psDeviceTable

table mandatory
.1.3.6.1.4.1.5591.1.4.2 · 1 row entry · 35 columns
Uses the scte variant from /opt/observium/mibs/scte.
Command help
Walk psDeviceTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCTE-HMS-PS-MIB' -M '/opt/observium/mibs/scte:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCTE-HMS-PS-MIB::psDeviceTable'
Table containing information about the individual 
power supplies being monitored
psDeviceEntry row .1.3.6.1.4.1.5591.1.4.2.1
List of information about each power supply being monitored.
Indexes
Column Syntax OID
Index into the psDeviceTable.Address of this device on the RS-485 path
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.5591.1.4.2.1.1
Version of the SCTE HMS protocol implemented in the monitored
equipment. The 'Protocol Version' implementation will comply
with the defined protocol in the SCTE 25-3 (formerly HMS 022) document with the
corresponding…
Integer32
Constraints:
range: 1-254
.1.3.6.1.4.1.5591.1.4.2.1.2
The content of this field is vendor specific. The intent is to provide
a text representation of the power supply or generator system software
version. Any printable ASCII characters can be included in this field.
NULL…
OctetString
Constraints:
range: 8-8
.1.3.6.1.4.1.5591.1.4.2.1.3
psDeviceIdmandatory
The content of this field is vendor specific. The intent is to provide
manufacturer and/or product specific ASCII text information that will
propagate to the manager's console verbatim. The following special
characte…
OctetString
Constraints:
range: 32-32
.1.3.6.1.4.1.5591.1.4.2.1.4
psBatteriesmandatory
Current number of batteries per battery string.
Integer32
Constraints:
range: 0-8
.1.3.6.1.4.1.5591.1.4.2.1.5
Current number of battery strings.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.5591.1.4.2.1.6
psTempSensorsmandatory
Number of Battery temperature sensors.
Integer32
Constraints:
range: 0-2
.1.3.6.1.4.1.5591.1.4.2.1.7
psOutputsmandatory
Number of power supply outputs.
Integer32
Constraints:
range: 1-5
.1.3.6.1.4.1.5591.1.4.2.1.8
Bit Map that defines if battery current is measured in this installation.
Bit set means this particular string supports this measurement.
Bits Addresses
0 Not used
1 1 String 1 has battery current suppo…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5591.1.4.2.1.9
Bit Map that defines if float current is measured in this installation.
Bit set means this particular string supports this measurement.
Bits Addresses
0 Not used
1 1 String 1 has float current support
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.5591.1.4.2.1.10
Defines if power supply supports monitoring of output voltage
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5591.1.4.2.1.11
Defines if power supply supports monitoring of input or line voltage
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported - value in psInputVoltagePresence.
3 = Field is su…
Enumeration
Enumerated Values:
1none
2binary
3analog
.1.3.6.1.4.1.5591.1.4.2.1.12
Defines if power supply supports the remote test feature:
1 = Function not supported.
2 - Function is supported.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5591.1.4.2.1.13
Defines if the power supply supports the major alarm indicator:
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
Constraints:
range: 0-255
.1.3.6.1.4.1.5591.1.4.2.1.14
Defines if the power supply supports the minor alarm indicator:
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
Constraints:
range: 0-255
.1.3.6.1.4.1.5591.1.4.2.1.15
Defines if the enclosure door switch is installed in this location:
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
Constraints:
range: 0-255
.1.3.6.1.4.1.5591.1.4.2.1.16
Defines the if batteries or string voltage are available:
1 = No battery voltage monitoring is available.
2 = Only full string battery voltage is available.
3 = Both individual battery and full string voltages are avail…
Enumeration
Enumerated Values:
1noMonitoring
2totalString
3both
Constraints:
range: 0-127
.1.3.6.1.4.1.5591.1.4.2.1.17
Defines if the output power measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5591.1.4.2.1.18
Defines if the output frequency measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5591.1.4.2.1.19
Defines if the input current measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5591.1.4.2.1.20
Defines if the input power measurement is supported
1 = No support. Discard associated value in Get_Power_Supply_Data response.
2 = Field is supported in this installation.
Enumeration
Enumerated Values:
1none
2supported
.1.3.6.1.4.1.5591.1.4.2.1.21
Power supply output voltage in 1/100 Volts units.
This RMS value is common for all outputs in a multiple output system.
This item requires an entry in the properties MIB
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.2.1.22
Scaled representation of input 'line' or 'grid' voltage. This is an
RMS value in 1/100 Volts units. This item requires an entry in the
properties MIB.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.2.1.23
Status of power supply inverter. Enumerated value indicates current
status of inverter.
1 = OFF,
2 = ON: AC Line Fail,
3 = ON: Local Test Cycle,
4 = ON: Remote test initiated
5 = ALARM: Last Test Failed
Enumeration
Enumerated Values:
1off
2lineFail
3testCycle
4testStarted
5testFailed
.1.3.6.1.4.1.5591.1.4.2.1.24
psMajorAlarmoptional
Service has been dropped or a service interruption is imminent.
Indicates that an immediate truck roll is appropriate.
Specific alarms and alarm nomenclature varies between vendors.
Vendors should disclose all conditi…
Enumeration
Enumerated Values:
1noAlarm
2alarm
.1.3.6.1.4.1.5591.1.4.2.1.25
psMinorAlarmoptional
A non-service effecting condition has occurred and should
be monitored. Specific alarms and alarm nomenclature varies
between vendors. Vendors should disclose all conditions that
contribute to this alarm in appropria…
Enumeration
Enumerated Values:
1noAlarm
2alarm
.1.3.6.1.4.1.5591.1.4.2.1.26
psTamperoptional
Indicates status of enclosure door. This notification is
NOT included in the 'Major' or 'Minor' alarm fields.
Individual users / installations must determine if a door
open status represents an alarm and if so, of …
Enumeration
Enumerated Values:
1closed
2open
.1.3.6.1.4.1.5591.1.4.2.1.27
Scaled representation of the full battery string in 1/100 Volts units.

This item requires an entry in the properties MIB.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.2.1.28
Equipment control

1 = Discontinue inverter operation,
2 = Begin inverter operation
Enumerationr/w
Enumerated Values:
1stopTest
2startTest
.1.3.6.1.4.1.5591.1.4.2.1.29
psPowerOutoptional
Representation of power supply output power in 1 W.
This item requires an entry in the properties MIB.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.2.1.30
Scaled representation of the power supply output frequency in 1/100 Hz.
This item requires an entry in the properties MIB.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.2.1.31
Scaled representation of the power supply RMS input current in 1/100 A.
This item requires an entry in the properties MIB.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.2.1.32
psPowerInoptional
Representation of the power supply input power in 1 W.
This item requires an entry in the properties MIB.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.2.1.33
Digital value indicating that line voltage is present and within
tolerance or not.
1 = lost
2 = ok.
This item requires entries in the discrete properties MIB.
Enumeration
Enumerated Values:
1lost
2ok
.1.3.6.1.4.1.5591.1.4.2.1.34
psFrequencyInmandatory
Operational frequency for input voltage
Enumeration
Enumerated Values:
1fiftyHz
2sixtyHz
.1.3.6.1.4.1.5591.1.4.2.1.35

psStringTable

table mandatory
.1.3.6.1.4.1.5591.1.4.3 · 1 row entry · 5 columns
Uses the scte variant from /opt/observium/mibs/scte.
Command help
Walk psStringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCTE-HMS-PS-MIB' -M '/opt/observium/mibs/scte:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCTE-HMS-PS-MIB::psStringTable'
Table containing strings data
psStringEntry row .1.3.6.1.4.1.5591.1.4.3.1
List of information about each string. Indexed by device and string number
Column Syntax OID
Index into the psStringTable. Corresponds to psDeviceAddress in psDeviceTable.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.5591.1.4.3.1.1
psStringmandatory
Index into the psStringTable.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.5591.1.4.3.1.2
Scaled representation of battery string charge current.
This is an RMS value in 1/100 Amps. When batteries being discharged,
this value will = 0.
This item requires an entry in the properties MIB.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.3.1.3
Scaled representation of battery string discharge current. This is
an RMS value in 1/100 Amps.If multiple strings are installed but only
one measurement sensor is used, this value represents the total battery
discharge…
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.3.1.4
Scaled representation of battery 'float' charge current in 1/100 Amps.
This field will be '0' under conditions other than during
actual float charging. When this field is non-zero (reporting
float current), other bat…
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.3.1.5

psBatteryTable

table mandatory
.1.3.6.1.4.1.5591.1.4.4 · 1 row entry · 4 columns
Uses the scte variant from /opt/observium/mibs/scte.
Command help
Walk psBatteryTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCTE-HMS-PS-MIB' -M '/opt/observium/mibs/scte:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCTE-HMS-PS-MIB::psBatteryTable'
Table containing batteries voltages
psBatteryEntry row .1.3.6.1.4.1.5591.1.4.4.1
List of information about each battery.Indexed by device number and string
Column Syntax OID
Index into the psBatteryTable. Corresponds to psDeviceAddress in psDeviceTable.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.5591.1.4.4.1.1
Index into the psBatteryTable. Corresponds to psString in psStringTable.
Integer32
Constraints:
range: 3701-3708
range: 1-2
.1.3.6.1.4.1.5591.1.4.4.1.2
psBatterymandatory
Index into the psBatteryTable.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.5591.1.4.4.1.3
Scaled representation of an individual battery voltage in 1/100 Volts.
String 'A' is used if only one battery string is active.
This item requires an entry in the properties MIB.
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.4.1.4

psOutputTable

table mandatory
.1.3.6.1.4.1.5591.1.4.5 · 1 row entry · 3 columns
Uses the scte variant from /opt/observium/mibs/scte.
Command help
Walk psOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCTE-HMS-PS-MIB' -M '/opt/observium/mibs/scte:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCTE-HMS-PS-MIB::psOutputTable'
Table containing output currents
psOutputEntry row .1.3.6.1.4.1.5591.1.4.5.1
List of information about each Output port. Indexed by device and port number
Column Syntax OID
Index into the psOutputTable.Corresponds to psDeviceAddress in psDeviceTable.
Integer32
Constraints:
range: 1-8
range: 1-8
.1.3.6.1.4.1.5591.1.4.5.1.1
psOutputmandatory
Index into the psOutputTable. Output number
Integer32
Constraints:
range: 1-5
.1.3.6.1.4.1.5591.1.4.5.1.2
Scaled representation of power supply RMS output current in 1/100 Amps.
This value is the total power supply output current if only one output
is active. If multiple outputs are active, this value represents output
#…
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.5591.1.4.5.1.3

psTemperatureSensorTable

table mandatory
.1.3.6.1.4.1.5591.1.4.6 · 1 row entry · 3 columns
Uses the scte variant from /opt/observium/mibs/scte.
Command help
Walk psTemperatureSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCTE-HMS-PS-MIB' -M '/opt/observium/mibs/scte:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCTE-HMS-PS-MIB::psTemperatureSensorTable'
Table containing temperature sensors information
psTemperatureSensorEntry row .1.3.6.1.4.1.5591.1.4.6.1
List of information about each Temperature sensor. Indexed by device and Sensor number
Column Syntax OID
Index into the psTemperatureSensorTable.Corresponds to psDeviceAddress in psDeviceTable.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.5591.1.4.6.1.1
Index into the psTemperatureSensorTable. Temperature sensor number
Integer32
Constraints:
range: 3711-3718
range: 1-2
.1.3.6.1.4.1.5591.1.4.6.1.2
Scaled representation of temperature.
in degrees C with a range of -40 to + 80 degrees C.
This item requires an entry in the properties MIB.
Integer32
Constraints:
range: 1-8
range: -40-80
.1.3.6.1.4.1.5591.1.4.6.1.3