SCHLEIFENBAUER-GENERIC-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
21
Rows
21
Columns
264
.1.3.6.1.4.1.44568.1.1.2.1 · 1 row entry · 19 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceIdentificationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceIdentificationTable'
General identification parameters.
deviceIdentificationEntry row .1.3.6.1.4.1.44568.1.1.2.1.1
General identification parameters.
Column Syntax OID
identificationDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.44568.1.1.2.1.1.1
idDeviceNameUser configurable device name or identifier.OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.2.1.1.2
idDeviceLocationUser configurable device location identifier.OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.2.1.1.3
idModuleTypeDevice category: 0 = Daisychain Module, 1 = Gateway Module, 2 = Controller Module (SF also uses -1 to meaning no module!)Enumeration
Enumerated Values:
0daisychain-module
1gateway-module
2controller-module
.1.3.6.1.4.1.44568.1.1.2.1.1.4
idProductProduct idOctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.44568.1.1.2.1.1.5
idModuleFirmwareFirmware version number.OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.44568.1.1.2.1.1.6
idMacAddressMAC address.OctetString
Constraints:
range: 0-18
.1.3.6.1.4.1.44568.1.1.2.1.1.7
idBirthdayDate Of Manufacture (DOM)OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.44568.1.1.2.1.1.8
idModuleSerialNumberModule serial numberOctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.44568.1.1.2.1.1.9
idModulePartNoModule part number.OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.44568.1.1.2.1.1.10
idSalesOrderNumberSales order numberOctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.44568.1.1.2.1.1.11
idSerialNumberSerial numberSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.2.1.1.12
idExtraTagThe device extra infoOctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.2.1.1.13
idStateThe device state info as stringOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.2.1.1.14
idVendorThe device vendor nameOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.2.1.1.15
idIdThe device unique identifierOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.2.1.1.16
idIpAddrThe device IP AddrSNMPv2-SMIIpAddress
Type Constraints:
range: 4
.1.3.6.1.4.1.44568.1.1.2.1.1.17
idTypeThe device type. e.g. PDU, UPS, etcOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.2.1.1.18
idLastErrorThe last error messageOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.2.1.1.19
.1.3.6.1.4.1.44568.1.1.3.1 · 1 row entry · 13 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceConfigTable'
A list to display device configuration.
deviceConfigEntry row .1.3.6.1.4.1.44568.1.1.3.1.1
A list to display device configuration.
Column Syntax OID
configDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.44568.1.1.3.1.1.1
configMaximumLoadMaximum rated load of the device per phase (this value is also mentioned on the PDU profile), usually either 16A, 32A or 63A.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.3.1.1.2
configCustomerNameCustom 64 character name field for the customer.OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.3.1.1.3
configFormFactorFormfactor of the device.OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.44568.1.1.3.1.1.4
configLengthLength of the device in millimeter.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.3.1.1.5
configNoBranchesThe number of branches available in the PDU, can be zero if no branches are available in the configuration.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.3.1.1.6
configNrOutlMeasuredNumber of measured outlets available in the PDU. If numbering of outlets used is non-contiguous: the highest outlet number is assumed as amount of measured outlets.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.3.1.1.7
configNoNeutralUse neutral current measurements if available: 0 = No neutral current measurement, 1 = Use neutral current measurement.Enumeration
Enumerated Values:
0no-neutral-current-measurement
1use-neutral-current-measurement
.1.3.6.1.4.1.44568.1.1.3.1.1.8
configNrOutletsTotalTotal number of outlets available in the PDU, including hardwired outlets without a switchmeasure module.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.3.1.1.9
configNrPhasesTotal number of inputs: either zero (for no input metering), one or three for a single or three phase system.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.3.1.1.10
configNrOutlSwitchedTotal number of switched outlets available. If the numbering of outlets used is non-contiguous: the highest outlet number is assumed as amount of switched outlets.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.3.1.1.11
configNoTotalsThe number of total calculations available in the PDU, this is usually one but can be more.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.3.1.1.12
configVoltRatingVoltage rating in V for this PDU.OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.44568.1.1.3.1.1.13
.1.3.6.1.4.1.44568.1.1.4.1 · 1 row entry · 9 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceSettingsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceSettingsTable'
device e.g. PDU settings.
deviceSettingsEntry row .1.3.6.1.4.1.44568.1.1.4.1.1
device e.g. PDU configuration.
Column Syntax OID
settingsDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.44568.1.1.4.1.1.1
setCurrentDropDetectionEnable or disable current drop detection (0 = disabled, 1 = enabled)Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.44568.1.1.4.1.1.2
setFixedOutletDelayMinimal delay between relay switch requests in milliseconds. The minimum delay is 100ms.100SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.4.1.1.3
setHighlightLocate a unit. Set to '1' to switch on and to '0' to switch off this function.Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.44568.1.1.4.1.1.4
setLedBrightnessLED brightness setting for the light ring of a PDU0.01%SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.4.1.1.5
setDisableOutletSwitchingSetting this will disable all means of switching an outlet; only the powerup modes and delays will be respected (0 = disabled, 1 = enabled).Enumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.44568.1.1.4.1.1.6
setOutletPowerupModeBehaviour of outlets on power-up. 0 = off, 1 = same state as at power down use default switch delay, 2 = same state, but delayed by individual delay timer, 3 = Outlets will always stay on (even at power down!)Enumerationr/w
Enumerated Values:
0no-switching-on-powerup
1system-wide-outlet-delay
2system-wide-and-individual-outlet-delay
3no-switching-on-power-down
.1.3.6.1.4.1.44568.1.1.4.1.1.7
setSensorChangeAlertModeEnables the sensor channel change detection. 0 = off (default), 1 = onEnumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.44568.1.1.4.1.1.8
setConfigUsbModeUSB Mode. 0 = Disabled, 1 = EnabledEnumerationr/w
Enumerated Values:
0disabled
1enabled
.1.3.6.1.4.1.44568.1.1.4.1.1.9
.1.3.6.1.4.1.44568.1.1.5.1 · 1 row entry · 5 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceDaisychainTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceDaisychainTable'
device e.g. daisychain values.
deviceDaisychainEntry row .1.3.6.1.4.1.44568.1.1.5.1.1
device e.g. PDU configuration.
Column Syntax OID
daisychainDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.44568.1.1.5.1.1.1
dChainBreakLocationDevice index of the ring break location. Can be used to determine between which devices the ring is broken.1SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.5.1.1.2
dChainBusStatusSPBUS network architecture configuration. 0 = open ring network, 1 = closed ring network1Enumeration
Enumerated Values:
0open
1closed
.1.3.6.1.4.1.44568.1.1.5.1.1.3
dChainNrUnitsFoundResult of scan command, denotes the number of devices on the SPBUS network.1SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.5.1.1.4
dChainUnitListList of unit addresses known to the device. Position ordered list of assigned unit addresses.1OctetString
Constraints:
range: 0-255
.1.3.6.1.4.1.44568.1.1.5.1.1.5
.1.3.6.1.4.1.44568.1.1.6.1 · 1 row entry · 2 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceResetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceResetTable'
device e.g. PDU reset values.
deviceResetEntry row .1.3.6.1.4.1.44568.1.1.6.1.1
device e.g. PDU configuration.
Column Syntax OID
resetDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.44568.1.1.6.1.1.1
resetRestartWriting '1' to this register will invoke a warm restart of the device. Note that this will have no effect on outlet status!1Enumerationr/w
Enumerated Values:
1restart
.1.3.6.1.4.1.44568.1.1.6.1.1.2
.1.3.6.1.4.1.44568.1.1.7.1 · 1 row entry · 22 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceInputsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceInputsTable'
A list to display status of Input.
deviceInputsEntry row .1.3.6.1.4.1.44568.1.1.7.1.1
A list to display status of Input.
Column Syntax OID
inputDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.1
inputIndexIndex of inputs.Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.7.1.1.2
inputNameUser configurable 64 character naming of the inputs or phases.OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.7.1.1.3
inputEnergyTotalEither the only phase in a single phase measurement; or one of the three phases in a multiphase measurement. This value is not resetable.KWhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.4
inputEnergySubtotalkWh subtotal register of the only phase in a single phase measurement; or one of three phases in a multiphase measurement.KWhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.5
inputActivePowerInput power (in W) x100, MEASURED by the device using current, voltage, and power factor measurements of a phase.0.01WSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.6
inputApparentPowerInput VA (volt-amps, in VA) 100x, MEASURED by the device using current and voltage measurements of a phase.0.01VASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.7
inputReactivePowerReactive power (volt-amps reactive, in VAR) 100x, MEASURED by the device.0.01VARSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.8
inputPowerFactorThe effective power factor for each input 100x.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.9
inputActualCurrentActual apparent, RMS current of an input 100x.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.10
inputActualVoltageThe actual voltage per input 100x.0.01VSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.11
inputFrequencyFrequency in Hz per input 100x.0.01HzSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.12
inputApparentEnergyThe apparent accumulated energy VAh of each phase 100x.5645VAhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.13
inputCrestFactorThe crest factor per input 100x. the ratio of peak values to the effective value.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.14
inputPeakCurrentInput peak apparent 100x, RMS current; highest value since last reset of the peaks.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.15
inputMaxRatedAmpsMaximum rated current in A per input.1ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.16
inputThdTotal harmonic distortion in percent per phase 100x.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.17
inputTypeType of input.1SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.18
inputMinVoltageRMS voltage dip; lowest value since reset of dips.0.01VSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.19
inputMaxVoltageRMS voltage peak; highest value since reset of peaks.0.01VSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.20
inputPhaseA mapping to which phase each input is connected to.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.21
inputStatusUnbalancedThe input unbalanced. 100x.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.7.1.1.22
.1.3.6.1.4.1.44568.1.1.8.1 · 1 row entry · 23 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceOutletsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceOutletsTable'
A list to display status of Outlet.
deviceOutletsEntry row .1.3.6.1.4.1.44568.1.1.8.1.1
A list to display status of Outlet.
Column Syntax OID
outletDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.1
outletIndexAn outlet index in pdu.Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.8.1.1.2
outletNameUser configurable naming of individual outlets.OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.8.1.1.3
outletEnergyTotalTotal kWh of selected outlet. This value is not resetable.KWhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.4
outletEnergySubtotalkWh subtotal register of selected output.KWhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.5
outletActivePowerOutput power (in W), MEASURED by the device x100 using current, voltage, and power factor measurements of an outlet.0.01WSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.6
outletApparentPowerOutput VA (volt-amps, in VA) 100x, MEASURED by the device using current and voltage measurements of an outlet.0.01VASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.7
outletReactivePowerReactive power (volt-amps reactive, in VAR) 100x, MEASURED by the device.0.01VARSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.8
outletPowerFactorPower factor x100 per outlet.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.9
outletActualCurrentActual apparent 100x, RMS current per outlet.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.10
outletActualVoltageActual voltage on outlet 100x.0.01VSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.11
outletTypeOutlet types: 0: Unknown, 1: BS, 2: C13, 3: C13 IEC Lock, 4: C19, 5: C19 IEC Lock, 6: CEE 16A 1 phase, 7: CEE 16A 3 phase, 8: CEE 32A 1 phase, 9: CEE 32A 3 phase, 10: CEE 63A 1 phase, 11: CEE 63A 3 phase, 12: COMBI IEC …1Enumeration
Enumerated Values:
0unknown
1bs
2c13
3c13-iec-lock
4c19
5c19-iec-lock
6cee-16a-1phase
7cee-16a-3phase
8cee-32a-1phase
9cee-32a-3phase
10cee-64a-1phase
11cee-64a-3phase
12combi-iec-lock
13gst-155
14gst-183
15gst-185
16schuko
17t13
18t23
19ute
.1.3.6.1.4.1.44568.1.1.8.1.1.12
outletPhaseA mapping to which input each outlet is connected to.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.13
outletCurrentStateThe state of the outlet relay(s).Enumerationr/w
Enumerated Values:
0off
1on
.1.3.6.1.4.1.44568.1.1.8.1.1.14
outletApparentEnergyThe apparent accumulated energy VAh of each outlet 100x.5645VAhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.15
outletCrestFactorThe crest factor per outlet 100x. the ratio of peak values to the effective value.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.16
outletPeakCurrentPeak apparent 100x, RMS current of an outlet; highest value since last reset of the peaks.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.17
outletMaxRatedAmpsOutlet maximum rated current in A.1ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.18
outletThdTotal harmonic distortion per outlet 100x.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.19
outletPowerCycleWriting '1' will cause the outlet to power cycle.1SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.20
outletPowerCycleDelayOutlet individual power cycle timer. This is the amount, in seconds.1SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.21
outletSwitchDelayDelay before an individual outlet's relay switches on at power-up, in seconds.1SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.22
outletBranchA mapping to which branch each outlet is connected to.1SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.8.1.1.23
.1.3.6.1.4.1.44568.1.1.9.1 · 1 row entry · 22 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceBranchesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceBranchesTable'
A list to display status of Branch.
deviceBranchesEntry row .1.3.6.1.4.1.44568.1.1.9.1.1
A list to display status of Outlet.
Column Syntax OID
branchDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.1
branchIndexA branch index in pdu.Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.9.1.1.2
branchNameUser configurable naming of a branch in 64 characters per branch.OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.9.1.1.3
branchEnergyTotalBranch energy total measurement in kWh. This value is not resetable. 24-bit little-endian integer.KWhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.4
branchEnergySubtotalBranch energy subtotal measurement in kWh. Reset to zero with [rsbmks]. 24-bit little-endian integer.KWhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.5
branchActivePowerBranch power (in W) x100, MEASURED by the device using current, voltage, and power factor measurements of an branch.0.01WSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.6
branchApparentPowerBranch VA (volt-amps) 100x, MEASURED by the device using current and voltage measurements of an branch.0.01VASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.7
branchReactivePowerReactive power (volt-amps reactive, in VAR) of a branch x100, MEASURED by the device.0.01VARSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.8
branchPowerFactorThe effective power factor per branch 100x.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.9
branchActualCurrentActual apparent 100x, RMS current of a branch.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.10
branchActualVoltageThe actual voltage per branch x100.0.01VSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.11
branchTypeBreaker type: 0: Unknown, 1: ETA (thermal, resettable), 2: HYMA (hydraulic magnetic), 3: MCB (thermal magnetic DIN), 4: MELT (small ceramic fuse), 5: REVOLVER (large ceramic fuse, DIN holder).1Enumeration
Enumerated Values:
0unknown
1eta
2hyma
3mcb
4melt
5revolver
.1.3.6.1.4.1.44568.1.1.9.1.1.12
branchPhaseA mapping to which phase (input) each branch is connected to.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.13
branchStatePower state of the branch, usable for determining if a branch is currently tripped. 0 = OK, 1 = Tripped.Enumeration
Enumerated Values:
0ok
1tripped
.1.3.6.1.4.1.44568.1.1.9.1.1.14
branchApparentEnergyThe apparent accumulated energy VAh of each branch. 100x5645VAhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.15
branchCrestFactorThe crest factor per branch 100x. the ratio of peak values to the effective value.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.16
branchPeakCurrentBranch peak apparent 100x, RMS current; highest value since last reset of the peaks.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.17
branchMaxRatedAmpsMaximum rated current in A per branch (representing the breakerfuse value).1ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.18
branchThdTotal harmonic distortion in percent per branch x100.0.01%SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.19
branchMinVoltageRMS voltage dip per branch; lowest value since reset of dips.0.01VSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.20
branchMaxVoltageRMS voltage peak per branch; highest value since reset of peaks.0.01VSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.21
branchFrequencyFrequency in Hz per branch 100x.0.01HzSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.9.1.1.22
.1.3.6.1.4.1.44568.1.1.10.1 · 1 row entry · 16 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceTotalsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceTotalsTable'
A list to display status of totals.
deviceTotalsEntry row .1.3.6.1.4.1.44568.1.1.10.1.1
A list to display status of totals.
Column Syntax OID
totalDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.1
totalIndexA total index in pdu.Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.10.1.1.2
totalEnergyTotal energy measurement in kWh. This value is not resetable.KWhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.3
totalActivePowerTotals power (in W) 100x, sum of phases.0.01WSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.4
totalApparentPowerTotals VA (volt-amps, in VA) 100x, sum of phases.0.01VASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.5
totalReactivePowerTotals reactive power (volt-amps reactive, in VAR) 100x, sum of phases.0.01VARSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.6
totalActualCurrentSystem total actual apparent 100x, RMS current.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.7
totalApparentEnergyThe total apparent energy in VAh 100x. This value is not resetable.5645VAhSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.8
totalPeakCurrentSystem total peak apparent 100x, RMS current; highest value since last reset of the peaks.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.9
totalNeutralPeakPeak neutral current 100x.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.10
totalNeutralCurrentNeutral current measurement 100x. This is the sum of the neutral measurents channels: (only in three phase configs, one channel for all except 63A, then there will be two).0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.11
totalOvervoltageProtectOvervoltage protection module measurement (0 = OK, 1 = Overvoltage detected).1Enumeration
Enumerated Values:
0ok
1overvoltage
.1.3.6.1.4.1.44568.1.1.10.1.1.12
totalResidualAcCurrentAC residual current measurement 100x.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.13
totalResidualPeakPeak residual current 100x.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.14
totalResidualCurrentResidual current measurement 100x.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.15
totalResidualDcCurrentDC residual current measurement 100x.0.01ASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.10.1.1.16
.1.3.6.1.4.1.44568.1.1.11.1 · 1 row entry · 9 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceSensorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceSensorsTable'
A list to display status of Sensors.
deviceSensorsEntry row .1.3.6.1.4.1.44568.1.1.11.1.1
A list to display status of Sensor.
Column Syntax OID
sensorDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.11.1.1.1
sensorIndexA port index in pdu.Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.11.1.1.2
sensorNameThe sensor port name.OctetStringr/w
Constraints:
range: 0-36
.1.3.6.1.4.1.44568.1.1.11.1.1.3
sensorValueThe sensor value 10x. E.g. a temperature of 25.7 C is passed as 257.0.1SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44568.1.1.11.1.1.4
sensorTypeThe sensor type string.OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.11.1.1.5
sensorSerialNumberSerial number of the sensor.OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.44568.1.1.11.1.1.6
sensorSourceSource of the sensor.Enumeration
Enumerated Values:
0internal
1usb1
2usb2
.1.3.6.1.4.1.44568.1.1.11.1.1.7
sensorStateState of the sensor.Enumeration
Enumerated Values:
0normal
1disconnected
2timeout
3configError
4genericError
.1.3.6.1.4.1.44568.1.1.11.1.1.8
sensorUnitSensor measurement unit.Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.11.1.1.9
.1.3.6.1.4.1.44568.1.1.40.1 · 1 row entry · 7 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceDigitalInputsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceDigitalInputsTable'
A list to display status of Digital Input.
deviceDigitalInputsEntry row .1.3.6.1.4.1.44568.1.1.40.1.1
A list to display status of Digital Input.
Column Syntax OID
digitalInputDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.40.1.1.1
digitalInputIndexA port index in pdu.Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.40.1.1.2
digitalInputNameThe digital input name.OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.40.1.1.3
digitalInputSerialNumberSerial number of the digital input.OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.44568.1.1.40.1.1.6
digitalInputSourceSource of the digital input.Enumeration
Enumerated Values:
0internal
1usb1
2usb2
.1.3.6.1.4.1.44568.1.1.40.1.1.7
digitalInputStateState of the digital input.Enumeration
Enumerated Values:
0normal
1disconnected
2timeout
3configError
4genericError
.1.3.6.1.4.1.44568.1.1.40.1.1.8
digitalInputValueThe digital input stateEnumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.44568.1.1.40.1.1.9
.1.3.6.1.4.1.44568.1.1.50.1 · 1 row entry · 7 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk deviceDigitalOutputsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceDigitalOutputsTable'
A list to display status of Digital Output.
deviceDigitalOutputsEntry row .1.3.6.1.4.1.44568.1.1.50.1.1
A list to display status of Digital Output.
Column Syntax OID
digitalOutputDeviceIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.50.1.1.1
digitalOutputIndexDigital Output index in pdu.Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.50.1.1.2
digitalOutputNameThe digital output port name.OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.50.1.1.3
digitalOutputSerialNumberSerial number of the digital output.OctetString
Constraints:
range: 0-8
.1.3.6.1.4.1.44568.1.1.50.1.1.6
digitalOutputSourceSource of the digital output.Enumeration
Enumerated Values:
0internal
1usb1
2usb2
.1.3.6.1.4.1.44568.1.1.50.1.1.7
digitalOutputStateState of the digital output.Enumeration
Enumerated Values:
0normal
1disconnected
2timeout
3configError
4genericError
.1.3.6.1.4.1.44568.1.1.50.1.1.8
digitalOutputValueThe digital outlet switch state.Enumerationr/w
Enumerated Values:
1off
2on
.1.3.6.1.4.1.44568.1.1.50.1.1.9
.1.3.6.1.4.1.44568.1.1.100.1 · 1 row entry · 16 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk dcStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::dcStatusTable'
A list to display status of Data center.
dcStatusEntry row .1.3.6.1.4.1.44568.1.1.100.1.1
A list to display status of Data Center.
Indexes
Column Syntax OID
dcStatusIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.100.1.1.1
dcStatusNameThe datacenter nameOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.100.1.1.2
dcStatusStateThe datacenter state .e.g normal, etc.OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.100.1.1.3
dcStatusKwhTotalThe data center KWhTotal.KWhInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.4
dcStatusPowerWattsThe datacenter power Watt. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.5
dcStatusPowerVAThe daracenter power VA. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.6
dcStatusCurrentThe data center current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.7
dcStatusVoltageThe data center Voltage. 100x.0.01VInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.8
dcStatusTempThe temperature. 10x.0.1CInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.9
dcStatusHumidityThe humidity. 10x.0.1%Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.10
dcStatusRcmCurrentThe residual current in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.11
dcStatusRcmCurrentAcThe residual current AC component in mAInteger32
Constraints:
range: 0-512
.1.3.6.1.4.1.44568.1.1.100.1.1.12
dcStatusRcmCurrentDcThe residual current DC component in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.13
dcStatusL1The data center L1current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.14
dcStatusL2The data center L2 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.15
dcStatusL3The data center L3 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.100.1.1.16
.1.3.6.1.4.1.44568.1.1.110.1 · 1 row entry · 17 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk roomStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::roomStatusTable'
A list to display status of rooms.
roomStatusEntry row .1.3.6.1.4.1.44568.1.1.110.1.1
A list to display status of a room.
Indexes
Column Syntax OID
roomStatusIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.110.1.1.1
roomStatusNameThe room nameOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.110.1.1.2
roomStatusStateThe room statee.g. normal, degradedOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.110.1.1.3
roomDcStatusNameThe datacenter name in which this room isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.110.1.1.4
roomStatusKwhTotalThe room KWhTotal.KWhInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.5
roomStatusPowerWattsThe room power Watt. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.6
roomStatusPowerVAThe room power VA. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.7
roomStatusCurrentThe room current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.8
roomStatusVoltageThe room Voltage. 100x.0.01VInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.9
roomStatusTempThe temperature. 10x.0.1CInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.10
roomStatusHumidityThe humidity. 10x.0.1%Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.11
roomStatusRcmCurrentThe residual current in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.12
roomStatusRcmCurrentAcThe residual current AC component in mAInteger32
Constraints:
range: 0-512
.1.3.6.1.4.1.44568.1.1.110.1.1.13
roomStatusRcmCurrentDcThe residual current DC component in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.14
roomStatusL1The room L1current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.15
roomStatusL2The room L2 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.16
roomStatusL3The room L3 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.110.1.1.17
.1.3.6.1.4.1.44568.1.1.120.1 · 1 row entry · 18 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk aisleStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::aisleStatusTable'
A list to display status of aisle.
aisleStatusEntry row .1.3.6.1.4.1.44568.1.1.120.1.1
A list to display status of an aisle.
Column Syntax OID
aisleStatusIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.120.1.1.1
aisleStatusNameThe aisle nameOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.120.1.1.2
aisleStatusStateThe aisle statee.g. normal, degradedOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.120.1.1.3
aisleDcStatusNameThe datacenter name in which this room isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.120.1.1.4
aisleRoomStatusNameThe room name in which this aisle isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.120.1.1.5
aisleStatusKwhTotalThe aisle KWhTotal.KWhInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.6
aisleStatusPowerWattsThe aisle power Watt. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.7
aisleStatusPowerVAThe aisle power VA. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.8
aisleStatusCurrentThe aisle current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.9
aisleStatusVoltageThe aisle Voltage. 100x.0.01VInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.10
aisleStatusTempThe aisle temperature. 10x.0.1CInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.11
aisleStatusHumidityThe aisle humidity. 10x.0.1%Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.12
aisleStatusRcmCurrentThe residual current in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.13
aisleStatusRcmCurrentAcThe residual current AC component in mAInteger32
Constraints:
range: 0-512
.1.3.6.1.4.1.44568.1.1.120.1.1.14
aisleStatusRcmCurrentDcThe residual current DC component in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.15
aisleStatusL1The aisle L1current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.16
aisleStatusL2The aisle L2 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.17
aisleStatusL3The aisle L3 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.120.1.1.18
.1.3.6.1.4.1.44568.1.1.130.1 · 1 row entry · 19 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk rackStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::rackStatusTable'
A list to display status of rack.
rackStatusEntry row .1.3.6.1.4.1.44568.1.1.130.1.1
A list to display status of an rack.
Indexes
Column Syntax OID
rackStatusIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.130.1.1.1
rackStatusNameThe rack nameOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.130.1.1.2
rackStatusStateThe rack state.g. normal, degradedOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.130.1.1.3
rackDcStatusNameThe datacenter name in which this room isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.130.1.1.4
rackRoomStatusNameThe room name in which this aisle isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.130.1.1.5
rackAisleStatusNameThe room name in which this aisle isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.130.1.1.6
rackStatusKwhTotalThe rack KWhTotal.KWhInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.7
rackStatusPowerWattsThe rack power Watt. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.8
rackStatusPowerVAThe rack power VA. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.9
rackStatusCurrentThe rack current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.10
rackStatusVoltageThe rack Voltage. 100x.0.01VInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.11
rackStatusTempThe rack temperature. 10x.0.1CInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.12
rackStatusHumidityThe rack humidity. 10x.0.1%Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.13
rackStatusRcmCurrentThe residual current in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.14
rackStatusRcmCurrentAcThe residual current AC component in mAInteger32
Constraints:
range: 0-512
.1.3.6.1.4.1.44568.1.1.130.1.1.15
rackStatusRcmCurrentDcThe residual current DC component in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.16
rackStatusL1The rack L1current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.17
rackStatusL2The rack L2 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.18
rackStatusL3The rack L3 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.130.1.1.19
.1.3.6.1.4.1.44568.1.1.140.1 · 1 row entry · 21 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk rackDeviceStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::rackDeviceStatusTable'
A list to display status of rackDevice.
rackDeviceStatusEntry row .1.3.6.1.4.1.44568.1.1.140.1.1
A list to display status of a rackDevice.
Column Syntax OID
rackDeviceStatusIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.140.1.1.1
rackDeviceStatusNameThe rack device nameOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.140.1.1.2
rackDeviceStatusStateThe rackDevice state.g. normal, degradedOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.140.1.1.3
rackDeviceDcStatusNameThe datacenter name in which this rack Device isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.140.1.1.4
rackDeviceRoomStatusNameThe rackDevice in tha rack inroom name in which this aisle isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.140.1.1.5
rackDeviceAisleStatusNameThe rackDevice in tha rack inroom name in which this aisle isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.140.1.1.6
rackDeviceRackStatusNameThe rackDevice in tha rack inroom name in which this aisle isOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.140.1.1.7
rackDeviceStatusKwhTotalThe aisle KWhTotal.KWhInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.8
rackDeviceStatusPowerWattsThe aisle power Watt. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.9
rackDeviceStatusPowerVAThe aisle power VA. 100x.0.01WInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.10
rackDeviceStatusCurrentThe aisle current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.11
rackDeviceStatusVoltageThe aisle Voltage. 100x.0.01VInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.12
rackDeviceStatusTempThe aisle temperature. 10x.0.1CInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.13
rackDeviceStatusHumidityThe aisle humidity. 10x.0.1%Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.14
rackDeviceStatusSwitchStateThe port switch state.Enumeration
Enumerated Values:
1off
2on
3mixed
.1.3.6.1.4.1.44568.1.1.140.1.1.15
rackDeviceStatusRcmCurrentThe residual current in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.16
rackDeviceStatusRcmCurrentAcThe residual current AC component in mAInteger32
Constraints:
range: 0-512
.1.3.6.1.4.1.44568.1.1.140.1.1.17
rackDeviceStatusRcmCurrentDcThe residual current DC component in mAInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.18
rackDeviceStatusL1The rack device L1 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.19
rackDeviceStatusL2The rack device L2 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.20
rackDeviceStatusL3The rack device L3 current. 100x.0.01AInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.140.1.1.21
.1.3.6.1.4.1.44568.1.1.141.1 · 1 row entry · 2 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk rackDeviceConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::rackDeviceConfigTable'
A list to change status of RackDevice switch.
rackDeviceConfigEntry row .1.3.6.1.4.1.44568.1.1.141.1.1
A list to edit status of Switch.
Column Syntax OID
rackDeviceConfigPduIndexA unique value for each group.Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.141.1.1.1
rackDeviceConfigSwitchStateThe rack Device switch state.Enumerationr/w
Enumerated Values:
1off
2on
.1.3.6.1.4.1.44568.1.1.141.1.1.2
.1.3.6.1.4.1.44568.1.1.600.1 · 1 row entry · 3 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk currentUserStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::currentUserStatusTable'
A list to display of current logged in users.
currentUserStatusEntry row .1.3.6.1.4.1.44568.1.1.600.1.1
A list to display status of Inlet.
Column Syntax OID
currentUserStatusIndexA unique value for each PDU. Its value
ranges between 1 and the value of pduCount.
Integer32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.600.1.1.1
currentUserStatusNameThe logged in user name.OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.600.1.1.2
currentUserStatusRoleThe role of this userOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.600.1.1.3
.1.3.6.1.4.1.44568.1.1.700.1 · 1 row entry · 7 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk warningsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::warningsTable'
A list to display of current warnings.
warningsEntry row .1.3.6.1.4.1.44568.1.1.700.1.1
A list to display warnings.
Indexes
Column Syntax OID
warningsIndexA unique value for each warningInteger32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.700.1.1.1
warningsTopLevelTypeThis is a group or sensorOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.700.1.1.2
warningsTopLevelNameThis is the group or device nameOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.700.1.1.3
warningsPortTypeThis is i, o s for device.OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.700.1.1.4
warningsPortIndexThis is zero based port indexInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.700.1.1.5
warningsPortVariablevoltage, Current, etc.OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.700.1.1.6
warningsValueThe value exceeding warning limit. 100x0.01Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.700.1.1.7
.1.3.6.1.4.1.44568.1.1.800.1 · 1 row entry · 7 columns
Uses the schleifenbauer variant from /opt/observium/mibs/schleifenbauer.
Command help
Walk criticalsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::criticalsTable'
A list to display of current criticals.
criticalsEntry row .1.3.6.1.4.1.44568.1.1.800.1.1
A list to display warnings.
Indexes
Column Syntax OID
criticalsIndexA unique value for each criticalInteger32
Constraints:
range: 1-256
.1.3.6.1.4.1.44568.1.1.800.1.1.1
criticalsTopLevelTypeThis is a group type or sensorOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.800.1.1.2
criticalsTopLevelNameThis is the group or device nameOctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.800.1.1.3
criticalsPortTypeThis is i, o s for device.OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.800.1.1.4
criticalsPortIndexThis is zero based port indexInteger32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.800.1.1.5
criticalsPortVariablevoltage, Current, etc.OctetString
Constraints:
range: 0-63
.1.3.6.1.4.1.44568.1.1.800.1.1.6
criticalsValueThe value exceeding critical limit. 100x0.01Integer32
Constraints:
range: 0-2147483647
.1.3.6.1.4.1.44568.1.1.800.1.1.7