SDEVICE-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
5
Rows
5
Columns
33
.1.3.6.1.4.1.31034.2.8 · 1 row entry · 13 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk inputmeasuresTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SDEVICE-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SDEVICE-MIB::inputmeasuresTable'
This table contains all measures related to the measured
inputs of the DEVICE. Note: either 1 or 3 channels, depending
on number of phases measured.
inputmeasuresEntry row .1.3.6.1.4.1.31034.2.8.1
The record containing the registers for the channel selected
by channelIndex.
Indexes
Column Syntax OID
channelIndex6The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.8.1.1
kWhTotalIEither the only phase in a single phase measurement; or one of
the three phases in a multiphase measurement.
KiloWattHour.1.3.6.1.4.1.31034.2.8.1.2
kWhSubtotalIkWh subtotal register of the only phase in a single phase
measurement; or one of three phases in a multiphase
measurement. Reset to zero with [rsimks].
KiloWattHour.1.3.6.1.4.1.31034.2.8.1.3
powerFactorIThe effective power factor in percent.DeciPowerFactor.1.3.6.1.4.1.31034.2.8.1.4
actualCurrentIActual apparent, RMS current.DeciAmps.1.3.6.1.4.1.31034.2.8.1.5
peakCurrentIPeak apparent, RMS current; highest value since last reset of
the alerts.
DeciAmps.1.3.6.1.4.1.31034.2.8.1.6
actualVoltageIThe actual voltage.DeciVolts.1.3.6.1.4.1.31034.2.8.1.7
minVoltageIRMS voltage dip; lowest value since reset of alerts.DeciVolts.1.3.6.1.4.1.31034.2.8.1.8
powerVAIPower value calculated, not in data model of device.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.8.1.9
powerWattIPower value calculated by the gateway, not in data model of
device.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.8.1.10
maxInletAmpsMaximum current per input phase in A; should last at least
[stpkdr] MilliSeconds before triggering an alert.
DeciAmpsr/w.1.3.6.1.4.1.31034.2.8.1.11
inputCTratioThe multiplier to use in case of use of /5 current
transformers. Defaults to 1.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.8.1.12
inputNameUser configurable naming of inputs or phases. Useful if
channels are used to measure branches..
SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31034.2.8.1.13

outletsTable

table
.1.3.6.1.4.1.31034.2.9 · 1 row entry · 2 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk outletsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SDEVICE-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SDEVICE-MIB::outletsTable'
This table contains the customer specific settings,
determining toutlestablehe behaviour of the DEVICE.
outletsEntry row .1.3.6.1.4.1.31034.2.9.1
The record containing the registers forthe channel selected by
channelIndex.
Indexes
Column Syntax OID
channelIndex4The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.9.1.1
outletNameUser configurable naming of individual outlets. Useful to
distinguish outlets based on customer or device name.
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31034.2.9.1.2
.1.3.6.1.4.1.31034.2.10 · 1 row entry · 9 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk outputmeasuresTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SDEVICE-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SDEVICE-MIB::outputmeasuresTable'
This table contains all measures related to the measured
outputs of the DEVICE. Note: up to 48 channels, depending on
number of measured outlets.
outputmeasuresEntry row .1.3.6.1.4.1.31034.2.10.1
The record containing the registers for the channel selected
by channelIndex.
Indexes
Column Syntax OID
channelIndex7The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.10.1.1
kWhTotalOTotal kWh of selected output.KiloWattHour.1.3.6.1.4.1.31034.2.10.1.2
kWhSubtotalOkWh subtotal register of selected output. Reset to zero with
[rsomks].
KiloWattHour.1.3.6.1.4.1.31034.2.10.1.3
powerFactorOPower factor of output.DeciPowerFactor.1.3.6.1.4.1.31034.2.10.1.4
actualCurrentOActual apparent, RMS current.DeciAmps.1.3.6.1.4.1.31034.2.10.1.5
peakCurrentOPeak apparent, RMS current; highest value since last reset of
alerts.
DeciAmps.1.3.6.1.4.1.31034.2.10.1.6
actualVoltageOActual voltage on output.DeciVolts.1.3.6.1.4.1.31034.2.10.1.7
maxOutletAmpsMaximum current per outlet in A; should last at least [stpkdr]
MilliSeconds before triggering an alert.
DeciAmpsr/w.1.3.6.1.4.1.31034.2.10.1.8
outputCTratioThe multiplier to use in case of use of /5 current
transformers. Defaults to 1.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.10.1.9
.1.3.6.1.4.1.31034.2.11 · 1 row entry · 5 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk switchedoutletsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SDEVICE-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SDEVICE-MIB::switchedoutletsTable'
This table contains the current status of switchable
DEVICE's.
switchedoutletsEntry row .1.3.6.1.4.1.31034.2.11.1
The record containing the registers for the channel selected
by channelIndex.
Indexes
Column Syntax OID
channelIndex5The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.11.1.1
currentStateThe actual state of the outlet relays. The hardware will
contain max 48 outlets. Writing is only effective after setting
[swounl].
Integer32r/w
Constraints:
range: 0-1
.1.3.6.1.4.1.31034.2.11.1.2
scheduledA one indicates pending activity; the switch delay has not yet
expired.
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.31034.2.11.1.3
unlockSetting the value to one will release the safety for this
outlet for a couple seconds; switching and rebooting are then
temporarily enabled.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.31034.2.11.1.4
individualOutletDelayDelay before an individual outlet switches on at power-up in
Seconds.
Secondsr/w.1.3.6.1.4.1.31034.2.11.1.5

sensorTable

table
.1.3.6.1.4.1.31034.2.12 · 1 row entry · 4 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk sensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SDEVICE-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SDEVICE-MIB::sensorTable'
This table contains the environmental measurements. As well
internal temperature as external temperature probes.
sensorEntry row .1.3.6.1.4.1.31034.2.12.1
The record containing the registers for the channel selected
by channelIndex.
Indexes
Column Syntax OID
channelIndex8The channel. Its value ranges between 1 and 48, depending on
the number of channels, usually 1.
Integer32
Constraints:
range: 1-48
.1.3.6.1.4.1.31034.2.12.1.1
sensorTypeType of connected sensor, either T, H or I for respectively
Temperature (C), Humidity (%) or dry switch contact
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31034.2.12.1.2
sensorValueValue of connected sensorDeciValue.1.3.6.1.4.1.31034.2.12.1.3
sensorNameUser definable name for sensors.SNMPv2-TCDisplayStringr/w
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.31034.2.12.1.4