SP2-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
144
Rows
144
Columns
679
.1.3.6.1.4.1.12148.10.3.4 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsVoltageTable'
This table contains information about mains voltage monitor
mainsVoltageEntry row .1.3.6.1.4.1.12148.10.3.4.1
Column Syntax OID
Index used for navigating the rows 1..12 of mainsVoltageTable
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.12148.10.3.4.1.1
The status of the measured mains voltage.
Enumeration .1.3.6.1.4.1.12148.10.3.4.1.2
A textual description of the mains voltage monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.3.4.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.4.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.3.4.1.5
The value of the measured mains voltage.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.4.1.10
.1.3.6.1.4.1.12148.10.3.5.2 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorsTable'
This table contains the number of voltage, current and frequency measurements in each AC Mains Monitor
mainsMonitorsEntry row .1.3.6.1.4.1.12148.10.3.5.2.1
Column Syntax OID
Index used for navigating the rows of mainsMonitorsTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.3.5.2.1.1
The number of voltage measurements in the AC Mains Monitor
Integer32
Constraints:
range: 0-3
.1.3.6.1.4.1.12148.10.3.5.2.1.2
The number of current measurements in the AC Mains Monitor
Integer32
Constraints:
range: 0-3
.1.3.6.1.4.1.12148.10.3.5.2.1.3
The number of frequency measurements in the AC Mains Monitor
Integer32
Constraints:
range: 0-3
.1.3.6.1.4.1.12148.10.3.5.2.1.4
.1.3.6.1.4.1.12148.10.3.5.3 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorVoltageTable'
This table contains information about mains voltage in AC Mains Monitor
mainsMonitorVoltageEntry row .1.3.6.1.4.1.12148.10.3.5.3.1
Column Syntax OID
Index used for navigating the rows 1..3 of mainsMonitorVolatgeTable
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.12148.10.3.5.3.1.1
The status of the measured mains voltage in AC Mains Monitor.
Enumeration .1.3.6.1.4.1.12148.10.3.5.3.1.2
A textual description of the mains voltage in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.3.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.3.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.3.5.3.1.5
The value of the measured mains voltage in AC Mains Monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.3.1.10
.1.3.6.1.4.1.12148.10.3.5.4 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorCurrentTable'
This table contains information about mains current in AC Mains Monitor
mainsMonitorCurrentEntry row .1.3.6.1.4.1.12148.10.3.5.4.1
Column Syntax OID
The status of the measured mains current in AC Mains Monitor.
Enumeration .1.3.6.1.4.1.12148.10.3.5.4.1.1
A textual description of the mains current in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.4.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.4.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.3.5.4.1.4
The value of the measured mains current in AC Mains Monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.4.1.5
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.4.1.6
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.4.1.7
.1.3.6.1.4.1.12148.10.3.5.5 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorFrequencyTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorFrequencyTable'
This table contains information about mains frequency in AC Mains Monitor
mainsMonitorFrequencyEntry row .1.3.6.1.4.1.12148.10.3.5.5.1
Column Syntax OID
The status of the measured mains frequency in AC Mains Monitor.
Enumeration .1.3.6.1.4.1.12148.10.3.5.5.1.1
A textual description of the mains frequency in AC Mains Monitor. This is stored in the system
controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.3.5.5.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.5.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.3.5.5.1.4
The value of the measured mains frequency in AC Mains Monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.5
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.6
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.7
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.8
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.5.1.9
.1.3.6.1.4.1.12148.10.3.5.6 · 1 row entry · 1 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorEnergyLogAccumulatedTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorEnergyLogAccumulatedTable'
This table contains the accumulated energy consumption measured in AC Mains Monitor
mainsMonitorEnergyLogAccumulatedEntry row .1.3.6.1.4.1.12148.10.3.5.6.1
Column Syntax OID
The accumulated energy consumption value
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.6.1.1
.1.3.6.1.4.1.12148.10.3.5.8 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorEnergyLogLastHoursTable'
This table contains energy consumption values logged every hour in AC Mains Monitor.
mainsMonitorEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.3.5.8.1
Column Syntax OID
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.5.8.1.1
Energy consumption value logged every hour in AC Mains Monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.8.1.2
.1.3.6.1.4.1.12148.10.3.5.10 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorEnergyLogLastDaysTable'
This table contains energy consumption values logged every day in AC Mains Monitor.
mainsMonitorEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.3.5.10.1
Column Syntax OID
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.5.10.1.1
Energy consumption value logged every day in AC Mains Monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.10.1.2
.1.3.6.1.4.1.12148.10.3.5.12 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorEnergyLogLastWeeksTable'
This table contains energy consumption values logged every week in AC Mains Monitor.
mainsMonitorEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.3.5.12.1
Column Syntax OID
Index used for navigating the rows 1..52 of mainsMonitorEnergyLogLastWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.5.12.1.1
Energy consumption value logged every week in AC Mains Monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.12.1.2
.1.3.6.1.4.1.12148.10.3.5.13 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorActivePowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorActivePowerTable'
This table contains information about mains active power in AC Mains Monitor
mainsMonitorActivePowerEntry row .1.3.6.1.4.1.12148.10.3.5.13.1
Column Syntax OID
The status of the measured mains active power in AC Mains Monitor.
Enumeration .1.3.6.1.4.1.12148.10.3.5.13.1.1
A textual description of the mains active power in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.13.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.13.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.3.5.13.1.4
The value of the measured mains active power in AC Mains Monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.13.1.5
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.13.1.6
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.13.1.7
.1.3.6.1.4.1.12148.10.3.5.14 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorReactivePowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorReactivePowerTable'
This table contains information about mains reactive power in AC Mains Monitor
mainsMonitorReactivePowerEntry row .1.3.6.1.4.1.12148.10.3.5.14.1
Column Syntax OID
The status of the measured mains reactive power in AC Mains Monitor.
Enumeration .1.3.6.1.4.1.12148.10.3.5.14.1.1
A textual description of the mains reactive power in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.14.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.14.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.3.5.14.1.4
The value of the measured mains reactive power in AC Mains Monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.14.1.5
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.14.1.6
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.14.1.7
.1.3.6.1.4.1.12148.10.3.5.15 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsMonitorApparentPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsMonitorApparentPowerTable'
This table contains information about mains apparent power in AC Mains Monitor
mainsMonitorApparentPowerEntry row .1.3.6.1.4.1.12148.10.3.5.15.1
Column Syntax OID
The status of the measured mains apparent power in AC Mains Monitor.
Enumeration .1.3.6.1.4.1.12148.10.3.5.15.1.1
A textual description of the mains apparent power in AC Mains Monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.3.5.15.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.3.5.15.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.3.5.15.1.4
The value of the measured mains apparent power in AC Mains Monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.15.1.5
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.15.1.6
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.5.15.1.7
.1.3.6.1.4.1.12148.10.3.6.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsOutageLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsOutageLogDaysTable'
This table contains daily mains outage or running time log depending on the log mode.
mainsOutageLogDaysEntry row .1.3.6.1.4.1.12148.10.3.6.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of mainsOutageLogDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.6.3.1.1
Mains outage or running time value in minutes, logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.6.3.1.2
.1.3.6.1.4.1.12148.10.3.6.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsOutageLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsOutageLogWeeksTable'
This table contains weekly mains outage or running time log depending on the log mode.
mainsOutageLogWeeksEntry row .1.3.6.1.4.1.12148.10.3.6.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of mainsOutageLogWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.6.5.1.1
Mains outage or running time value in hours, logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.6.5.1.2
.1.3.6.1.4.1.12148.10.3.6.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsOutageLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsOutageLogMonthsTable'
This table contains monthly mains outage or running time log depending on the log mode.
mainsOutageLogMonthsEntry row .1.3.6.1.4.1.12148.10.3.6.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of mainsOutageLogMonthsTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.6.7.1.1
Mains outage or running time value in hours, logged every month.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.6.7.1.2
.1.3.6.1.4.1.12148.10.3.8 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupsTable'
This table contains the status of mains group and number of phases in each group.
mainsGroupsEntry row .1.3.6.1.4.1.12148.10.3.8.1
Indexes
Column Syntax OID
Index used for navigating the rows 1..10 of mainsGroupTable
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.3.8.1.1
The status of mains group.
Enumeration .1.3.6.1.4.1.12148.10.3.8.1.2
This value showing the number of phases of the mains group subsystem.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.8.1.3
.1.3.6.1.4.1.12148.10.3.9 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupMainsFailureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupMainsFailureTable'
This table contains information about mains failure monitor of mains group
mainsGroupMainsFailureEntry row .1.3.6.1.4.1.12148.10.3.9.1
Indexes
Column Syntax OID
This status value shows if the number of failed phases is higher than the defined alarm level for the mains group
Enumeration .1.3.6.1.4.1.12148.10.3.9.1.1
A textual description of the mains group phase failure monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.3.9.1.2
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.9.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.3.9.1.4
The detected number of failed phases in the mains group.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.9.1.5
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.9.1.6
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.9.1.7
.1.3.6.1.4.1.12148.10.3.10 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupVoltageTable'
This table contains information about mains voltage monitors for mains group
mainsGroupVoltageEntry row .1.3.6.1.4.1.12148.10.3.10.1
Column Syntax OID
Index used for navigating the rows 1..12 of mainsGroupVoltageTable
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.12148.10.3.10.1.1
The status of the measured mains voltage of the mains group.
Enumeration .1.3.6.1.4.1.12148.10.3.10.1.2
A textual description of the mains voltage monitor of the mains group. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.3.10.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.3.10.1.5
The value of the measured mains voltage in the mains group.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.10.1.10
.1.3.6.1.4.1.12148.10.3.11 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupOutageLogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupOutageLogTable'
This table contains total mains outage of the mains group and number of entries in each log table.
mainsGroupOutageLogEntry row .1.3.6.1.4.1.12148.10.3.11.1
Indexes
Column Syntax OID
This is the total mains outage time measured in hours in the mains group.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.11.1.1
This is the maximal number of entries stored in daily mains outage log.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.11.1.2
This is the maximal number of entries stored in weekly mains outage time log.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.11.1.3
This is the maximal number of entries stored in monthly mains outage time log.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.11.1.4
.1.3.6.1.4.1.12148.10.3.12 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupOutageLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupOutageLogDaysTable'
This table contains daily mains outage time log of mains group.
mainsGroupOutageLogDaysEntry row .1.3.6.1.4.1.12148.10.3.12.1
Column Syntax OID
Index used for navigating the rows 1..52 of mainsGroupOutageLogDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.12.1.1
Mains outage time value in minutes of each mains group, logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.12.1.2
.1.3.6.1.4.1.12148.10.3.13 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupOutageLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupOutageLogWeeksTable'
This table contains weekly mains outage time log of mains group.
mainsGroupOutageLogWeeksEntry row .1.3.6.1.4.1.12148.10.3.13.1
Column Syntax OID
Index used for navigating the rows 1..52 of mainsGroupOutageLogWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.13.1.1
Mains outage time value in hours of each mains group, logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.13.1.2
.1.3.6.1.4.1.12148.10.3.14 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainsGroupOutageLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainsGroupOutageLogMonthsTable'
This table contains monthly mains outage time log of mains group.
mainsGroupOutageLogMonthsEntry row .1.3.6.1.4.1.12148.10.3.14.1
Column Syntax OID
Index used for navigating the rows 1..52 of mainsGroupOutageLogMonthsTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.3.14.1.1
Mains outage time value in hours of each mains group, logged every month.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.3.14.1.2
.1.3.6.1.4.1.12148.10.4.16 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorDailyRunSetupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorDailyRunSetupTable'
This table contains configurations of generator daily run.
generatorDailyRunSetupEntry row .1.3.6.1.4.1.12148.10.4.16.1
Column Syntax OID
Index used for navigating the rows 1..7 of generatorDailyRunSetupTable
Enumeration .1.3.6.1.4.1.12148.10.4.16.1.1
Generator daily starting time.
Integer32r/w
Constraints:
range: 0-23
.1.3.6.1.4.1.12148.10.4.16.1.2
Generator daily stopping time.
Integer32r/w
Constraints:
range: 0-23
.1.3.6.1.4.1.12148.10.4.16.1.3
.1.3.6.1.4.1.12148.10.4.22 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorTankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorTankTable'
This table contains information about generator fuel tanks.
generatorTankEntry row .1.3.6.1.4.1.12148.10.4.22.1
Column Syntax OID
Index used for navigating the rows 1..2 of generatorTankTable
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.12148.10.4.22.1.1
The status of the measured fuel level in tank.
Enumeration .1.3.6.1.4.1.12148.10.4.22.1.2
A textual description of the fuel level monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.4.22.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.4.22.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.4.22.1.5
The value of the measured fuel level.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.22.1.10
.1.3.6.1.4.1.12148.10.4.23.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorEnergyLogLastHoursTable'
This table contains hourly energy log of generator.
generatorEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.4.23.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of generatorEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.23.3.1.1
Energy value logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.23.3.1.2
.1.3.6.1.4.1.12148.10.4.23.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorEnergyLogLastDaysTable'
This table contains daily energy log of generator.
generatorEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.4.23.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of generatorEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.23.5.1.1
Energy value logged every day
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.23.5.1.2
.1.3.6.1.4.1.12148.10.4.23.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorEnergyLogLastWeeksTable'
This table contains weekly energy log of generator.
generatorEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.4.23.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of generatorEnergyLogLastWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.23.7.1.1
Energy value logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.23.7.1.2
.1.3.6.1.4.1.12148.10.4.24.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorRunHoursLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorRunHoursLogLastDaysTable'
generator running time in minutes
generatorRunHoursLogLastDaysEntry row .1.3.6.1.4.1.12148.10.4.24.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of generatorRunHoursLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.24.3.1.1
Generator running time in minutes, logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.24.3.1.2
.1.3.6.1.4.1.12148.10.4.24.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorRunHoursLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorRunHoursLogLastWeeksTable'
generator running time in hours
generatorRunHoursLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.4.24.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of generatorRunHoursLogLastWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.24.5.1.1
Generator running time in hours, logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.24.5.1.2
.1.3.6.1.4.1.12148.10.4.24.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorRunHoursLogLastMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorRunHoursLogLastMonthsTable'
generator running time in hours
generatorRunHoursLogLastMonthsEntry row .1.3.6.1.4.1.12148.10.4.24.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of generatorRunHoursLogLastMonthsTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.24.7.1.1
Generator running time in hours, logged every month.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.24.7.1.2
.1.3.6.1.4.1.12148.10.4.25.1 · 1 row entry · 1 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorFuelConsumptionTotalUsedTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorFuelConsumptionTotalUsedTable'
This table contains total fuel consumption for each tank.
generatorFuelConsumptionTotalUsedEntry row .1.3.6.1.4.1.12148.10.4.25.1.1
Column Syntax OID
Total fuel consumption value.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.25.1.1.1
.1.3.6.1.4.1.12148.10.4.25.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorFuelConsumptionLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorFuelConsumptionLogLastDaysTable'
This table contains generator daily fuel consumption log.
generatorFuelConsumptionLogLastDaysEntry row .1.3.6.1.4.1.12148.10.4.25.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.25.3.1.1
Generator fuel consumption value, logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.25.3.1.2
.1.3.6.1.4.1.12148.10.4.25.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorFuelConsumptionLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorFuelConsumptionLogLastWeeksTable'
This table contains generator weekly fuel consumption log.
generatorFuelConsumptionLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.4.25.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.25.5.1.1
Generator fuel consumption value, logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.25.5.1.2
.1.3.6.1.4.1.12148.10.4.25.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk generatorFuelConsumptionLogLastMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::generatorFuelConsumptionLogLastMonthsTable'
This table contains generator hourly fuel consumption log.
generatorFuelConsumptionLogLastMonthsEntry row .1.3.6.1.4.1.12148.10.4.25.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of generatorFuelConsumptionLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.4.25.7.1.1
Generator fuel consumption value, logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.4.25.7.1.2
.1.3.6.1.4.1.12148.10.5.6 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierTable'
This table shows the information of each rectifier installed in the system.
rectifierEntry row .1.3.6.1.4.1.12148.10.5.6.1
Indexes
Column Syntax OID
Index used for navigating the rows 1..100 of rectifierTable
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.5.6.1.1
The overall status of rectifier.
Enumeration .1.3.6.1.4.1.12148.10.5.6.1.2
The output current value of rectifier.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.6.1.3
The input voltage value of rectifier.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.6.1.4
Type of rectifier
OctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.5.6.1.5
Hardware part number of rectifier
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.5.6.1.6
Hardware version number of rectifier
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.5.6.1.7
Part number of secondary software in rectifier
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.5.6.1.8
Version number of secondary software in rectifier
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.5.6.1.9
Serial number of rectifier
OctetString
Constraints:
range: 1-12
.1.3.6.1.4.1.12148.10.5.6.1.10
.1.3.6.1.4.1.12148.10.5.7.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifiersEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifiersEnergyLogLastHoursTable'
This table contains hourly energy log of rectifiers.
rectifiersEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.5.7.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.7.3.1.1
Energy value logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.7.3.1.2
.1.3.6.1.4.1.12148.10.5.7.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifiersEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifiersEnergyLogLastDaysTable'
This table contains daily energy log of rectifiers.
rectifiersEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.5.7.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.7.5.1.1
Energy value logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.7.5.1.2
.1.3.6.1.4.1.12148.10.5.7.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifiersEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifiersEnergyLogLastWeeksTable'
This table contains weekly energy log of rectifiers.
rectifiersEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.5.7.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of rectifiersEnergyLogLastWeekTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.7.7.1.1
Energy value logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.7.7.1.2
.1.3.6.1.4.1.12148.10.5.9 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupsTable'
This table contains status and the number of installed rectifiers of each rectifier groups.
rectifierGroupsEntry row .1.3.6.1.4.1.12148.10.5.9.1
Column Syntax OID
Index used for navigating the rows 1..10 of rectifierGroupsTable
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.5.9.1.1
The status of each rectifier group.
Enumeration .1.3.6.1.4.1.12148.10.5.9.1.2
Number of installed rectifiers in each rectifier groups
Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.12148.10.5.9.1.3
.1.3.6.1.4.1.12148.10.5.10 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupCurrentTable'
This table contains information about the total rectifier current of each rectifier groups, which is calculated 
by summing up current from each rectifier in a rectifier group.
rectifierGroupCurrentEntry row .1.3.6.1.4.1.12148.10.5.10.1
Column Syntax OID
The status of the measured total rectifier current of the rectifier group
Enumeration .1.3.6.1.4.1.12148.10.5.10.1.1
A textual description of the total rectifier current monitor of a rectifier group. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.5.10.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.10.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.5.10.1.4
The value of the measured total rectifier current of each rectifier group.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.10.1.5
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.10.1.6
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.10.1.7
.1.3.6.1.4.1.12148.10.5.11 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupCapacityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupCapacityTable'
This table contains information about the used rectifier capacity of each rectifier group.
rectifierGroupCapacityEntry row .1.3.6.1.4.1.12148.10.5.11.1
Column Syntax OID
The status of the measured used rectifier capacity of each rectifier group
Enumeration .1.3.6.1.4.1.12148.10.5.11.1.1
A textual description of the used rectifier capacity monitor of each rectifier group. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.5.11.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.11.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.5.11.1.4
The used rectifier capacity value presented in percentage of the total installed rectifier capacity of each rectifier group.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.11.1.5
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.11.1.6
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.11.1.7
.1.3.6.1.4.1.12148.10.5.12 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupErrorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupErrorTable'
This table contains information about the rectifier error monitor of each rectifier group.
rectifierGroupErrorEntry row .1.3.6.1.4.1.12148.10.5.12.1
Column Syntax OID
This status value shows if the number of failed units is higher than the defined alarm level.
Enumeration .1.3.6.1.4.1.12148.10.5.12.1.1
A textual description of the rectifier error monitor of each rectifier group. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.5.12.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.12.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.5.12.1.4
The number of failed rectifiers of each rectifier group.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.12.1.5
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.12.1.6
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.12.1.7
.1.3.6.1.4.1.12148.10.5.13 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupRectifierTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupRectifierTable'
This table shows the information of each rectifier installed in each of the rectifier group in the system.
rectifierGroupRectifierEntry row .1.3.6.1.4.1.12148.10.5.13.1
Column Syntax OID
Index used for navigating the rows 1..100 of rectifierGroupRectifierTable
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.5.13.1.1
The overall status of rectifier.
Enumeration .1.3.6.1.4.1.12148.10.5.13.1.2
The output current value of rectifier.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.13.1.3
The input voltage value of rectifier.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.13.1.4
Type of rectifier
OctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.5.13.1.5
Hardware part number of rectifier
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.5.13.1.6
Hardware version number of rectifier
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.5.13.1.7
Part number of secondary software in rectifier
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.5.13.1.8
Version number of secondary software in rectifier
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.5.13.1.9
.1.3.6.1.4.1.12148.10.5.14 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupEnergyLogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupEnergyLogTable'
This branch contains information about rectifiers' energy logs of each rectifier group.
rectifierGroupEnergyLogEntry row .1.3.6.1.4.1.12148.10.5.14.1
Column Syntax OID
This is the accumulated energy delivered from rectifiers of each rectifier group.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.14.1.1
This is the maximal number of entries stored in rectifier group hourly energy log.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.14.1.2
This is the maximal number of entries stored in rectifier group daily energy log.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.14.1.3
This is the maximal number of entries stored in rectifier group weekly energy log.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.14.1.4
.1.3.6.1.4.1.12148.10.5.15 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupEnergyLogLastHoursTable'
This table contains hourly energy log of each rectifier group
rectifierGroupEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.5.15.1
Column Syntax OID
Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.15.1.1
Energy value logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.15.1.2
.1.3.6.1.4.1.12148.10.5.16 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupEnergyLogLastDaysTable'
This table contains daily energy log of each rectifier group
rectifierGroupEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.5.16.1
Column Syntax OID
Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLasDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.16.1.1
Energy value logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.16.1.2
.1.3.6.1.4.1.12148.10.5.17 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupEnergyLogLastWeeksTable'
This table contains weekly energy log of each rectifier group
rectifierGroupEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.5.17.1
Column Syntax OID
Index used for navigating the rows 1..52 of rectifierGroupEnergyLogLastWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.5.17.1.1
Energy value logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.17.1.2
.1.3.6.1.4.1.12148.10.5.19 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk rectifierGroupTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::rectifierGroupTemperatureTable'
This table contains information about the highest rectifier temperature of each rectifier groups, which is calculated 
by summing up current from each rectifier in a rectifier group.
rectifierGroupTemperatureEntry row .1.3.6.1.4.1.12148.10.5.19.1
Column Syntax OID
The status of the measured highest rectifier temperature of the rectifier group
Enumeration .1.3.6.1.4.1.12148.10.5.19.1.1
A textual description of the highest rectifier temperature monitor of a rectifier group. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.5.19.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.5.19.1.4
The value of the measured highest rectifier temperature of each rectifier group.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.5
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.6
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.7
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.8
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.5.19.1.9
.1.3.6.1.4.1.12148.10.6.2 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcGroupsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcGroupsTable'
This table contains information about dcdc groups.
dcdcGroupsEntry row .1.3.6.1.4.1.12148.10.6.2.1
Indexes
Column Syntax OID
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.6.2.1.1
The overall status of dcdc group.
Enumeration .1.3.6.1.4.1.12148.10.6.2.1.2
Number of installed dcdc converters.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.2.1.3
Output voltage of dcdc converters
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.2.1.4
Number of dcdc currents
Integer32
Constraints:
range: 0-5
.1.3.6.1.4.1.12148.10.6.2.1.5
Number of dcdc capacities
Integer32
Constraints:
range: 0-5
.1.3.6.1.4.1.12148.10.6.2.1.6
Number of dcdc alarms
Integer32
Constraints:
range: 0-5
.1.3.6.1.4.1.12148.10.6.2.1.7
.1.3.6.1.4.1.12148.10.6.3 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcCurrentTable'
This table contains information about the total dcdc current.
dcdcCurrentEntry row .1.3.6.1.4.1.12148.10.6.3.1
Indexes
Column Syntax OID
The status of the measured total dcdc current.
Enumeration .1.3.6.1.4.1.12148.10.6.3.1.1
A textual description of the total dcdc current monitor. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.6.3.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.6.3.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.6.3.1.4
The value of the measured total dcdc current.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.3.1.5
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.3.1.6
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.3.1.7
.1.3.6.1.4.1.12148.10.6.4 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcCapacityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcCapacityTable'
This table contains information about the used dcdc capacity.
dcdcCapacityEntry row .1.3.6.1.4.1.12148.10.6.4.1
Indexes
Column Syntax OID
The status of the measured used dcdc capacity.
Enumeration .1.3.6.1.4.1.12148.10.6.4.1.1
A textual description of the used dcdc capacity monitor. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.6.4.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.6.4.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.6.4.1.4
The used dcdc capacity value presented in percentage of the total installed dcdc capacity.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.4.1.5
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.4.1.6
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.4.1.7

dcdcTable

table
.1.3.6.1.4.1.12148.10.6.5 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcTable'
This table shows the information of each dcdc converter installed in the system.
dcdcEntry row .1.3.6.1.4.1.12148.10.6.5.1
Column Syntax OID
Index used for navigating the rows 1..100 of dcdcTable
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.6.5.1.1
The overall status of dcdc converter
Enumeration .1.3.6.1.4.1.12148.10.6.5.1.2
The output current value of dcdc.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.5.1.3
The input voltage value of dcdc.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.5.1.4
Type of dcdc converter
OctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.6.5.1.5
Hardware part number of dcdc converter
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.6.5.1.6
Hardware version number of dcdc converter
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.6.5.1.7
Part number of secondary software in dcdc converter
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.6.5.1.8
Version number of secondary software in dcdc converter
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.6.5.1.9
.1.3.6.1.4.1.12148.10.6.6 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk dcdcErrorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::dcdcErrorTable'
This table contains information about the dcdc error monitor.
dcdcErrorEntry row .1.3.6.1.4.1.12148.10.6.6.1
Indexes
Column Syntax OID
This status value shows if the number of failed units is higher than the defined alarm level.
Enumeration .1.3.6.1.4.1.12148.10.6.6.1.1
A textual description of the dcdc error monitor. This is stored in the system controller
and can be changed by the user
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.6.6.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.6.6.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.6.6.1.4
The number of failed dcdc converters.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.6.1.5
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.6.1.6
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.6.6.1.7
.1.3.6.1.4.1.12148.10.7.6 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk solarChargerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::solarChargerTable'
This table shows the information of each solar charger installed in the system.
solarChargerEntry row .1.3.6.1.4.1.12148.10.7.6.1
Column Syntax OID
Index used for navigating the rows 1..100 of solarChargerTable
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.7.6.1.1
The overall status of solar charger.
Enumeration .1.3.6.1.4.1.12148.10.7.6.1.2
The output current value of solar charger.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.6.1.3
The input voltage value of solar charger.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.6.1.4
Type of solar charger
OctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.7.6.1.5
Hardware part number of solar charger
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.7.6.1.6
Hardware version number of solar charger
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.7.6.1.7
Part number of secondary software in solar charger
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.7.6.1.8
Version number of secondary software in solar charger
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.7.6.1.9
.1.3.6.1.4.1.12148.10.7.7.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk solarChargersEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::solarChargersEnergyLogLastHoursTable'
This table contains hourly energy log of solar chargers.
solarChargersEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.7.7.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.7.7.3.1.1
Energy value logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.7.3.1.2
.1.3.6.1.4.1.12148.10.7.7.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk solarChargersEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::solarChargersEnergyLogLastDaysTable'
This table contains daily energy log of solar chargers.
solarChargersEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.7.7.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.7.7.5.1.1
Energy value logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.7.5.1.2
.1.3.6.1.4.1.12148.10.7.7.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk solarChargersEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::solarChargersEnergyLogLastWeeksTable'
This table contains weekly energy log of solar chargers.
solarChargersEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.7.7.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of solarChargersEnergyLogLastWeekTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.7.7.7.1.1
Energy value logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.7.7.7.1.2
.1.3.6.1.4.1.12148.10.8.6 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk windChargerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::windChargerTable'
This table shows the information of each wind charger installed in the system.
windChargerEntry row .1.3.6.1.4.1.12148.10.8.6.1
Column Syntax OID
Index used for navigating the rows 1..100 of windChargerTable
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.8.6.1.1
The overall status of wind charger.
Enumeration .1.3.6.1.4.1.12148.10.8.6.1.2
The output current value of wind charger.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.6.1.3
The input voltage value of wind charger.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.6.1.4
Type of wind charger
OctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.8.6.1.5
Hardware part number of wind charger
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.8.6.1.6
Hardware version number of wind charger
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.8.6.1.7
Part number of secondary software in wind charger
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.8.6.1.8
Version number of secondary software in wind charger
OctetString
Constraints:
range: 0-6
.1.3.6.1.4.1.12148.10.8.6.1.9
.1.3.6.1.4.1.12148.10.8.7.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk windChargersEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::windChargersEnergyLogLastHoursTable'
This table contains hourly energy log of wind chargers.
windChargersEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.8.7.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of windChargersEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.8.7.3.1.1
Energy value logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.7.3.1.2
.1.3.6.1.4.1.12148.10.8.7.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk windChargersEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::windChargersEnergyLogLastDaysTable'
This table contains daily energy log of wind chargers.
windChargersEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.8.7.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of windChargersEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.8.7.5.1.1
Energy value logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.7.5.1.2
.1.3.6.1.4.1.12148.10.8.7.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk windChargersEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::windChargersEnergyLogLastWeeksTable'
This table contains weekly energy log of wind chargers.
windChargersEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.8.7.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of windChargersEnergyLogLastWeekTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.8.7.7.1.1
Energy value logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.8.7.7.1.2
.1.3.6.1.4.1.12148.10.9.5 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadGroupTable'
This table contains information about load groups.
loadGroupEntry row .1.3.6.1.4.1.12148.10.9.5.1
Indexes
Column Syntax OID
Index used for navigating the rows 1..8 of loadGroupTable
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.9.5.1.1
The status of load group
Enumeration .1.3.6.1.4.1.12148.10.9.5.1.2
Number of LVLDs installed in load group
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.9.5.1.3
Number of voltages in load group
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.9.5.1.4
.1.3.6.1.4.1.12148.10.9.6 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadLVLDTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadLVLDTable'
This table contains information about LVLDs
loadLVLDEntry row .1.3.6.1.4.1.12148.10.9.6.1
Column Syntax OID
Index used for navigating the rows 1..8 of loadLVLDTable
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.9.6.1.1
The status of LVLD
Enumeration .1.3.6.1.4.1.12148.10.9.6.1.2
A textual description of the LVLD. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.9.6.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.9.6.1.4
This value once enabled, the alarm condition of the LVLD will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.9.6.1.5
The measured value of the LVLD.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.6.1.6
The load Contactor's Reconnect Voltage
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.6.1.7
The load Contactor's Disconnect Voltage
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.6.1.8
Enable/disable LVLD disconnect delay.
Enumerationr/w .1.3.6.1.4.1.12148.10.9.6.1.9
LVLD disconnect delay time in minutes.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.6.1.10
.1.3.6.1.4.1.12148.10.9.7 · 1 row entry · 5 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadFuseTable'
This table contains information about load fuse
loadFuseEntry row .1.3.6.1.4.1.12148.10.9.7.1
Indexes
Column Syntax OID
The status of load fuse
Enumeration .1.3.6.1.4.1.12148.10.9.7.1.1
A textual description of the load fuse monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.9.7.1.2
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.9.7.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.9.7.1.4
The measured value of the load fuse.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.7.1.5
.1.3.6.1.4.1.12148.10.9.8.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadEnergyLogLastHoursTable'
loadEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.9.8.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of loadEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.9.8.3.1.1
Energy value logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.8.3.1.2
.1.3.6.1.4.1.12148.10.9.8.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadEnergyLogLastDaysTable'
loadEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.9.8.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of loadEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.9.8.5.1.1
Energy value logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.8.5.1.2
.1.3.6.1.4.1.12148.10.9.8.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadEnergyLogLastWeeksTable'
loadEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.9.8.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of loadEnergyLogLastWeekTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.9.8.7.1.1
Energy value logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.8.7.1.2
.1.3.6.1.4.1.12148.10.9.9 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk loadVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::loadVoltageTable'
This table contains information about voltages
loadVoltageEntry row .1.3.6.1.4.1.12148.10.9.9.1
Column Syntax OID
Index used for navigating the rows 1..3 of loadVoltageTable
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.12148.10.9.9.1.1
The status of voltage
Enumeration .1.3.6.1.4.1.12148.10.9.9.1.2
A textual description of the voltage. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.9.9.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.9.9.1.4
This value once enabled, the alarm condition of the LVLD will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.9.9.1.5
The measured value of the voltage.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.9.9.1.6
.1.3.6.1.4.1.12148.10.10.16.4 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryTestResultTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryTestResultTable'
This table contains the battery test results stored in controller.
batteryTestResultEntry row .1.3.6.1.4.1.12148.10.10.16.4.1
Column Syntax OID
A index pointing to one of ten possible battery test results
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.10.16.4.1.1
This is the time and date when the test started.
SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.12148.10.10.16.4.1.2
This is the test duration in minutes.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.3
This is the discharged Ah during test.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.4
This is the calculated battery quality (SoH)in percentage.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.5
This is the test end voltage in volt.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.6
This is the test result.
Enumeration .1.3.6.1.4.1.12148.10.10.16.4.1.7
This is the test Termination Criteria.
Enumeration .1.3.6.1.4.1.12148.10.10.16.4.1.8
This is the battery temperature
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.16.4.1.9
.1.3.6.1.4.1.12148.10.10.18.2 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankTable'
batteryBankEntry row .1.3.6.1.4.1.12148.10.10.18.2.1
Column Syntax OID
Index used for navigating the rows 1..8 of batteryBankTable
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.10.18.2.1.1
The overall status of battery bank
Enumeration .1.3.6.1.4.1.12148.10.10.18.2.1.2
Number of temperature measurements in battery bank.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.18.2.1.3
Number of current measurements in battery bank.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.18.2.1.4
Number of fuses installed in battery bank.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.18.2.1.5
Number of symmetry measurements available in battery bank.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.18.2.1.6
.1.3.6.1.4.1.12148.10.10.18.3 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankTemperatureTable'
batteryBankTemperatureEntry row .1.3.6.1.4.1.12148.10.10.18.3.1
Column Syntax OID
This index denotes which row in the temperature input table.
The size of the table is defined by the batteryBankNumberOfTemp
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.18.3.1.1
The status of battery temperature monitor
Enumeration .1.3.6.1.4.1.12148.10.10.18.3.1.2
A textual description of the battery temperature monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.18.3.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.18.3.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.10.18.3.1.5
The measured battery temperature.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.3.1.10
.1.3.6.1.4.1.12148.10.10.18.4 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankCurrentTable'
batteryBankCurrentEntry row .1.3.6.1.4.1.12148.10.10.18.4.1
Column Syntax OID
This index denotes which row in the current input table.
The size of the table is defined by the system
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.18.4.1.1
The status of battery current monitor
Enumeration .1.3.6.1.4.1.12148.10.10.18.4.1.2
A textual description of the battery current monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.18.4.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.18.4.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.10.18.4.1.5
The measured battery current
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.4.1.10
.1.3.6.1.4.1.12148.10.10.18.5 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankFuseTable'
batteryBankFuseEntry row .1.3.6.1.4.1.12148.10.10.18.5.1
Column Syntax OID
This index denotes which row in the fuse table.
The size of the table is defined by the system
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.18.5.1.1
The status of battery fuse monitor
Enumeration .1.3.6.1.4.1.12148.10.10.18.5.1.2
A textual description of the battery fuse monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.18.5.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.18.5.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.10.18.5.1.5
The measured value of battery fuse input.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.5.1.6
.1.3.6.1.4.1.12148.10.10.18.6 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryBankSymmetryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryBankSymmetryTable'
batteryBankSymmetryEntry row .1.3.6.1.4.1.12148.10.10.18.6.1
Column Syntax OID
This index denotes which row in the symmetry input table.
The size of the table is defined by the batteryMonitorNumberOfSymmetries
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.10.18.6.1.1
The status of battery symmetry monitor
Enumeration .1.3.6.1.4.1.12148.10.10.18.6.1.2
A textual description of the battery monitor symmetry. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.18.6.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.18.6.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.10.18.6.1.5
The measured battery symmetry voltage in battery monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.6.1.6
The measured battery symmetry delta voltage in battery monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.6.1.7
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.6.1.8
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.18.6.1.9
.1.3.6.1.4.1.12148.10.10.19.2 · 1 row entry · 5 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorsTable'
batteryMonitorsEntry row .1.3.6.1.4.1.12148.10.10.19.2.1
Column Syntax OID
Index used for navigating the rows 1..8 of batteryMonitorsTable
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.10.19.2.1.1
The number of temperature measurements in battery monitor.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.19.2.1.2
The number of current measurements in battery monitor.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.19.2.1.3
The number of fuse measurements in battery monitor.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.19.2.1.4
The number of symmetry measurements in battery monitor.
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.10.19.2.1.5
.1.3.6.1.4.1.12148.10.10.19.3 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorTemperatureTable'
batteryMonitorTemperatureEntry row .1.3.6.1.4.1.12148.10.10.19.3.1
Column Syntax OID
This index denotes which row in the temperature input table.
The size of the table is defined by the batteryMonitorNumberOfTemperatures
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.19.3.1.1
The status of battery temperature monitor
Enumeration .1.3.6.1.4.1.12148.10.10.19.3.1.2
A textual description of the battery monitor temperature. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.19.3.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.19.3.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.10.19.3.1.5
The measured battery temperature in battery monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.3.1.10
.1.3.6.1.4.1.12148.10.10.19.4 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorCurrentTable'
batteryMonitorCurrentEntry row .1.3.6.1.4.1.12148.10.10.19.4.1
Column Syntax OID
This index denotes which row in the current input table.
The size of the table is defined by the batteryMonitorNumberOfCurrents
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.19.4.1.1
The status of battery current monitor
Enumeration .1.3.6.1.4.1.12148.10.10.19.4.1.2
A textual description of the battery monitor current. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.19.4.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.19.4.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.10.19.4.1.5
The measured battery current in battery monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.4.1.10
.1.3.6.1.4.1.12148.10.10.19.5 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorFuseTable'
batteryMonitorFuseEntry row .1.3.6.1.4.1.12148.10.10.19.5.1
Column Syntax OID
This index denotes which row in the fuse table.
The size of the table is defined by the batteryMonitorNumberOfFuses
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.10.19.5.1.1
The status of battery fuse monitor
Enumeration .1.3.6.1.4.1.12148.10.10.19.5.1.2
A textual description of the battery monitor fuse. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.19.5.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.19.5.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.10.19.5.1.5
The measured value of battery fuse in battery monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.5.1.6
.1.3.6.1.4.1.12148.10.10.19.6 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryMonitorSymmetryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryMonitorSymmetryTable'
batteryMonitorSymmetryEntry row .1.3.6.1.4.1.12148.10.10.19.6.1
Column Syntax OID
This index denotes which row in the symmetry input table.
The size of the table is defined by the batteryMonitorNumberOfSymmetries
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.10.19.6.1.1
The status of battery symmetry monitor
Enumeration .1.3.6.1.4.1.12148.10.10.19.6.1.2
A textual description of the battery monitor symmetry. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.19.6.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.10.19.6.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.10.19.6.1.5
The measured battery symmetry voltage in battery monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.6.1.6
The measured battery symmetry delta voltage in battery monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.6.1.7
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.6.1.8
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.19.6.1.9
.1.3.6.1.4.1.12148.10.10.20.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryEnergyLogLastHoursTable'
This table contains hourly energy log of battery.
batteryEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.10.20.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.20.3.1.1
Energy value logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.20.3.1.2
.1.3.6.1.4.1.12148.10.10.20.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryEnergyLogLastDaysTable'
This table contains daily energy log of battery.
batteryEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.10.20.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.20.5.1.1
Energy value logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.20.5.1.2
.1.3.6.1.4.1.12148.10.10.20.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryEnergyLogLastWeeksTable'
This table contains weekly energy log of battery.
batteryEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.10.20.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.20.7.1.1
Energy value logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.20.7.1.2
.1.3.6.1.4.1.12148.10.10.21.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryCycleLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryCycleLogDaysTable'
This table contains daily battery discharge cycle log.
batteryCycleLogDaysEntry row .1.3.6.1.4.1.12148.10.10.21.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryCycleLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.21.3.1.1
Number of discharge cycles logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.21.3.1.2
.1.3.6.1.4.1.12148.10.10.21.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryCycleLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryCycleLogWeeksTable'
This table contains weekly battery discharge cycle log.
batteryCycleLogWeeksEntry row .1.3.6.1.4.1.12148.10.10.21.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.21.5.1.1
Number of discharge cycles logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.21.5.1.2
.1.3.6.1.4.1.12148.10.10.21.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryCycleLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryCycleLogMonthsTable'
This table contains monthly battery discharge cycle log.
batteryCycleLogMonthsEntry row .1.3.6.1.4.1.12148.10.10.21.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryCycleLogLastMonthTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.21.7.1.1
Number of discharge cycles logged every month.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.21.7.1.2
.1.3.6.1.4.1.12148.10.10.25.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryRunTimeLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryRunTimeLogDaysTable'
This table contains daily battery run time log.
batteryRunTimeLogDaysEntry row .1.3.6.1.4.1.12148.10.10.25.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryRunTimeLogDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.25.3.1.1
Battery running minutes logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.25.3.1.2
.1.3.6.1.4.1.12148.10.10.25.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryRunTimeLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryRunTimeLogWeeksTable'
This table contains weekly battery run time log.
batteryRunTimeLogWeeksEntry row .1.3.6.1.4.1.12148.10.10.25.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryRunTimeLogWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.25.5.1.1
Battery running hours logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.25.5.1.2
.1.3.6.1.4.1.12148.10.10.25.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryRunTimeLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryRunTimeLogMonthsTable'
This table contains monthly battery run time log.
batteryRunTimeLogMonthsEntry row .1.3.6.1.4.1.12148.10.10.25.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryRunTimeLogMonthsTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.10.25.7.1.1
Battery running hours logged every month.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.25.7.1.2
.1.3.6.1.4.1.12148.10.10.26.4 · 1 row entry · 20 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryModuleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryModuleTable'
Information of individule battery module
batteryModuleEntry row .1.3.6.1.4.1.12148.10.10.26.4.1
Column Syntax OID
Index used for navigating the rows 1..100 of batteryModuleTable
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.10.26.4.1.1
The status value for the battery module
Enumeration .1.3.6.1.4.1.12148.10.10.26.4.1.2
Battery voltage value
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.3
Battery current value
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.4
Battery remaining capacity value
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.5
Battery temperature value
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.6
Battery quality value
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.7
Maximal charging current in Amp
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.8
Maximal discharge current in Amp
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.9
Battery mode
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.10.26.4.1.10
Charge mode
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.10.26.4.1.11
Battery manufaturer
OctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.10.26.4.1.12
Part number
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.26.4.1.13
Serial number
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.26.4.1.14
Software version
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.10.26.4.1.15
Date of production
OctetString
Constraints:
range: 8-11
.1.3.6.1.4.1.12148.10.10.26.4.1.16
Accumulated Ah charged
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.17
Accumulated Ah discharged
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.18
Number of charge cycles
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.19
Number of discharge cycles
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.10.26.4.1.20
.1.3.6.1.4.1.12148.10.11.1 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk inputControlUnitsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::inputControlUnitsTable'
inputControlUnitsEntry row .1.3.6.1.4.1.12148.10.11.1.1
Column Syntax OID
Index used for navigating the rows of inputControlUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.11.1.1.1
Number of programmable inputs available in controller.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.11.1.1.2
.1.3.6.1.4.1.12148.10.11.2 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk inputControlUnitInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::inputControlUnitInputTable'
This table contains the status of the programmable inputs for Control Units.
inputControlUnitInputEntry row .1.3.6.1.4.1.12148.10.11.2.1
Column Syntax OID
Index used for navigating the rows of inputControlUnitInputTable
The size of the table is defined by the inputControlUnitNumberOfInputs
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.11.2.1.1
Programmable input status.
Enumeration .1.3.6.1.4.1.12148.10.11.2.1.2
A textual description of the programmable input. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.11.2.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.11.2.1.4
This will enable or disable this inputs Alarm functionality.
Setting 'disabled' here will turn off lock the status to 'disabled' state
Enumerationr/w .1.3.6.1.4.1.12148.10.11.2.1.5
The inputs measured Value. Depending on the type of input, this may
represent a Voltage, a Temperature, a Current or a Boolean value.
Note: This value can only be set for virtual input on SP2 master or Smartpack S.
Whe…
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.11.2.1.6
Configuration of the input type. Configurations available for different controllers are as follows:
SP2 Basic(normally open, normally closed);
SP2 BasicInd(normally open,normally closed, temperature, temp 4-20mA, voltag…
Enumerationr/w .1.3.6.1.4.1.12148.10.11.2.1.7
.1.3.6.1.4.1.12148.10.11.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk inputIoUnitsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::inputIoUnitsTable'
inputIoUnitsEntry row .1.3.6.1.4.1.12148.10.11.3.1
Column Syntax OID
Index used for navigating the rows of inputIoUnitsTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.11.3.1.1
Number of programmable inputs available in IO unit.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.11.3.1.2
.1.3.6.1.4.1.12148.10.11.4 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk inputIoUnitProgInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::inputIoUnitProgInputTable'
This table contains the status of the programmable inputs for I/O monitor units.
.
inputIoUnitProgInputEntry row .1.3.6.1.4.1.12148.10.11.4.1
Column Syntax OID
The Index to the Input of the selected I/O monitor unit.
Or the input number if you like.
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.12148.10.11.4.1.1
Programmable input status.
Enumeration .1.3.6.1.4.1.12148.10.11.4.1.2
A textual description of the programmable input in IO unit. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.11.4.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.11.4.1.4
This will enable or disable this inputs Alarm functionality.
Setting 'disabled' here will turn off lock the status to 'disabled' state
Enumerationr/w .1.3.6.1.4.1.12148.10.11.4.1.5
The inputs measured Value. Depending on the type of input, this may
represent a Voltage, a Temperature, a Current or a Boolean value.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.11.4.1.6
Configuration of the input type. Configurations available for IO unit are normally open,
normally closed, diode matrix, voltage and clock. Note: If an input is set to 'clock', it can
not be configurated to 'normally op…
Enumerationr/w .1.3.6.1.4.1.12148.10.11.4.1.7
.1.3.6.1.4.1.12148.10.12.1 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk outputControlUnitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::outputControlUnitTable'
outputControlUnitEntry row .1.3.6.1.4.1.12148.10.12.1.1
Column Syntax OID
Index used for navigating the rows of outputControlUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.12.1.1.1
Number of outputs available in controller.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.12.1.1.2
.1.3.6.1.4.1.12148.10.12.2 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk outputControlUnitOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::outputControlUnitOutputTable'
This table contains the status of the outputs for Control Units.
outputControlUnitOutputEntry row .1.3.6.1.4.1.12148.10.12.2.1
Column Syntax OID
Index used for navigating the rows of outputControlUnitoutputTable
The size of the table is defined by the outputControlUnitNumberOfOutputs
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.12.2.1.1
General output relays may be 'energized' or 'not energized'. 'energized' and
'not energized' correspond
to normal and alarm condition respectively for normally
activated configuration.
Latched contactors may have val…
Enumeration .1.3.6.1.4.1.12148.10.12.2.1.2
A textual description of the output. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.12.2.1.3
.1.3.6.1.4.1.12148.10.12.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk outputIoUnitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::outputIoUnitTable'
outputIoUnitEntry row .1.3.6.1.4.1.12148.10.12.3.1
Column Syntax OID
Index used for navigating the rows of outputIoUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.12.3.1.1
Number of outputs available in IO unit.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.12.3.1.2
.1.3.6.1.4.1.12148.10.12.4 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk outputIoUnitOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::outputIoUnitOutputTable'
This table contains the status of the outputs for IO Units.
outputIoUnitOutputEntry row .1.3.6.1.4.1.12148.10.12.4.1
Column Syntax OID
Index used for navigating the rows of outputIOUnitOutputTable
The size of the table is defined by the outputIOUnitNumberOfOutputs
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.12.4.1.1
General output relays may be 'energized' or 'not energized'.
Latched contactors may have values 'disconnected' or 'connected'
Enumeration .1.3.6.1.4.1.12148.10.12.4.1.2
A textual description of the output in IO unit. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.12.4.1.3
.1.3.6.1.4.1.12148.10.13.4.6 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk snmpTrapsTargetAddressTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::snmpTrapsTargetAddressTable'
This table shows the trap target address. Note that it is NOT allowed 
to change or create SNMP v3 trap target address IPs.
snmpTrapsTargetAddressEntry row .1.3.6.1.4.1.12148.10.13.4.6.1
Column Syntax OID
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.13.4.6.1.1
Note that it is only allowed
to change or create SNMP v2c trap target address IPs.
OctetStringr/w
Constraints:
range: 1-80
.1.3.6.1.4.1.12148.10.13.4.6.1.2
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.4.6.1.3
Enumeration .1.3.6.1.4.1.12148.10.13.4.6.1.4
.1.3.6.1.4.1.12148.10.13.7.2 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlSystemIoUnitsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlSystemIoUnitsTable'
controlSystemIoUnitsEntry row .1.3.6.1.4.1.12148.10.13.7.2.1
Column Syntax OID
Index used for navigating the rows of controlSystemIoUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.7.2.1.1
Number of temperature measurements available in IO unit
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.13.7.2.1.2
Number of fan measurements available in IO unit
Integer32
Constraints:
range: 0-4
.1.3.6.1.4.1.12148.10.13.7.2.1.3
.1.3.6.1.4.1.12148.10.13.7.3 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlSystemIoUnitTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlSystemIoUnitTemperatureTable'
controlSystemIoUnitTemperatureEntry row .1.3.6.1.4.1.12148.10.13.7.3.1
Column Syntax OID
Index used for navigating the rows of controlSystemIoUnitTemperatureTable
The size of the table is defined by the controlSystemIoUnitNumberOfTemperatures
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.12148.10.13.7.3.1.1
The status of temperature monitor
Enumeration .1.3.6.1.4.1.12148.10.13.7.3.1.2
A textual description of the temperature monitor in control system. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.7.3.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.7.3.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.13.7.3.1.5
The measured temperature value.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.3.1.10
.1.3.6.1.4.1.12148.10.13.7.4 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlSystemIoUnitFanTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlSystemIoUnitFanTable'
controlSystemIoUnitFanEntry row .1.3.6.1.4.1.12148.10.13.7.4.1
Column Syntax OID
Index used for navigating the rows 1..2 of ioUnitFan Table
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.12148.10.13.7.4.1.1
The measured fan speed
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.4.1.2
The measured fan speed deviation
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.4.1.3
Fan speed control value in percentage
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.7.4.1.4
.1.3.6.1.4.1.12148.10.13.8.2 · 1 row entry · 8 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlUnitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlUnitTable'
A table containing an inventory listing. Each row represent one of the system hardware 
unit that is connected to the can bus. These units are system controllers, 
battery monitors, I/O units, AC Mains Monitor boxes and load monitors.  Due to the system 
architechture the tables index are not contiguous. Each unit type har its own address 
range on the can bus.  All unit types except the system controller may contain 
from 0 to 14 units.  The system controlller can never be zero.  Then there is no powersystem.
controlUnitEntry row .1.3.6.1.4.1.12148.10.13.8.2.1
One row in the table containing all hardware units connected to the canbus.
Column Syntax OID
Index used for navigating the rows of controlUnitTable
The size of the table is defined by the controlUnitNumberOfUnits
Integer32
Constraints:
range: 1-254
.1.3.6.1.4.1.12148.10.13.8.2.1.1
A textual description of the control unit
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.12148.10.13.8.2.1.2
The overall status of the control unit.
Enumeration .1.3.6.1.4.1.12148.10.13.8.2.1.3
Serial number of the control unit.
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.13.8.2.1.4
Hardware part number of the control unit.
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.13.8.2.1.5
Hardware version of the control unit.
OctetString
Constraints:
range: 0-20
.1.3.6.1.4.1.12148.10.13.8.2.1.6
Software part number of the control unit.
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.13.8.2.1.7
Software version of the control unit.
OctetString
Constraints:
range: 0-20
.1.3.6.1.4.1.12148.10.13.8.2.1.8
.1.3.6.1.4.1.12148.10.13.9.2 · 1 row entry · 5 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorsTable'
currentMonitorsEntry row .1.3.6.1.4.1.12148.10.13.9.2.1
Column Syntax OID
Index used for navigating the rows of currentMonitorsTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.9.2.1.1
This shows if the current monitor is configured as standard load monitor (1), load current
monitor (2), rectifier current monitor (3), dcdc current monitor (4), solar current monitor (5),
wind current monitor (6) or fu…
Enumeration .1.3.6.1.4.1.12148.10.13.9.2.1.2
This is the unit index for each current monitor type.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.2.1.3
Number of fuse measurements in current monitor.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.13.9.2.1.4
Number of current measurements in current monitor.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.13.9.2.1.5
.1.3.6.1.4.1.12148.10.13.9.3 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorFuseTable'
currentMonitorFuseEntry row .1.3.6.1.4.1.12148.10.13.9.3.1
Column Syntax OID
Index used for navigating the rows of currentMonitorFuseTable
The size of the table is defined by the currentMonitorNumberOfFuses
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.13.9.3.1.1
The status of fuse in current monitor
Enumeration .1.3.6.1.4.1.12148.10.13.9.3.1.2
A textual description of the fuse monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.13.9.3.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.9.3.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.13.9.3.1.5
The measured fuse value.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.3.1.6
.1.3.6.1.4.1.12148.10.13.9.4 · 1 row entry · 8 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorCurrentTable'
currentMonitorCurrentEntry row .1.3.6.1.4.1.12148.10.13.9.4.1
Column Syntax OID
Index used for navigating the rows of currentMonitorCurrentTable
The size of the table is defined by the currentMonitorNumberOfCurrents
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.13.9.4.1.1
The status of current in current monitor
Enumeration .1.3.6.1.4.1.12148.10.13.9.4.1.2
A textual description of the current monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.9.4.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.9.4.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.13.9.4.1.5
The measured current value.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.4.1.6
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.4.1.7
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.4.1.8
.1.3.6.1.4.1.12148.10.13.9.5 · 1 row entry · 1 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorEnergyLogAccumulatedTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorEnergyLogAccumulatedTable'
This table contains the accumulated energy consumption measured in current monitor
currentMonitorEnergyLogAccumulatedEntry row .1.3.6.1.4.1.12148.10.13.9.5.1
Column Syntax OID
The accumulated energy consumption value
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.5.1.1
.1.3.6.1.4.1.12148.10.13.9.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorEnergyLogLastHoursTable'
This table contains energy consumption values logged every hour in current monitor.
currentMonitorEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.13.9.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.9.7.1.1
Energy consumption value logged every hour in current monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.7.1.2
.1.3.6.1.4.1.12148.10.13.9.9 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorEnergyLogLastDaysTable'
This table contains energy consumption values logged every day in current monitor.
currentMonitorEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.13.9.9.1
Column Syntax OID
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.9.9.1.1
Energy consumption value logged every day in current monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.9.1.2
.1.3.6.1.4.1.12148.10.13.9.11 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk currentMonitorEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::currentMonitorEnergyLogLastWeeksTable'
This table contains energy consumption values logged every week in current monitor.
currentMonitorEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.13.9.11.1
Column Syntax OID
Index used for navigating the rows 1..52 of currentMonitorEnergyLogLastWeekTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.9.11.1.1
Energy consumption value logged every week in current monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.9.11.1.2
.1.3.6.1.4.1.12148.10.13.10.2 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorsTable'
flexiMonitorsEntry row .1.3.6.1.4.1.12148.10.13.10.2.1
Column Syntax OID
Index used for navigating the rows of flexiMonitorsTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.10.2.1.1
This shows if the fleximonitor is configured as battery monitor (1), load
monitor (2), rectifier monitor (3), controller monitor(4), dcdc monitor (5), solar monitor (6),
wind monitor (7) or fuel cell monitor 8).
Enumeration .1.3.6.1.4.1.12148.10.13.10.2.1.2
This is the unit index for each fleximonitor type.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.2.1.3
Number of inputs in fleximonitor.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.13.10.2.1.4
Number of outputs in fleximonitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.2.1.5
Number of current inputs in fleximonitor.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.12148.10.13.10.2.1.6
.1.3.6.1.4.1.12148.10.13.10.3 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorInputTable'
flexiMonitorInputEntry row .1.3.6.1.4.1.12148.10.13.10.3.1
Column Syntax OID
Index used for navigating the rows of flexiMonitorInputTable
The size of the table is defined by the flexiMonitorNumberOfInputs
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.13.10.3.1.1
Programmable input status.
Enumeration .1.3.6.1.4.1.12148.10.13.10.3.1.2
A textual description of the programmable input. This is stored in the system controller
and can be changed by the user. .
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.10.3.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.10.3.1.4
This will enable or disable this inputs Alarm functionality.
Setting 'disabled' here will turn off lock the status to 'disabled' state
Enumerationr/w .1.3.6.1.4.1.12148.10.13.10.3.1.5
The inputs measured Value. Depending on the type of input, this may
represent a Voltage, a Temperature, a Current, a Speed or a Boolean value.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.3.1.6
Configuration of the input type. Available configurations are: ProgIn-Normally Open(1), ProgIn-Normally Closed(2),
Voltage(3), Temperature(4),Current(5),Speed(6),Fuse-Normally Open(7),Fuse-Normally Closed(8), Fuse-Diode…
Enumerationr/w .1.3.6.1.4.1.12148.10.13.10.3.1.7
.1.3.6.1.4.1.12148.10.13.10.4 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorOutputTable'
flexiMonitorOutputEntry row .1.3.6.1.4.1.12148.10.13.10.4.1
Column Syntax OID
Index used for navigating the rows of flexiMonitorOutputTable
The size of the table is defined by the flexiMonitorNumberOfOutputs
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.13.10.4.1.1
General output relays may be 'energized' or 'not energized'. 'energized' and
'not energized' correspond
to normal and alarm condition respectively for normally
activated configuration.
Latched contactors may have val…
Enumeration .1.3.6.1.4.1.12148.10.13.10.4.1.2
A textual description of the output. This is stored in the system controller
and can be changed by the user.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.13.10.4.1.3
.1.3.6.1.4.1.12148.10.13.10.5 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorCurrentInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorCurrentInputTable'
flexiMonitorCurrentInputEntry row .1.3.6.1.4.1.12148.10.13.10.5.1
Column Syntax OID
Index used for navigating the rows of flexiMonitorInputTable
The size of the table is defined by the flexiMonitorNumberOfInputs
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.12148.10.13.10.5.1.1
A textual description of the programmable input. This is stored in the system controller
and can be changed by the user. .
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.10.5.1.2
Price per kW. To be used together with energy cost logs.
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.13.10.5.1.3
The currency used in energy cost logs.
OctetStringr/w
Constraints:
range: 1-6
.1.3.6.1.4.1.12148.10.13.10.5.1.4
.1.3.6.1.4.1.12148.10.13.10.7 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyCostLogLastMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyCostLogLastMonthsTable'
flexiMonitorEnergyCostLogLastMonthsEntry row .1.3.6.1.4.1.12148.10.13.10.7.1
Column Syntax OID
Index used for navigating the rows 1..12
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.7.1.1
Index by month
Enumeration .1.3.6.1.4.1.12148.10.13.10.7.1.2
Energy in kWh
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.7.1.3
Energy cost
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.13.10.7.1.4
.1.3.6.1.4.1.12148.10.13.10.9 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyCostLogLastYearsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyCostLogLastYearsTable'
flexiMonitorEnergyCostLogLastYearsEntry row .1.3.6.1.4.1.12148.10.13.10.9.1
Column Syntax OID
Index used for navigating the rows 1..12
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.9.1.1
Index by year
OctetString
Constraints:
range: 4-4
.1.3.6.1.4.1.12148.10.13.10.9.1.2
Energy in kWh
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.9.1.3
Energy cost
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.12148.10.13.10.9.1.4
.1.3.6.1.4.1.12148.10.13.10.10 · 1 row entry · 1 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyLogAccumulatedTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyLogAccumulatedTable'
This table contains the accumulated energy consumption measured in fleximonitor
flexiMonitorEnergyLogAccumulatedEntry row .1.3.6.1.4.1.12148.10.13.10.10.1
Column Syntax OID
The accumulated energy consumption value
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.10.1.1
.1.3.6.1.4.1.12148.10.13.10.12 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyLogLastHoursTable'
This table contains energy consumption values logged every hour in fleximonitor.
flexiMonitorEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.13.10.12.1
Column Syntax OID
Index used for navigating the rows 1..52 of flexiMonitorEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.10.12.1.1
Energy consumption value logged every hour in fleximonitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.12.1.2
.1.3.6.1.4.1.12148.10.13.10.14 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyLogLastDaysTable'
This table contains energy consumption values logged every day in fleximonitor.
flexiMonitorEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.13.10.14.1
Column Syntax OID
Index used for navigating the rows 1..52 of flexiMonitorEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.10.14.1.1
Energy consumption value logged every day in fleximonitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.14.1.2
.1.3.6.1.4.1.12148.10.13.10.16 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk flexiMonitorEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::flexiMonitorEnergyLogLastWeeksTable'
This table contains energy consumption values logged every week in fleximonitor.
flexiMonitorEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.13.10.16.1
Column Syntax OID
Index used for navigating the rows 1..52 of flexiMonitorEnergyLogLastWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.10.16.1.1
Energy consumption value logged every week in fleximonitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.10.16.1.2
.1.3.6.1.4.1.12148.10.13.11.1 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainControlUnitsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainControlUnitsTable'
mainControlUnitsEntry row .1.3.6.1.4.1.12148.10.13.11.1.1
Column Syntax OID
Index used for navigating the rows of controlUnitTable
The size of the table is defined by the system
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.11.1.1.1
Total number of temperature measurements in main controller
Integer32
Constraints:
range: 1-14
.1.3.6.1.4.1.12148.10.13.11.1.1.2
.1.3.6.1.4.1.12148.10.13.11.2 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainControlUnitTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainControlUnitTemperatureTable'
mainControlUnitTemperatureEntry row .1.3.6.1.4.1.12148.10.13.11.2.1
Column Syntax OID
This index denotes which row in the temperature input table.
The size of the table is defined by the batteryBankNumberOfTemp
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.13.11.2.1.1
The status of battery temperature monitor
Enumeration .1.3.6.1.4.1.12148.10.13.11.2.1.2
A textual description of the battery temperature monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.11.2.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.11.2.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.13.11.2.1.5
The measured battery temperature.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.2.1.10
.1.3.6.1.4.1.12148.10.13.11.3 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk mainControlUnitEarthFaultTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::mainControlUnitEarthFaultTable'
mainControlUnitEarthFaultEntry row .1.3.6.1.4.1.12148.10.13.11.3.1
Column Syntax OID
This status value shows if the earth resistance is lower than the defined alarm level.
Enumeration .1.3.6.1.4.1.12148.10.13.11.3.1.1
A textual description of the earth fault monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.11.3.1.2
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.3.1.3
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.13.11.3.1.4
The measured value of the earth resistance in kOhm.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.3.1.5
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.11.3.1.6
.1.3.6.1.4.1.12148.10.13.24 · 1 row entry · 4 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk controlSystemGenericModbusDataTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::controlSystemGenericModbusDataTable'
controlSystemGenericModbusDataEntry row .1.3.6.1.4.1.12148.10.13.24.1
Column Syntax OID
Index used for navigating the rows of table
The size of the table is defined by the system
Integer32
Constraints:
range: 1-50
.1.3.6.1.4.1.12148.10.13.24.1.1
description of generic Modbus data
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.12148.10.13.24.1.2
Value of generic Modbus data
OctetString
Constraints:
range: 0-32
.1.3.6.1.4.1.12148.10.13.24.1.3
Unit of generic Modbus data
OctetString
Constraints:
range: 0-12
.1.3.6.1.4.1.12148.10.13.24.1.4
.1.3.6.1.4.1.12148.10.13.26 · 1 row entry · 7 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericAlarmMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericAlarmMonitorTable'
generic alarm monitors to be used with 3rd-party modbus devices
genericAlarmMonitorEntry row .1.3.6.1.4.1.12148.10.13.26.1
Column Syntax OID
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.13.26.1.1
The state of the alarm monitor can be either one of the defined enumerated values
Enumeration .1.3.6.1.4.1.12148.10.13.26.1.2
A textual description of the generic alarm monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.26.1.3
The number of consecutive times this alamcondition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero w…
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.26.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.13.26.1.5
The generic alarm monitor value. Scale is dependent on the scale setting of the corresponding generic modbus value.
Integer32
Constraints:
range: 0-9999
.1.3.6.1.4.1.12148.10.13.26.1.6
A textual description of the unit of generic alarm monitor.
OctetString
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.13.26.1.7
.1.3.6.1.4.1.12148.10.13.27 · 1 row entry · 5 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericLogsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericLogsTable'
Generic logs connected to the last ten generic alarm monitors (#91-#100)
genericLogsEntry row .1.3.6.1.4.1.12148.10.13.27.1
Column Syntax OID
generic log index 1...10
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.13.27.1.1
This is the accumulated trip log value in hours.
SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.13.27.1.2
This is the maximal number of entries stored in daily log
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.27.1.3
This is the maximal number of entries stored in weekly log
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.27.1.4
This is the maximal number of entries stored in monthly log
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.27.1.5
.1.3.6.1.4.1.12148.10.13.28 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericLogDaysTable'
This table contains daily generic log.
genericLogDaysEntry row .1.3.6.1.4.1.12148.10.13.28.1
Column Syntax OID
Index used for navigating the rows 1..52 of genericLogDaysTable
Unsigned32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.28.1.1
generic monitor value in minutes logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.28.1.2
.1.3.6.1.4.1.12148.10.13.29 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericLogWeeksTable'
This table contains weekly generic log.
genericLogWeeksEntry row .1.3.6.1.4.1.12148.10.13.29.1
Column Syntax OID
Index used for navigating the rows 1..52 of genericLogWeeksTable
Unsigned32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.29.1.1
generic monitor value in hours logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.29.1.2
.1.3.6.1.4.1.12148.10.13.30 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk genericLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::genericLogMonthsTable'
This table contains monthly generic log.
genericLogMonthsEntry row .1.3.6.1.4.1.12148.10.13.30.1
Column Syntax OID
Index used for navigating the rows 1..52 of genericLogMonthsTable
Unsigned32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.13.30.1.1
generic monitor value in hours logged every month.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.13.30.1.2
.1.3.6.1.4.1.12148.10.14.1 · 1 row entry · 3 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk alarmGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::alarmGroupTable'
alarmGroupEntry row .1.3.6.1.4.1.12148.10.14.1.1
Indexes
Column Syntax OID
Index used for navigating the rows 1..49 of alarmGroupTable
Integer32
Constraints:
range: 1-49
.1.3.6.1.4.1.12148.10.14.1.1.1
The status of alarm group
Enumeration .1.3.6.1.4.1.12148.10.14.1.1.2
A textual description of the alarm group. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.14.1.1.3
.1.3.6.1.4.1.12148.10.15.16.4 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2TestResultTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2TestResultTable'
This table contains the battery test results stored in controller.
batteryGroup2TestResultEntry row .1.3.6.1.4.1.12148.10.15.16.4.1
Column Syntax OID
A index pointing to one of ten possible battery test results
Integer32
Constraints:
range: 1-10
.1.3.6.1.4.1.12148.10.15.16.4.1.1
This is the time and date when the test started.
SNMPv2-TCDateAndTime
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.12148.10.15.16.4.1.2
This is the test duration in minutes.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.3
This is the discharged Ah during test.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.4
This is the calculated battery quality (SoH)in percentage.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.5
This is the test end voltage in volt.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.6
This is the test result.
Enumeration .1.3.6.1.4.1.12148.10.15.16.4.1.7
This is the test Termination Criteria.
Enumeration .1.3.6.1.4.1.12148.10.15.16.4.1.8
This is the battery temperature
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.16.4.1.9
.1.3.6.1.4.1.12148.10.15.18.6 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2BankTemperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2BankTemperatureTable'
batteryGroup2BankTemperatureEntry row .1.3.6.1.4.1.12148.10.15.18.6.1
Column Syntax OID
This index denotes which row in the temperature input table.
The size of the table is defined by the batteryGroup2BankNumberOfTemperatures
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.15.18.6.1.1
The status of battery temperature monitor
Enumeration .1.3.6.1.4.1.12148.10.15.18.6.1.2
A textual description of the battery temperature monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.15.18.6.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.15.18.6.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.15.18.6.1.5
The measured battery temperature.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.6.1.10
.1.3.6.1.4.1.12148.10.15.18.7 · 1 row entry · 10 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2BankCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2BankCurrentTable'
batteryGroup2BankCurrentEntry row .1.3.6.1.4.1.12148.10.15.18.7.1
Column Syntax OID
This index denotes which row in the current input table.
The size of the table is defined by the system
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.15.18.7.1.1
The status of battery current monitor
Enumeration .1.3.6.1.4.1.12148.10.15.18.7.1.2
A textual description of the battery current monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.15.18.7.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.15.18.7.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.15.18.7.1.5
The measured battery current
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.6
The major high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.7
The minor high alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.8
The minor low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.9
The major low alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.7.1.10
.1.3.6.1.4.1.12148.10.15.18.8 · 1 row entry · 6 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2BankFuseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2BankFuseTable'
batteryGroup2BankFuseEntry row .1.3.6.1.4.1.12148.10.15.18.8.1
Column Syntax OID
This index denotes which row in the fuse table.
The size of the table is defined by the system
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.12148.10.15.18.8.1.1
The status of battery fuse monitor
Enumeration .1.3.6.1.4.1.12148.10.15.18.8.1.2
A textual description of the battery fuse monitor. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.15.18.8.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.15.18.8.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.15.18.8.1.5
The measured value of battery fuse input.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.8.1.6
.1.3.6.1.4.1.12148.10.15.18.9 · 1 row entry · 9 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2BankSymmetryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2BankSymmetryTable'
batteryGroup2BankSymmetryEntry row .1.3.6.1.4.1.12148.10.15.18.9.1
Column Syntax OID
This index denotes which row in the symmetry input table.
The size of the table is defined by the batteryMonitorNumberOfSymmetries
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.12148.10.15.18.9.1.1
The status of battery symmetry monitor
Enumeration .1.3.6.1.4.1.12148.10.15.18.9.1.2
A textual description of the battery monitor symmetry. This is stored in the system controller
and can be changed by the user.
OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.12148.10.15.18.9.1.3
The number of consecutive times this alam condition has been transmitted in a trap.
When trap repetition is enabled, this counter increments every time this trap is repeated.
The counter is automatically set to zero …
SNMPv2-SMICounter32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.12148.10.15.18.9.1.4
This value once enabled, the alarm condition of the monitor will be reported.
Enumerationr/w .1.3.6.1.4.1.12148.10.15.18.9.1.5
The measured battery symmetry voltage in battery monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.9.1.6
The measured battery symmetry delta voltage in battery monitor.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.9.1.7
The major alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.9.1.8
The minor alarm limit
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.18.9.1.9
.1.3.6.1.4.1.12148.10.15.19.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2EnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2EnergyLogLastHoursTable'
This table contains hourly energy log of battery.
batteryGroup2EnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.15.19.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.19.3.1.1
Energy value logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.19.3.1.2
.1.3.6.1.4.1.12148.10.15.19.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2EnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2EnergyLogLastDaysTable'
This table contains daily energy log of battery.
batteryGroup2EnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.15.19.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.19.5.1.1
Energy value logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.19.5.1.2
.1.3.6.1.4.1.12148.10.15.19.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2EnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2EnergyLogLastWeeksTable'
This table contains weekly energy log of battery.
batteryGroup2EnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.15.19.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryEnergyLogLastWeekTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.19.7.1.1
Energy value logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.19.7.1.2
.1.3.6.1.4.1.12148.10.15.20.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2CycleLogDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2CycleLogDaysTable'
This table contains daily battery discharge cycle log.
batteryGroup2CycleLogDaysEntry row .1.3.6.1.4.1.12148.10.15.20.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryCycleLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.20.3.1.1
Number of discharge cycles logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.20.3.1.2
.1.3.6.1.4.1.12148.10.15.20.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2CycleLogWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2CycleLogWeeksTable'
This table contains weekly battery discharge cycle log.
batteryGroup2CycleLogWeeksEntry row .1.3.6.1.4.1.12148.10.15.20.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryCycleLogLastWeeksTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.20.5.1.1
Number of discharge cycles logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.20.5.1.2
.1.3.6.1.4.1.12148.10.15.20.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk batteryGroup2CycleLogMonthsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::batteryGroup2CycleLogMonthsTable'
This table contains monthly battery discharge cycle log.
batteryGroup2CycleLogMonthsEntry row .1.3.6.1.4.1.12148.10.15.20.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of batteryCycleLogLastMonthTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.15.20.7.1.1
Number of discharge cycles logged every month.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.15.20.7.1.2
.1.3.6.1.4.1.12148.10.19.6 · 1 row entry · 26 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk fuelCellTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::fuelCellTable'
This table shows the information of each fuel cell installed in the system.
fuelCellEntry row .1.3.6.1.4.1.12148.10.19.6.1
Indexes
Column Syntax OID
Index used for navigating the rows 1..100 of fuelCellTable
Integer32
Constraints:
range: 1-100
.1.3.6.1.4.1.12148.10.19.6.1.1
The overall status of fuel cell.
Enumeration .1.3.6.1.4.1.12148.10.19.6.1.2
The mode value of fuel cell.
Enumeration .1.3.6.1.4.1.12148.10.19.6.1.3
The output current value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.4
The input voltage value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.5
The input voltage value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.6
Type of fuel cell
OctetString
Constraints:
range: 0-27
.1.3.6.1.4.1.12148.10.19.6.1.7
The inlet temp value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.8
The outlet temp value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.9
The room temp value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.10
The fan value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.11
The H2 storage 1 value of fuel cell.
Enumeration .1.3.6.1.4.1.12148.10.19.6.1.12
The H2 storage 2 value of fuel cell.
Enumeration .1.3.6.1.4.1.12148.10.19.6.1.13
The H2 storage 3 value of fuel cell.
Enumeration .1.3.6.1.4.1.12148.10.19.6.1.14
The DO22 value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.15
The DO23 value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.16
The DO24 value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.17
The DO25 value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.18
The DO26 value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.19
The DO27 value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.20
The DC1 current value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.21
The DC2 current value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.22
The DC3 current value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.23
The DC4 current value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.24
The DC5 current value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.25
The DC6 current value of fuel cell.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.6.1.26
.1.3.6.1.4.1.12148.10.19.7.3 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk fuelCellsEnergyLogLastHoursTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::fuelCellsEnergyLogLastHoursTable'
This table contains hourly energy log of fuel cell.
fuelCellsEnergyLogLastHoursEntry row .1.3.6.1.4.1.12148.10.19.7.3.1
Column Syntax OID
Index used for navigating the rows 1..52 of fuelCellsEnergyLogLastHoursTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.19.7.3.1.1
Energy value logged every hour.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.7.3.1.2
.1.3.6.1.4.1.12148.10.19.7.5 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk fuelCellsEnergyLogLastDaysTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::fuelCellsEnergyLogLastDaysTable'
This table contains daily energy log of fuel cell.
fuelCellsEnergyLogLastDaysEntry row .1.3.6.1.4.1.12148.10.19.7.5.1
Column Syntax OID
Index used for navigating the rows 1..52 of fuelCellsEnergyLogLastDaysTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.19.7.5.1.1
Energy value logged every day.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.7.5.1.2
.1.3.6.1.4.1.12148.10.19.7.7 · 1 row entry · 2 columns
Uses the eltek variant from /opt/observium/mibs/eltek.
Command help
Walk fuelCellsEnergyLogLastWeeksTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SP2-MIB' -M '/opt/observium/mibs/eltek:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SP2-MIB::fuelCellsEnergyLogLastWeeksTable'
This table contains weekly energy log of fuel cell.
fuelCellsEnergyLogLastWeeksEntry row .1.3.6.1.4.1.12148.10.19.7.7.1
Column Syntax OID
Index used for navigating the rows 1..52 of fuelCellsEnergyLogLastWeekTable
Integer32
Constraints:
range: 1-52
.1.3.6.1.4.1.12148.10.19.7.7.1.1
Energy value logged every week.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.12148.10.19.7.7.1.2