.6.1.4.1.12148.10.10.21.7.1
Column Syntax OID
batteryCycleLogMonthsIndexIndex used for navigating the rows 1..52 of batteryCycleLogLastMonthTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.21.7.1.1
batteryCycleLogMonthsValueNumber of discharge cycles logged every month.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.21.7.1.2
.1.3.6.1.4.1.12148.10.10.25.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryRunTimeLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryRunTimeLogDaysTable'
This table contains daily battery run time log.
batteryRunTimeLogDaysEntry row .1.3.6.1.4.1.12148.10.10.25.3.1
Column Syntax OID
batteryRunTimeLogDaysIndexIndex used for navigating the rows 1..52 of batteryRunTimeLogDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.25.3.1.1
batteryRunTimeLogDaysValueBattery running minutes logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.25.3.1.2
.1.3.6.1.4.1.12148.10.10.25.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryRunTimeLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryRunTimeLogWeeksTable'
This table contains weekly battery run time log.
batteryRunTimeLogWeeksEntry row .1.3.6.1.4.1.12148.10.10.25.5.1
Column Syntax OID
batteryRunTimeLogWeeksIndexIndex used for navigating the rows 1..52 of batteryRunTimeLogWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.25.5.1.1
batteryRunTimeLogWeeksValueBattery running hours logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.25.5.1.2
.1.3.6.1.4.1.12148.10.10.25.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryRunTimeLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryRunTimeLogMonthsTable'
This table contains monthly battery run time log.
batteryRunTimeLogMonthsEntry row .1.3.6.1.4.1.12148.10.10.25.7.1
Column Syntax OID
batteryRunTimeLogMonthsIndexIndex used for navigating the rows 1..52 of batteryRunTimeLogMonthsTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.25.7.1.1
batteryRunTimeLogMonthsValueBattery running hours logged every month.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.25.7.1.2
.1.3.6.1.4.1.12148.10.10.26.4 · 1 row entry · 20 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryModuleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryModuleTable'
Information of individule battery module
batteryModuleEntry row .1.3.6.1.4.1.12148.10.10.26.4.1
Column Syntax OID
batteryModuleIndexIndex used for navigating the rows 1..100 of batteryModuleTableInteger32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.10.26.4.1.1
batteryModuleStatusThe status value for the battery moduleEnumeration.1.3.6.1.4.1.12148.10.10.26.4.1.2
batteryModuleBatteryVoltageBattery voltage valueSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.3
batteryModuleBatteryCurrentBattery current valueSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.4
batteryModuleBatteryRemCapBattery remaining capacity valueSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.5
batteryModuleBatteryTemperatureBattery temperature valueSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.6
batteryModuleBatteryQualityBattery quality valueSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.7
batteryModuleMaxChargeCurrentMaximal charging current in AmpSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.8
batteryModuleMaxDischargeCurrentMaximal discharge current in AmpSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.9
batteryModuleBatteryModeBattery modeSNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.10.26.4.1.10
batteryModuleChargeModeCharge modeSNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.10.26.4.1.11
batteryModuleManufacturerBattery manufaturerOctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.10.26.4.1.12
batteryModulePartNumberPart numberOctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.26.4.1.13
batteryModuleSerialNumberSerial numberOctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.26.4.1.14
batteryModuleSoftwareVersionSoftware versionOctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.26.4.1.15
batteryModuleProductionDateDate of productionOctetString
Constraints:
range: 8-11
.1.3.6.1.4.1.12148.10.10.26.4.1.16
batteryModuleAccumulatedAhChargedAccumulated Ah chargedSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.17
batteryModuleAccumulatedAhDischargedAccumulated Ah dischargedSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.18
batteryModuleNoOfChargeCyclesNumber of charge cyclesSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.19
batteryModuleNoOfDischargeCyclesNumber of discharge cyclesSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.20
.1.3.6.1.4.1.12148.10.11.1 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk inputControlUnitsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::inputControlUnitsTable'
inputControlUnitsEntry row .1.3.6.1.4.1.12148.10.11.1.1
Column Syntax OID
inputControlUnitIndexIndex used for navigating the rows of inputControlUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.11.1.1.1
inputControlUnitNumberOfInputsNumber of programmable inputs available in controller.Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.11.1.1.2
.1.3.6.1.4.1.12148.10.11.2 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk inputControlUnitInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::inputControlUnitInputTable'
This table contains the status of the programmable inputs for Control Units.
Column Syntax OID
inputControlUnitInputIndexIndex used for navigating the rows of inputControlUnitInputTable
The size of the table is defined by the inputControlUnitNumberOfInputs
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.11.2.1.1
inputControlUnitInputStatusProgrammable input status.Enumeration.1.3.6.1.4.1.12148.10.11.2.1.2
inputControlUnitInputDescriptionA textual description of the programmable input. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.11.2.1.3
inputControlUnitInputTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.11.2.1.4
inputControlUnitInputAlarmEnableThis will enable or disable this inputs Alarm functionality.
Setting 'disabled' here will turn off lock the status to 'disabled' state
Enumerationr/w.1.3.6.1.4.1.12148.10.11.2.1.5
inputControlUnitInputValueThe inputs measured Value. Depending on the type of input, this may
represent a Voltage, a Temperature, a Current or a Boolean value.
Note: This value can only be set for virtual input on SP2 master or Smartpack S.
Whe…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.11.2.1.6
inputControlUnitInputConfigurationConfiguration of the input type. Configurations available for different controllers are as follows:
SP2 Basic(normally open, normally closed);
SP2 BasicInd(normally open,normally closed, temperature, temp 4-20mA, voltag…
Enumerationr/w.1.3.6.1.4.1.12148.10.11.2.1.7
.1.3.6.1.4.1.12148.10.11.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk inputIoUnitsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::inputIoUnitsTable'
inputIoUnitsEntry row .1.3.6.1.4.1.12148.10.11.3.1
Column Syntax OID
inputIoUnitIndexIndex used for navigating the rows of inputIoUnitsTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.11.3.1.1
inputIoUnitNumberOfInputsNumber of programmable inputs available in IO unit.Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.11.3.1.2
.1.3.6.1.4.1.12148.10.11.4 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk inputIoUnitProgInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::inputIoUnitProgInputTable'
This table contains the status of the programmable inputs for I/O monitor units.
.
inputIoUnitProgInputEntry row .1.3.6.1.4.1.12148.10.11.4.1
Column Syntax OID
inputIoUnitProgInputIndexThe Index to the Input of the selected I/O monitor unit.
Or the input number if you like.
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.12148.10.11.4.1.1
inputIoUnitProgInputStatusProgrammable input status.Enumeration.1.3.6.1.4.1.12148.10.11.4.1.2
inputIoUnitProgInputDescriptionA textual description of the programmable input in IO unit. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.11.4.1.3
inputIoUnitProgInputTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.11.4.1.4
inputIoUnitProgInputAlarmEnableThis will enable or disable this inputs Alarm functionality.
Setting 'disabled' here will turn off lock the status to 'disabled' state
Enumerationr/w.1.3.6.1.4.1.12148.10.11.4.1.5
inputIoUnitProgInputValueThe inputs measured Value. Depending on the type of input, this may
represent a Voltage, a Temperature, a Current or a Boolean value.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.11.4.1.6
inputIoUnitProgInputConfigurationConfiguration of the input type. Configurations available for IO unit are normally open,
normally closed, diode matrix, voltage and clock. Note: If an input is set to 'clock', it can
not be configurated to 'normally op…
Enumerationr/w.1.3.6.1.4.1.12148.10.11.4.1.7
.1.3.6.1.4.1.12148.10.12.1 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk outputControlUnitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::outputControlUnitTable'
outputControlUnitEntry row .1.3.6.1.4.1.12148.10.12.1.1
Column Syntax OID
outputControlUnitIndexIndex used for navigating the rows of outputControlUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.12.1.1.1
outputControlUnitNumberOfOutputsNumber of outputs available in controller.Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.12.1.1.2
.1.3.6.1.4.1.12148.10.12.2 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk outputControlUnitOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::outputControlUnitOutputTable'
This table contains the status of the outputs for Control Units.
Column Syntax OID
outputControlUnitOutputIndexIndex used for navigating the rows of outputControlUnitoutputTable
The size of the table is defined by the outputControlUnitNumberOfOutputs
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.12.2.1.1
outputControlUnitOutputStatusGeneral output relays may be 'energized' or 'not energized'. 'energized' and
'not energized' correspond
to normal and alarm condition respectively for normally
activated configuration.
Latched contactors may have val…
Enumeration.1.3.6.1.4.1.12148.10.12.2.1.2
outputControlUnitOutputDescriptionA textual description of the output. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.12.2.1.3
.1.3.6.1.4.1.12148.10.12.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk outputIoUnitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::outputIoUnitTable'
outputIoUnitEntry row .1.3.6.1.4.1.12148.10.12.3.1
Column Syntax OID
outputIoUnitIndexIndex used for navigating the rows of outputIoUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.12.3.1.1
outputIoUnitNumberOfOutputsNumber of outputs available in IO unit.Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.12.3.1.2
.1.3.6.1.4.1.12148.10.12.4 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk outputIoUnitOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::outputIoUnitOutputTable'
This table contains the status of the outputs for IO Units.
outputIoUnitOutputEntry row .1.3.6.1.4.1.12148.10.12.4.1
Column Syntax OID
outputIoUnitOutputIndexIndex used for navigating the rows of outputIOUnitOutputTable
The size of the table is defined by the outputIOUnitNumberOfOutputs
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.12.4.1.1
outputIoUnitOutputStatusGeneral output relays may be 'energized' or 'not energized'.
Latched contactors may have values 'disconnected' or 'connected'
Enumeration.1.3.6.1.4.1.12148.10.12.4.1.2
outputIoUnitOutputDescriptionA textual description of the output in IO unit. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.12.4.1.3
.1.3.6.1.4.1.12148.10.13.4.6 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk snmpTrapsTargetAddressTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::snmpTrapsTargetAddressTable'
This table shows the trap target address. Note that it is NOT allowed 
to change or create SNMP v3 trap target address IPs.
snmpTrapsTargetAddressEntry row .1.3.6.1.4.1.12148.10.13.4.6.1
Column Syntax OID
snmpTrapsTargetAddressIndexInteger32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.13.4.6.1.1
snmpTrapsTargetAddressIPNote that it is only allowed
to change or create SNMP v2c trap target address IPs.
OctetStringr/w
Constraints:
range: 1-80
.1.3.6.1.4.1.12148.10.13.4.6.1.2
snmpTrapsTargetAddressPortSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.4.6.1.3
snmpTrapsTargetAddressVersionEnumeration.1.3.6.1.4.1.12148.10.13.4.6.1.4
.1.3.6.1.4.1.12148.10.13.7.2 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlSystemIoUnitsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlSystemIoUnitsTable'
controlSystemIoUnitsEntry row .1.3.6.1.4.1.12148.10.13.7.2.1
Column Syntax OID
controlSystemIoUnitIndexIndex used for navigating the rows of controlSystemIoUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.7.2.1.1
controlSystemIoUnitNumberOfTemperaturesNumber of temperature measurements available in IO unitInteger32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.13.7.2.1.2
controlSystemIoUnitNumberOfFansNumber of fan measurements available in IO unitInteger32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.13.7.2.1.3
.1.3.6.1.4.1.12148.10.13.7.3 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlSystemIoUnitTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlSystemIoUnitTemperatureTable'
Column Syntax OID
controlSystemIoUnitTemperatureIndexIndex used for navigating the rows of controlSystemIoUnitTemperatureTable
The size of the table is defined by the controlSystemIoUnitNumberOfTemperatures
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.12148.10.13.7.3.1.1
controlSystemIoUnitTemperatureStatusThe status of temperature monitorEnumeration.1.3.6.1.4.1.12148.10.13.7.3.1.2
controlSystemIoUnitTemperatureDescriptionA textual description of the temperature monitor in control system. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.7.3.1.3
controlSystemIoUnitTemperatureTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.7.3.1.4
controlSystemIoUnitTemperatureAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.13.7.3.1.5
controlSystemIoUnitTemperatureValueThe measured temperature value.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.6
controlSystemIoUnitTemperatureMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.7
controlSystemIoUnitTemperatureMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.8
controlSystemIoUnitTemperatureMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.9
controlSystemIoUnitTemperatureMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.10
.1.3.6.1.4.1.12148.10.13.7.4 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlSystemIoUnitFanTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlSystemIoUnitFanTable'
Column Syntax OID
controlSystemIoUnitFanIndexIndex used for navigating the rows 1..2 of ioUnitFan TableInteger32
Constraints:
range: 1-2
.1.3.6.1.4.1.12148.10.13.7.4.1.1
controlSystemIoUnitFanSpeedValueThe measured fan speedSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.4.1.2
controlSystemIoUnitFanSpeedDeviationThe measured fan speed deviationSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.4.1.3
controlSystemIoUnitFanControlFan speed control value in percentageSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.4.1.4
.1.3.6.1.4.1.12148.10.13.8.2 · 1 row entry · 8 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlUnitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlUnitTable'
A table containing an inventory listing. Each row represent one of the system hardware 
unit that is connected to the can bus. These units are system controllers, 
battery monitors, I/O units, AC Mains Monitor boxes and load monitors.  Due to the system 
architechture the tables index are not contiguous. Each unit type har its own address 
range on the can bus.  All unit types except the system controller may contain 
from 0 to 14 units.  The system controlller can never be zero.  Then there is no powersystem.
controlUnitEntry row .1.3.6.1.4.1.12148.10.13.8.2.1
One row in the table containing all hardware units connected to the canbus.
Column Syntax OID
controlUnitIndexIndex used for navigating the rows of controlUnitTable
The size of the table is defined by the controlUnitNumberOfUnits
Integer32
Constraints:
range: 1-254
.1.3.6.1.4.1.12148.10.13.8.2.1.1
controlUnitDescriptionA textual description of the control unitOctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.12148.10.13.8.2.1.2
controlUnitStatusThe overall status of the control unit.Enumeration.1.3.6.1.4.1.12148.10.13.8.2.1.3
controlUnitSerialNumberSerial number of the control unit.OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.13.8.2.1.4
controlUnitHwPartNumberHardware part number of the control unit.OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.13.8.2.1.5
controlUnitHwVersionHardware version of the control unit.OctetString
Constraints:
range: 0-20
.1.3.6.1.4.1.12148.10.13.8.2.1.6
controlUnitSwPartNumberSoftware part number of the control unit.OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.13.8.2.1.7
controlUnitSwVersionSoftware version of the control unit.OctetString
Constraints:
range: 0-20
.1.3.6.1.4.1.12148.10.13.8.2.1.8
.1.3.6.1.4.1.12148.10.13.9.2 · 1 row entry · 5 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorsTable'
currentMonitorsEntry row .1.3.6.1.4.1.12148.10.13.9.2.1
Column Syntax OID
currentMonitorIndexIndex used for navigating the rows of currentMonitorsTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.9.2.1.1
currentMonitorTypeThis shows if the current monitor is configured as standard load monitor (1), load current
monitor (2), rectifier current monitor (3), dcdc current monitor (4), solar current monitor (5),
wind current monitor (6) or fu…
Enumeration.1.3.6.1.4.1.12148.10.13.9.2.1.2
currentMonitorIdThis is the unit index for each current monitor type.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.2.1.3
currentMonitorNumberOfFusesNumber of fuse measurements in current monitor.Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.13.9.2.1.4
currentMonitorNumberOfCurrentsNumber of current measurements in current monitor.Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.13.9.2.1.5
.1.3.6.1.4.1.12148.10.13.9.3 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorFuseTable'
currentMonitorFuseEntry row .1.3.6.1.4.1.12148.10.13.9.3.1
Column Syntax OID
currentMonitorFuseIndexIndex used for navigating the rows of currentMonitorFuseTable
The size of the table is defined by the currentMonitorNumberOfFuses
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.13.9.3.1.1
currentMonitorFuseStatusThe status of fuse in current monitorEnumeration.1.3.6.1.4.1.12148.10.13.9.3.1.2
currentMonitorFuseDescriptionA textual description of the fuse monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.13.9.3.1.3
currentMonitorFuseTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.9.3.1.4
currentMonitorFuseAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.13.9.3.1.5
currentMonitorFuseValueThe measured fuse value.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.3.1.6
.1.3.6.1.4.1.12148.10.13.9.4 · 1 row entry · 8 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorCurrentTable'
Column Syntax OID
currentMonitorCurrentIndexIndex used for navigating the rows of currentMonitorCurrentTable
The size of the table is defined by the currentMonitorNumberOfCurrents
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.13.9.4.1.1
currentMonitorCurrentStatusThe status of current in current monitorEnumeration.1.3.6.1.4.1.12148.10.13.9.4.1.2
currentMonitorCurrentDescriptionA textual description of the current monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.9.4.1.3
currentMonitorCurrentTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.9.4.1.4
currentMonitorCurrentAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.13.9.4.1.5
currentMonitorCurrentValueThe measured current value.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.4.1.6
currentMonitorCurrentMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.4.1.7
currentMonitorCurrentMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.4.1.8
.1.3.6.1.4.1.12148.10.13.9.5 · 1 row entry · 1 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorEnergyLogAccumulatedTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorEnergyLogAccumulatedTable'
This table contains the accumulated energy consumption measured in current monitor
Column Syntax OID
currentMonitorEnergyLogAccumulatedThe accumulated energy consumption valueSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.5.1.1
.1.3.6.1.4.1.12148.10.13.9.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorEnergyLogLastHoursTable'
This table contains energy consumption values logged every hour in current monitor.
Column Syntax OID
currentMonitorEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of currentMonitorEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.9.7.1.1
currentMonitorEnergyLogLastHoursValueEnergy consumption value logged every hour in current monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.7.1.2
.1.3.6.1.4.1.12148.10.13.9.9 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorEnergyLogLastDaysTable'
This table contains energy consumption values logged every day in current monitor.
Column Syntax OID
currentMonitorEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of currentMonitorEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.9.9.1.1
currentMonitorEnergyLogLastDaysValueEnergy consumption value logged every day in current monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.9.1.2
.1.3.6.1.4.1.12148.10.13.9.11 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorEnergyLogLastWeeksTable'
This table contains energy consumption values logged every week in current monitor.
Column Syntax OID
currentMonitorEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of currentMonitorEnergyLogLastWeekTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.9.11.1.1
currentMonitorEnergyLogLastWeeksValueEnergy consumption value logged every week in current monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.11.1.2
.1.3.6.1.4.1.12148.10.13.10.2 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorsTable'
flexiMonitorsEntry row .1.3.6.1.4.1.12148.10.13.10.2.1
Column Syntax OID
flexiMonitorIndexIndex used for navigating the rows of flexiMonitorsTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.10.2.1.1
flexiMonitorTypeThis shows if the fleximonitor is configured as battery monitor (1), load
monitor (2), rectifier monitor (3), controller monitor(4), dcdc monitor (5), solar monitor (6),
wind monitor (7) or fuel cell monitor 8).
Enumeration.1.3.6.1.4.1.12148.10.13.10.2.1.2
flexiMonitorIdThis is the unit index for each fleximonitor type.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.2.1.3
flexiMonitorNumberOfInputsNumber of inputs in fleximonitor.Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.13.10.2.1.4
flexiMonitorNumberOfOutputsNumber of outputs in fleximonitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.2.1.5
flexiMonitorNumberOfCurrentInputsNumber of current inputs in fleximonitor.Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.13.10.2.1.6
.1.3.6.1.4.1.12148.10.13.10.3 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorInputTable'
flexiMonitorInputEntry row .1.3.6.1.4.1.12148.10.13.10.3.1
Column Syntax OID
flexiMonitorInputIndexIndex used for navigating the rows of flexiMonitorInputTable
The size of the table is defined by the flexiMonitorNumberOfInputs
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.13.10.3.1.1
flexiMonitorInputStatusProgrammable input status.Enumeration.1.3.6.1.4.1.12148.10.13.10.3.1.2
flexiMonitorInputDescriptionA textual description of the programmable input. This is stored in the system controller
and can be changed by the user. .
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.10.3.1.3
flexiMonitorInputTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.10.3.1.4
flexiMonitorInputAlarmEnableThis will enable or disable this inputs Alarm functionality.
Setting 'disabled' here will turn off lock the status to 'disabled' state
Enumerationr/w.1.3.6.1.4.1.12148.10.13.10.3.1.5
flexiMonitorInputValueThe inputs measured Value. Depending on the type of input, this may
represent a Voltage, a Temperature, a Current, a Speed or a Boolean value.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.3.1.6
flexiMonitorInputConfigurationConfiguration of the input type. Available configurations are: ProgIn-Normally Open(1), ProgIn-Normally Closed(2),
Voltage(3), Temperature(4),Current(5),Speed(6),Fuse-Normally Open(7),Fuse-Normally Closed(8), Fuse-Diode…
Enumerationr/w.1.3.6.1.4.1.12148.10.13.10.3.1.7
.1.3.6.1.4.1.12148.10.13.10.4 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorOutputTable'
flexiMonitorOutputEntry row .1.3.6.1.4.1.12148.10.13.10.4.1
Column Syntax OID
flexiMonitorOutputIndexIndex used for navigating the rows of flexiMonitorOutputTable
The size of the table is defined by the flexiMonitorNumberOfOutputs
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.13.10.4.1.1
flexiMonitorOutputStatusGeneral output relays may be 'energized' or 'not energized'. 'energized' and
'not energized' correspond
to normal and alarm condition respectively for normally
activated configuration.
Latched contactors may have val…
Enumeration.1.3.6.1.4.1.12148.10.13.10.4.1.2
flexiMonitorOutputDescriptionA textual description of the output. This is stored in the system controller
and can be changed by the user.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.13.10.4.1.3
.1.3.6.1.4.1.12148.10.13.10.5 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorCurrentInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorCurrentInputTable'
Column Syntax OID
flexiMonitorCurrentInputIndexIndex used for navigating the rows of flexiMonitorInputTable
The size of the table is defined by the flexiMonitorNumberOfInputs
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.13.10.5.1.1
flexiMonitorCurrentInputDescriptionA textual description of the programmable input. This is stored in the system controller
and can be changed by the user. .
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.10.5.1.2
flexiMonitorCurrentInputPricePerKWPrice per kW. To be used together with energy cost logs.SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.13.10.5.1.3
flexiMonitorCurrentInputCurrencyThe currency used in energy cost logs.OctetStringr/w
Constraints:
range: 1-6
.1.3.6.1.4.1.12148.10.13.10.5.1.4
.1.3.6.1.4.1.12148.10.13.10.7 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyCostLogLastMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyCostLogLastMonthsTable'
Column Syntax OID
flexiMonitorEnergyCostLogLastMonthsIndexIndex used for navigating the rows 1..12SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.7.1.1
flexiMonitorEnergyCostLogLastMonthsMonthIndex by monthEnumeration.1.3.6.1.4.1.12148.10.13.10.7.1.2
flexiMonitorEnergyCostLogLastMonthsEnergyEnergy in kWhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.7.1.3
flexiMonitorEnergyCostLogLastMonthsCostEnergy costSNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.13.10.7.1.4
.1.3.6.1.4.1.12148.10.13.10.9 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyCostLogLastYearsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyCostLogLastYearsTable'
Column Syntax OID
flexiMonitorEnergyCostLogLastYearsIndexIndex used for navigating the rows 1..12SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.9.1.1
flexiMonitorEnergyCostLogLastYearsYearIndex by yearOctetString
Constraints:
range: 4-4
.1.3.6.1.4.1.12148.10.13.10.9.1.2
flexiMonitorEnergyCostLogLastYearsEnergyEnergy in kWhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.9.1.3
flexiMonitorEnergyCostLogLastYearsCostEnergy costSNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.13.10.9.1.4
.1.3.6.1.4.1.12148.10.13.10.10 · 1 row entry · 1 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyLogAccumulatedTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyLogAccumulatedTable'
This table contains the accumulated energy consumption measured in fleximonitor
Column Syntax OID
flexiMonitorEnergyLogAccumulatedThe accumulated energy consumption valueSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.10.1.1
.1.3.6.1.4.1.12148.10.13.10.12 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyLogLastHoursTable'
This table contains energy consumption values logged every hour in fleximonitor.
Column Syntax OID
flexiMonitorEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of flexiMonitorEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.10.12.1.1
flexiMonitorEnergyLogLastHoursValueEnergy consumption value logged every hour in fleximonitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.12.1.2
.1.3.6.1.4.1.12148.10.13.10.14 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyLogLastDaysTable'
This table contains energy consumption values logged every day in fleximonitor.
Column Syntax OID
flexiMonitorEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of flexiMonitorEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.10.14.1.1
flexiMonitorEnergyLogLastDaysValueEnergy consumption value logged every day in fleximonitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.14.1.2
.1.3.6.1.4.1.12148.10.13.10.16 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyLogLastWeeksTable'
This table contains energy consumption values logged every week in fleximonitor.
Column Syntax OID
flexiMonitorEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of flexiMonitorEnergyLogLastWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.10.16.1.1
flexiMonitorEnergyLogLastWeeksValueEnergy consumption value logged every week in fleximonitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.16.1.2
.1.3.6.1.4.1.12148.10.13.11.1 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainControlUnitsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainControlUnitsTable'
mainControlUnitsEntry row .1.3.6.1.4.1.12148.10.13.11.1.1
Column Syntax OID
mainControlUnitIndexIndex used for navigating the rows of controlUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.11.1.1.1
mainControlUnitNumberOfTemperaturesTotal number of temperature measurements in main controllerInteger32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.11.1.1.2
.1.3.6.1.4.1.12148.10.13.11.2 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainControlUnitTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainControlUnitTemperatureTable'
Column Syntax OID
mainControlUnitTemperatureIndexThis index denotes which row in the temperature input table.
The size of the table is defined by the batteryBankNumberOfTemp
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.13.11.2.1.1
mainControlUnitTemperatureStatusThe status of battery temperature monitorEnumeration.1.3.6.1.4.1.12148.10.13.11.2.1.2
mainControlUnitTemperatureDescriptionA textual description of the battery temperature monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.11.2.1.3
mainControlUnitTemperatureTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.11.2.1.4
mainControlUnitTemperatureAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.13.11.2.1.5
mainControlUnitTemperatureValueThe measured battery temperature.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.6
mainControlUnitTemperatureMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.7
mainControlUnitTemperatureMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.8
mainControlUnitTemperatureMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.9
mainControlUnitTemperatureMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.10
.1.3.6.1.4.1.12148.10.13.11.3 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainControlUnitEarthFaultTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainControlUnitEarthFaultTable'
mainControlUnitEarthFaultEntry row .1.3.6.1.4.1.12148.10.13.11.3.1
Column Syntax OID
mainControlUnitEarthFaultStatusThis status value shows if the earth resistance is lower than the defined alarm level.Enumeration.1.3.6.1.4.1.12148.10.13.11.3.1.1
mainControlUnitEarthFaultDescriptionA textual description of the earth fault monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.11.3.1.2
mainControlUnitEarthFaultTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.3.1.3
mainControlUnitEarthFaultAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.13.11.3.1.4
mainControlUnitEarthFaultValueThe measured value of the earth resistance in kOhm.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.3.1.5
mainControlUnitEarthFaultMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.3.1.6
.1.3.6.1.4.1.12148.10.13.24 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlSystemGenericModbusDataTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlSystemGenericModbusDataTable'
Column Syntax OID
controlSystemGenericModbusDataIndexIndex used for navigating the rows of table
The size of the table is defined by the system
Integer32
Constraints:
range: 1-50
.1.3.6.1.4.1.12148.10.13.24.1.1
controlSystemGenericModbusDataDescriptiondescription of generic Modbus dataOctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.12148.10.13.24.1.2
controlSystemGenericModbusDataValueValue of generic Modbus dataOctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.12148.10.13.24.1.3
controlSystemGenericModbusDataUnitUnit of generic Modbus dataOctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.13.24.1.4
.1.3.6.1.4.1.12148.10.13.26 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericAlarmMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericAlarmMonitorTable'
generic alarm monitors to be used with 3rd-party modbus devices
genericAlarmMonitorEntry row .1.3.6.1.4.1.12148.10.13.26.1
Column Syntax OID
genericAlarmMonitorIndexInteger32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.13.26.1.1
genericAlarmMonitorStatusThe state of the alarm monitor can be either one of the defined enumerated valuesEnumeration.1.3.6.1.4.1.12148.10.13.26.1.2
genericAlarmMonitorDescriptionA textual description of the generic alarm monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.26.1.3
genericAlarmMonitorTrapRepeatCounterThe number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.26.1.4
genericAlarmMonitorAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.13.26.1.5
genericAlarmMonitorValueThe generic alarm monitor value. Scale is dependent on the scale setting of the corresponding generic modbus value.Integer32
Constraints:
range: 0-9999
.1.3.6.1.4.1.12148.10.13.26.1.6
genericAlarmMonitorUnitA textual description of the unit of generic alarm monitor.OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.26.1.7
.1.3.6.1.4.1.12148.10.13.27 · 1 row entry · 5 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericLogsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericLogsTable'
Generic logs connected to the last ten generic alarm monitors (#91-#100)
genericLogsEntry row .1.3.6.1.4.1.12148.10.13.27.1
Column Syntax OID
genericLogsIndexgeneric log index 1...10Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.13.27.1.1
genericLogsAccumulatedThis is the accumulated trip log value in hours.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.27.1.2
genericLogsDaysNumberOfEntriesThis is the maximal number of entries stored in daily logSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.27.1.3
genericLogsWeeksNumberOfEntriesThis is the maximal number of entries stored in weekly logSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.27.1.4
genericLogsMonthsNumberOfEntriesThis is the maximal number of entries stored in monthly logSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.27.1.5
.1.3.6.1.4.1.12148.10.13.28 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericLogDaysTable'
This table contains daily generic log.
genericLogDaysEntry row .1.3.6.1.4.1.12148.10.13.28.1
Column Syntax OID
genericLogDaysIndexIndex used for navigating the rows 1..52 of genericLogDaysTableUnsigned32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.28.1.1
genericLogDaysValuegeneric monitor value in minutes logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.28.1.2
.1.3.6.1.4.1.12148.10.13.29 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericLogWeeksTable'
This table contains weekly generic log.
genericLogWeeksEntry row .1.3.6.1.4.1.12148.10.13.29.1
Column Syntax OID
genericLogWeeksIndexIndex used for navigating the rows 1..52 of genericLogWeeksTableUnsigned32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.29.1.1
genericLogWeeksValuegeneric monitor value in hours logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.29.1.2
.1.3.6.1.4.1.12148.10.13.30 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericLogMonthsTable'
This table contains monthly generic log.
genericLogMonthsEntry row .1.3.6.1.4.1.12148.10.13.30.1
Column Syntax OID
genericLogMonthsIndexIndex used for navigating the rows 1..52 of genericLogMonthsTableUnsigned32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.30.1.1
genericLogMonthsValuegeneric monitor value in hours logged every month.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.30.1.2
.1.3.6.1.4.1.12148.10.14.1 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk alarmGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::alarmGroupTable'
alarmGroupEntry row .1.3.6.1.4.1.12148.10.14.1.1
Indexes
Column Syntax OID
alarmGroupIndexIndex used for navigating the rows 1..49 of alarmGroupTableInteger32
Constraints:
range: 1-49
.1.3.6.1.4.1.12148.10.14.1.1.1
alarmGroupStatusThe status of alarm groupEnumeration.1.3.6.1.4.1.12148.10.14.1.1.2
alarmGroupDescriptionA textual description of the alarm group. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.14.1.1.3
.1.3.6.1.4.1.12148.10.15.16.4 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2TestResultTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2TestResultTable'
This table contains the battery test results stored in controller.
batteryGroup2TestResultEntry row .1.3.6.1.4.1.12148.10.15.16.4.1
Column Syntax OID
batteryGroup2TestResultIndexA index pointing to one of ten possible battery test resultsInteger32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.15.16.4.1.1
batteryGroup2TestResultStartDateTimeThis is the time and date when the test started.SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.12148.10.15.16.4.1.2
batteryGroup2TestResultDurationThis is the test duration in minutes.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.3
batteryGroup2TestResultDischargedThis is the discharged Ah during test.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.4
batteryGroup2TestResultQualityThis is the calculated battery quality (SoH)in percentage.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.5
batteryGroup2TestResultEndVoltageThis is the test end voltage in volt.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.6
batteryGroup2TestResultTestResultThis is the test result.Enumeration.1.3.6.1.4.1.12148.10.15.16.4.1.7
batteryGroup2TestResultTerminationCriteriaThis is the test Termination Criteria.Enumeration.1.3.6.1.4.1.12148.10.15.16.4.1.8
batteryGroup2TestResultBatteryTemperatureThis is the battery temperatureSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.9
.1.3.6.1.4.1.12148.10.15.18.6 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2BankTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2BankTemperatureTable'
batteryGroup2BankTemperatureEntry row .1.3.6.1.4.1.12148.10.15.18.6.1
Column Syntax OID
batteryGroup2TemperatureIndexThis index denotes which row in the temperature input table.
The size of the table is defined by the batteryGroup2BankNumberOfTemperatures
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.15.18.6.1.1
batteryGroup2TemperatureStatusThe status of battery temperature monitorEnumeration.1.3.6.1.4.1.12148.10.15.18.6.1.2
batteryGroup2TemperatureDescriptionA textual description of the battery temperature monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.15.18.6.1.3
batteryGroup2TemperatureTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.15.18.6.1.4
batteryGroup2TemperatureAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.15.18.6.1.5
batteryGroup2TemperatureValueThe measured battery temperature.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.6
batteryGroup2TemperatureMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.7
batteryGroup2TemperatureMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.8
batteryGroup2TemperatureMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.9
batteryGroup2TemperatureMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.10
.1.3.6.1.4.1.12148.10.15.18.7 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2BankCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2BankCurrentTable'
batteryGroup2BankCurrentEntry row .1.3.6.1.4.1.12148.10.15.18.7.1
Column Syntax OID
batteryGroup2CurrentIndexThis index denotes which row in the current input table.
The size of the table is defined by the system
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.15.18.7.1.1
batteryGroup2CurrentStatusThe status of battery current monitorEnumeration.1.3.6.1.4.1.12148.10.15.18.7.1.2
batteryGroup2CurrentDescriptionA textual description of the battery current monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.15.18.7.1.3
batteryGroup2CurrentTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.15.18.7.1.4
batteryGroup2CurrentAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.15.18.7.1.5
batteryGroup2CurrentValueThe measured battery currentSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.6
batteryGroup2CurrentMajorHighLevelThe major high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.7
batteryGroup2CurrentMinorHighLevelThe minor high alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.8
batteryGroup2CurrentMinorLowLevelThe minor low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.9
batteryGroup2CurrentMajorLowLevelThe major low alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.10
.1.3.6.1.4.1.12148.10.15.18.8 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2BankFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2BankFuseTable'
batteryGroup2BankFuseEntry row .1.3.6.1.4.1.12148.10.15.18.8.1
Column Syntax OID
batteryGroup2FuseIndexThis index denotes which row in the fuse table.
The size of the table is defined by the system
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.15.18.8.1.1
batteryGroup2FuseStatusThe status of battery fuse monitorEnumeration.1.3.6.1.4.1.12148.10.15.18.8.1.2
batteryGroup2FuseDescriptionA textual description of the battery fuse monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.15.18.8.1.3
batteryGroup2FuseTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.15.18.8.1.4
batteryGroup2FuseAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.15.18.8.1.5
batteryGroup2FuseValueThe measured value of battery fuse input.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.8.1.6
.1.3.6.1.4.1.12148.10.15.18.9 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2BankSymmetryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2BankSymmetryTable'
batteryGroup2BankSymmetryEntry row .1.3.6.1.4.1.12148.10.15.18.9.1
Column Syntax OID
batteryGroup2BankSymmetryIndexThis index denotes which row in the symmetry input table.
The size of the table is defined by the batteryMonitorNumberOfSymmetries
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.15.18.9.1.1
batteryGroup2BankSymmetryStatusThe status of battery symmetry monitorEnumeration.1.3.6.1.4.1.12148.10.15.18.9.1.2
batteryGroup2BankSymmetryDescriptionA textual description of the battery monitor symmetry. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.15.18.9.1.3
batteryGroup2BankSymmetryTrapRepeatCounterThe number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.15.18.9.1.4
batteryGroup2BankSymmetryAlarmEnableThis value once enabled, the alarm condition of the monitor will be reported.Enumerationr/w.1.3.6.1.4.1.12148.10.15.18.9.1.5
batteryGroup2BankSymmetryMeasureValueThe measured battery symmetry voltage in battery monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.9.1.6
batteryGroup2BankSymmetryDeltaValueThe measured battery symmetry delta voltage in battery monitor.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.9.1.7
batteryGroup2BankSymmetryMajorAlarmLevelThe major alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.9.1.8
batteryGroup2BankSymmetryMinorAlarmLevelThe minor alarm limitSNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.9.1.9
.1.3.6.1.4.1.12148.10.15.19.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2EnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2EnergyLogLastHoursTable'
This table contains hourly energy log of battery.
Column Syntax OID
batteryGroup2EnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of batteryEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.19.3.1.1
batteryGroup2EnergyLogLastHoursValueEnergy value logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.19.3.1.2
.1.3.6.1.4.1.12148.10.15.19.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2EnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2EnergyLogLastDaysTable'
This table contains daily energy log of battery.
batteryGroup2EnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.15.19.5.1
Column Syntax OID
batteryGroup2EnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of batteryEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.19.5.1.1
batteryGroup2EnergyLogLastDaysValueEnergy value logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.19.5.1.2
.1.3.6.1.4.1.12148.10.15.19.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2EnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2EnergyLogLastWeeksTable'
This table contains weekly energy log of battery.
Column Syntax OID
batteryGroup2EnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of batteryEnergyLogLastWeekTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.19.7.1.1
batteryGroup2EnergyLogLastWeeksValueEnergy value logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.19.7.1.2
.1.3.6.1.4.1.12148.10.15.20.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2CycleLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2CycleLogDaysTable'
This table contains daily battery discharge cycle log.
batteryGroup2CycleLogDaysEntry row .1.3.6.1.4.1.12148.10.15.20.3.1
Column Syntax OID
batteryGroup2CycleLogDaysIndexIndex used for navigating the rows 1..52 of batteryCycleLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.20.3.1.1
batteryGroup2CycleLogDaysValueNumber of discharge cycles logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.20.3.1.2
.1.3.6.1.4.1.12148.10.15.20.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2CycleLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2CycleLogWeeksTable'
This table contains weekly battery discharge cycle log.
batteryGroup2CycleLogWeeksEntry row .1.3.6.1.4.1.12148.10.15.20.5.1
Column Syntax OID
batteryGroup2CycleLogWeeksIndexIndex used for navigating the rows 1..52 of batteryCycleLogLastWeeksTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.20.5.1.1
batteryGroup2CycleLogWeeksValueNumber of discharge cycles logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.20.5.1.2
.1.3.6.1.4.1.12148.10.15.20.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2CycleLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2CycleLogMonthsTable'
This table contains monthly battery discharge cycle log.
batteryGroup2CycleLogMonthsEntry row .1.3.6.1.4.1.12148.10.15.20.7.1
Column Syntax OID
batteryGroup2CycleLogMonthsIndexIndex used for navigating the rows 1..52 of batteryCycleLogLastMonthTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.20.7.1.1
batteryGroup2CycleLogMonthsValueNumber of discharge cycles logged every month.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.20.7.1.2
.1.3.6.1.4.1.12148.10.19.6 · 1 row entry · 26 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk fuelCellTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::fuelCellTable'
This table shows the information of each fuel cell installed in the system.
fuelCellEntry row .1.3.6.1.4.1.12148.10.19.6.1
Indexes
Column Syntax OID
fuelCellIndexIndex used for navigating the rows 1..100 of fuelCellTableInteger32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.19.6.1.1
fuelCellStatusThe overall status of fuel cell.Enumeration.1.3.6.1.4.1.12148.10.19.6.1.2
fuelCellModeThe mode value of fuel cell.Enumeration.1.3.6.1.4.1.12148.10.19.6.1.3
fuelCellCurrentValueThe output current value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.4
fuelCellVoltageValueThe input voltage value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.5
fuelCellPowerValueThe input voltage value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.6
fuelCellTypeType of fuel cellOctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.19.6.1.7
fuelCellInletTemperatureThe inlet temp value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.8
fuelCellOutletTemperatureThe outlet temp value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.9
fuelCellRoomTemperatureThe room temp value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.10
fuelCellFanThe fan value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.11
fuelCellH2Storage1The H2 storage 1 value of fuel cell.Enumeration.1.3.6.1.4.1.12148.10.19.6.1.12
fuelCellH2Storage2The H2 storage 2 value of fuel cell.Enumeration.1.3.6.1.4.1.12148.10.19.6.1.13
fuelCellH2Storage3The H2 storage 3 value of fuel cell.Enumeration.1.3.6.1.4.1.12148.10.19.6.1.14
fuelCellDO22The DO22 value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.15
fuelCellDO23The DO23 value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.16
fuelCellDO24The DO24 value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.17
fuelCellDO25The DO25 value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.18
fuelCellDO26The DO26 value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.19
fuelCellDO27The DO27 value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.20
fuelCellDC1currentThe DC1 current value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.21
fuelCellDC2currentThe DC2 current value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.22
fuelCellDC3currentThe DC3 current value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.23
fuelCellDC4currentThe DC4 current value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.24
fuelCellDC5currentThe DC5 current value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.25
fuelCellDC6currentThe DC6 current value of fuel cell.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.26
.1.3.6.1.4.1.12148.10.19.7.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk fuelCellsEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::fuelCellsEnergyLogLastHoursTable'
This table contains hourly energy log of fuel cell.
fuelCellsEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.19.7.3.1
Column Syntax OID
fuelCellsEnergyLogLastHoursIndexIndex used for navigating the rows 1..52 of fuelCellsEnergyLogLastHoursTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.19.7.3.1.1
fuelCellsEnergyLogLastHoursValueEnergy value logged every hour.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.7.3.1.2
.1.3.6.1.4.1.12148.10.19.7.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk fuelCellsEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::fuelCellsEnergyLogLastDaysTable'
This table contains daily energy log of fuel cell.
fuelCellsEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.19.7.5.1
Column Syntax OID
fuelCellsEnergyLogLastDaysIndexIndex used for navigating the rows 1..52 of fuelCellsEnergyLogLastDaysTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.19.7.5.1.1
fuelCellsEnergyLogLastDaysValueEnergy value logged every day.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.7.5.1.2
.1.3.6.1.4.1.12148.10.19.7.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk fuelCellsEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::fuelCellsEnergyLogLastWeeksTable'
This table contains weekly energy log of fuel cell.
fuelCellsEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.19.7.7.1
Column Syntax OID
fuelCellsEnergyLogLastWeeksIndexIndex used for navigating the rows 1..52 of fuelCellsEnergyLogLastWeekTableInteger32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.19.7.7.1.1
fuelCellsEnergyLogLastWeeksValueEnergy value logged every week.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.7.7.1.2