SCHLEIFENBAUER-GENERIC-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
21
Rows
21
Columns
264
.1.3.6.1.4.1.44568.1.1.2.1
·
1 row entry
·
19 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceIdentificationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceIdentificationTable'
General identification parameters.
General identification parameters.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
| identificationDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.44568.1.1.2.1.1.1 | ||||||
| idDeviceNameUser configurable device name or identifier. | OctetStringr/w Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.2.1.1.2 | ||||||
| idDeviceLocationUser configurable device location identifier. | OctetStringr/w Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.2.1.1.3 | ||||||
| idModuleTypeDevice category: 0 = Daisychain Module, 1 = Gateway Module, 2 = Controller Module (SF also uses -1 to meaning no module!) | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.2.1.1.4 | ||||||
| idProductProduct id | OctetString Constraints: range: 0-15 | .1.3.6.1.4.1.44568.1.1.2.1.1.5 | ||||||
| idModuleFirmwareFirmware version number. | OctetString Constraints: range: 0-15 | .1.3.6.1.4.1.44568.1.1.2.1.1.6 | ||||||
| idMacAddressMAC address. | OctetString Constraints: range: 0-18 | .1.3.6.1.4.1.44568.1.1.2.1.1.7 | ||||||
| idBirthdayDate Of Manufacture (DOM) | OctetString Constraints: range: 0-15 | .1.3.6.1.4.1.44568.1.1.2.1.1.8 | ||||||
| idModuleSerialNumberModule serial number | OctetString Constraints: range: 0-15 | .1.3.6.1.4.1.44568.1.1.2.1.1.9 | ||||||
| idModulePartNoModule part number. | OctetString Constraints: range: 0-15 | .1.3.6.1.4.1.44568.1.1.2.1.1.10 | ||||||
| idSalesOrderNumberSales order number | OctetString Constraints: range: 0-15 | .1.3.6.1.4.1.44568.1.1.2.1.1.11 | ||||||
| idSerialNumberSerial number | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.2.1.1.12 | ||||||
| idExtraTagThe device extra info | OctetStringr/w Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.2.1.1.13 | ||||||
| idStateThe device state info as string | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.2.1.1.14 | ||||||
| idVendorThe device vendor name | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.2.1.1.15 | ||||||
| idIdThe device unique identifier | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.2.1.1.16 | ||||||
| idIpAddrThe device IP Addr | SNMPv2-SMIIpAddress Type Constraints: range: 4 | .1.3.6.1.4.1.44568.1.1.2.1.1.17 | ||||||
| idTypeThe device type. e.g. PDU, UPS, etc | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.2.1.1.18 | ||||||
| idLastErrorThe last error message | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.2.1.1.19 |
deviceConfigTable
table.1.3.6.1.4.1.44568.1.1.3.1
·
1 row entry
·
13 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceConfigTable'
A list to display device configuration.
A list to display device configuration.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| configDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.44568.1.1.3.1.1.1 | ||||
| configMaximumLoadMaximum rated load of the device per phase (this value is also mentioned on the PDU profile), usually either 16A, 32A or 63A. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.3.1.1.2 | ||||
| configCustomerNameCustom 64 character name field for the customer. | OctetStringr/w Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.3.1.1.3 | ||||
| configFormFactorFormfactor of the device. | OctetString Constraints: range: 0-15 | .1.3.6.1.4.1.44568.1.1.3.1.1.4 | ||||
| configLengthLength of the device in millimeter. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.3.1.1.5 | ||||
| configNoBranchesThe number of branches available in the PDU, can be zero if no branches are available in the configuration. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.3.1.1.6 | ||||
| configNrOutlMeasuredNumber of measured outlets available in the PDU. If numbering of outlets used is non-contiguous: the highest outlet number is assumed as amount of measured outlets. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.3.1.1.7 | ||||
| configNoNeutralUse neutral current measurements if available: 0 = No neutral current measurement, 1 = Use neutral current measurement. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.3.1.1.8 | ||||
| configNrOutletsTotalTotal number of outlets available in the PDU, including hardwired outlets without a switchmeasure module. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.3.1.1.9 | ||||
| configNrPhasesTotal number of inputs: either zero (for no input metering), one or three for a single or three phase system. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.3.1.1.10 | ||||
| configNrOutlSwitchedTotal number of switched outlets available. If the numbering of outlets used is non-contiguous: the highest outlet number is assumed as amount of switched outlets. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.3.1.1.11 | ||||
| configNoTotalsThe number of total calculations available in the PDU, this is usually one but can be more. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.3.1.1.12 | ||||
| configVoltRatingVoltage rating in V for this PDU. | OctetString Constraints: range: 0-15 | .1.3.6.1.4.1.44568.1.1.3.1.1.13 |
deviceSettingsTable
table.1.3.6.1.4.1.44568.1.1.4.1
·
1 row entry
·
9 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceSettingsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceSettingsTable'
device e.g. PDU settings.
device e.g. PDU configuration.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| settingsDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.44568.1.1.4.1.1.1 | ||||||||
| setCurrentDropDetectionEnable or disable current drop detection (0 = disabled, 1 = enabled) | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.4.1.1.2 | ||||||||
| setFixedOutletDelayMinimal delay between relay switch requests in milliseconds. The minimum delay is 100ms. | 100SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.4.1.1.3 | ||||||||
| setHighlightLocate a unit. Set to '1' to switch on and to '0' to switch off this function. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.4.1.1.4 | ||||||||
| setLedBrightnessLED brightness setting for the light ring of a PDU | 0.01%SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.4.1.1.5 | ||||||||
| setDisableOutletSwitchingSetting this will disable all means of switching an outlet; only the powerup modes and delays will be respected (0 = disabled, 1 = enabled). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.4.1.1.6 | ||||||||
| setOutletPowerupModeBehaviour of outlets on power-up. 0 = off, 1 = same state as at power down use default switch delay, 2 = same state, but delayed by individual delay timer, 3 = Outlets will always stay on (even at power down!) | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.4.1.1.7 | ||||||||
| setSensorChangeAlertModeEnables the sensor channel change detection. 0 = off (default), 1 = on | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.4.1.1.8 | ||||||||
| setConfigUsbModeUSB Mode. 0 = Disabled, 1 = Enabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.4.1.1.9 |
deviceDaisychainTable
table.1.3.6.1.4.1.44568.1.1.5.1
·
1 row entry
·
5 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceDaisychainTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceDaisychainTable'
device e.g. daisychain values.
device e.g. PDU configuration.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| daisychainDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.44568.1.1.5.1.1.1 | ||||
| dChainBreakLocationDevice index of the ring break location. Can be used to determine between which devices the ring is broken. | 1SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.5.1.1.2 | ||||
| dChainBusStatusSPBUS network architecture configuration. 0 = open ring network, 1 = closed ring network | 1Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.5.1.1.3 | ||||
| dChainNrUnitsFoundResult of scan command, denotes the number of devices on the SPBUS network. | 1SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.5.1.1.4 | ||||
| dChainUnitListList of unit addresses known to the device. Position ordered list of assigned unit addresses. | 1OctetString Constraints: range: 0-255 | .1.3.6.1.4.1.44568.1.1.5.1.1.5 |
deviceResetTable
table.1.3.6.1.4.1.44568.1.1.6.1
·
1 row entry
·
2 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceResetTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceResetTable'
device e.g. PDU reset values.
device e.g. PDU configuration.
Indexes
| Column | Syntax | OID | ||
|---|---|---|---|---|
| resetDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.44568.1.1.6.1.1.1 | ||
| resetRestartWriting '1' to this register will invoke a warm restart of the device. Note that this will have no effect on outlet status! | 1Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.6.1.1.2 |
deviceInputsTable
table.1.3.6.1.4.1.44568.1.1.7.1
·
1 row entry
·
22 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceInputsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceInputsTable'
A list to display status of Input.
A list to display status of Input.
Indexes
| Column | Syntax | OID |
|---|---|---|
| inputDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.1 |
| inputIndexIndex of inputs. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.7.1.1.2 |
| inputNameUser configurable 64 character naming of the inputs or phases. | OctetStringr/w Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.7.1.1.3 |
| inputEnergyTotalEither the only phase in a single phase measurement; or one of the three phases in a multiphase measurement. This value is not resetable. | KWhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.4 |
| inputEnergySubtotalkWh subtotal register of the only phase in a single phase measurement; or one of three phases in a multiphase measurement. | KWhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.5 |
| inputActivePowerInput power (in W) x100, MEASURED by the device using current, voltage, and power factor measurements of a phase. | 0.01WSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.6 |
| inputApparentPowerInput VA (volt-amps, in VA) 100x, MEASURED by the device using current and voltage measurements of a phase. | 0.01VASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.7 |
| inputReactivePowerReactive power (volt-amps reactive, in VAR) 100x, MEASURED by the device. | 0.01VARSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.8 |
| inputPowerFactorThe effective power factor for each input 100x. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.9 |
| inputActualCurrentActual apparent, RMS current of an input 100x. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.10 |
| inputActualVoltageThe actual voltage per input 100x. | 0.01VSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.11 |
| inputFrequencyFrequency in Hz per input 100x. | 0.01HzSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.12 |
| inputApparentEnergyThe apparent accumulated energy VAh of each phase 100x. | 5645VAhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.13 |
| inputCrestFactorThe crest factor per input 100x. the ratio of peak values to the effective value. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.14 |
| inputPeakCurrentInput peak apparent 100x, RMS current; highest value since last reset of the peaks. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.15 |
| inputMaxRatedAmpsMaximum rated current in A per input. | 1ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.16 |
| inputThdTotal harmonic distortion in percent per phase 100x. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.17 |
| inputTypeType of input. | 1SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.18 |
| inputMinVoltageRMS voltage dip; lowest value since reset of dips. | 0.01VSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.19 |
| inputMaxVoltageRMS voltage peak; highest value since reset of peaks. | 0.01VSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.20 |
| inputPhaseA mapping to which phase each input is connected to. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.21 |
| inputStatusUnbalancedThe input unbalanced. 100x. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.7.1.1.22 |
deviceOutletsTable
table.1.3.6.1.4.1.44568.1.1.8.1
·
1 row entry
·
23 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceOutletsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceOutletsTable'
A list to display status of Outlet.
A list to display status of Outlet.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| outletDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.1 | ||||||||||||||||||||||||||||||||||||||||
| outletIndexAn outlet index in pdu. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.8.1.1.2 | ||||||||||||||||||||||||||||||||||||||||
| outletNameUser configurable naming of individual outlets. | OctetStringr/w Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.8.1.1.3 | ||||||||||||||||||||||||||||||||||||||||
| outletEnergyTotalTotal kWh of selected outlet. This value is not resetable. | KWhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.4 | ||||||||||||||||||||||||||||||||||||||||
| outletEnergySubtotalkWh subtotal register of selected output. | KWhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.5 | ||||||||||||||||||||||||||||||||||||||||
| outletActivePowerOutput power (in W), MEASURED by the device x100 using current, voltage, and power factor measurements of an outlet. | 0.01WSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.6 | ||||||||||||||||||||||||||||||||||||||||
| outletApparentPowerOutput VA (volt-amps, in VA) 100x, MEASURED by the device using current and voltage measurements of an outlet. | 0.01VASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.7 | ||||||||||||||||||||||||||||||||||||||||
| outletReactivePowerReactive power (volt-amps reactive, in VAR) 100x, MEASURED by the device. | 0.01VARSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.8 | ||||||||||||||||||||||||||||||||||||||||
| outletPowerFactorPower factor x100 per outlet. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.9 | ||||||||||||||||||||||||||||||||||||||||
| outletActualCurrentActual apparent 100x, RMS current per outlet. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.10 | ||||||||||||||||||||||||||||||||||||||||
| outletActualVoltageActual voltage on outlet 100x. | 0.01VSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.11 | ||||||||||||||||||||||||||||||||||||||||
| outletTypeOutlet types: 0: Unknown, 1: BS, 2: C13, 3: C13 IEC Lock, 4: C19, 5: C19 IEC Lock, 6: CEE 16A 1 phase, 7: CEE 16A 3 phase, 8: CEE 32A 1 phase, 9: CEE 32A 3 phase, 10: CEE 63A 1 phase, 11: CEE 63A 3 phase, 12: COMBI IEC … | 1Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.8.1.1.12 | ||||||||||||||||||||||||||||||||||||||||
| outletPhaseA mapping to which input each outlet is connected to. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.13 | ||||||||||||||||||||||||||||||||||||||||
| outletCurrentStateThe state of the outlet relay(s). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.8.1.1.14 | ||||||||||||||||||||||||||||||||||||||||
| outletApparentEnergyThe apparent accumulated energy VAh of each outlet 100x. | 5645VAhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.15 | ||||||||||||||||||||||||||||||||||||||||
| outletCrestFactorThe crest factor per outlet 100x. the ratio of peak values to the effective value. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.16 | ||||||||||||||||||||||||||||||||||||||||
| outletPeakCurrentPeak apparent 100x, RMS current of an outlet; highest value since last reset of the peaks. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.17 | ||||||||||||||||||||||||||||||||||||||||
| outletMaxRatedAmpsOutlet maximum rated current in A. | 1ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.18 | ||||||||||||||||||||||||||||||||||||||||
| outletThdTotal harmonic distortion per outlet 100x. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.19 | ||||||||||||||||||||||||||||||||||||||||
| outletPowerCycleWriting '1' will cause the outlet to power cycle. | 1SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.20 | ||||||||||||||||||||||||||||||||||||||||
| outletPowerCycleDelayOutlet individual power cycle timer. This is the amount, in seconds. | 1SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.21 | ||||||||||||||||||||||||||||||||||||||||
| outletSwitchDelayDelay before an individual outlet's relay switches on at power-up, in seconds. | 1SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.22 | ||||||||||||||||||||||||||||||||||||||||
| outletBranchA mapping to which branch each outlet is connected to. | 1SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.8.1.1.23 |
deviceBranchesTable
table.1.3.6.1.4.1.44568.1.1.9.1
·
1 row entry
·
22 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceBranchesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceBranchesTable'
A list to display status of Branch.
A list to display status of Outlet.
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| branchDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.1 | ||||||||||||
| branchIndexA branch index in pdu. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.9.1.1.2 | ||||||||||||
| branchNameUser configurable naming of a branch in 64 characters per branch. | OctetStringr/w Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.9.1.1.3 | ||||||||||||
| branchEnergyTotalBranch energy total measurement in kWh. This value is not resetable. 24-bit little-endian integer. | KWhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.4 | ||||||||||||
| branchEnergySubtotalBranch energy subtotal measurement in kWh. Reset to zero with [rsbmks]. 24-bit little-endian integer. | KWhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.5 | ||||||||||||
| branchActivePowerBranch power (in W) x100, MEASURED by the device using current, voltage, and power factor measurements of an branch. | 0.01WSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.6 | ||||||||||||
| branchApparentPowerBranch VA (volt-amps) 100x, MEASURED by the device using current and voltage measurements of an branch. | 0.01VASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.7 | ||||||||||||
| branchReactivePowerReactive power (volt-amps reactive, in VAR) of a branch x100, MEASURED by the device. | 0.01VARSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.8 | ||||||||||||
| branchPowerFactorThe effective power factor per branch 100x. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.9 | ||||||||||||
| branchActualCurrentActual apparent 100x, RMS current of a branch. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.10 | ||||||||||||
| branchActualVoltageThe actual voltage per branch x100. | 0.01VSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.11 | ||||||||||||
| branchTypeBreaker type: 0: Unknown, 1: ETA (thermal, resettable), 2: HYMA (hydraulic magnetic), 3: MCB (thermal magnetic DIN), 4: MELT (small ceramic fuse), 5: REVOLVER (large ceramic fuse, DIN holder). | 1Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.9.1.1.12 | ||||||||||||
| branchPhaseA mapping to which phase (input) each branch is connected to. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.13 | ||||||||||||
| branchStatePower state of the branch, usable for determining if a branch is currently tripped. 0 = OK, 1 = Tripped. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.9.1.1.14 | ||||||||||||
| branchApparentEnergyThe apparent accumulated energy VAh of each branch. 100x | 5645VAhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.15 | ||||||||||||
| branchCrestFactorThe crest factor per branch 100x. the ratio of peak values to the effective value. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.16 | ||||||||||||
| branchPeakCurrentBranch peak apparent 100x, RMS current; highest value since last reset of the peaks. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.17 | ||||||||||||
| branchMaxRatedAmpsMaximum rated current in A per branch (representing the breakerfuse value). | 1ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.18 | ||||||||||||
| branchThdTotal harmonic distortion in percent per branch x100. | 0.01%SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.19 | ||||||||||||
| branchMinVoltageRMS voltage dip per branch; lowest value since reset of dips. | 0.01VSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.20 | ||||||||||||
| branchMaxVoltageRMS voltage peak per branch; highest value since reset of peaks. | 0.01VSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.21 | ||||||||||||
| branchFrequencyFrequency in Hz per branch 100x. | 0.01HzSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.9.1.1.22 |
deviceTotalsTable
table.1.3.6.1.4.1.44568.1.1.10.1
·
1 row entry
·
16 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceTotalsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceTotalsTable'
A list to display status of totals.
A list to display status of totals.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| totalDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.1 | ||||
| totalIndexA total index in pdu. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.10.1.1.2 | ||||
| totalEnergyTotal energy measurement in kWh. This value is not resetable. | KWhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.3 | ||||
| totalActivePowerTotals power (in W) 100x, sum of phases. | 0.01WSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.4 | ||||
| totalApparentPowerTotals VA (volt-amps, in VA) 100x, sum of phases. | 0.01VASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.5 | ||||
| totalReactivePowerTotals reactive power (volt-amps reactive, in VAR) 100x, sum of phases. | 0.01VARSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.6 | ||||
| totalActualCurrentSystem total actual apparent 100x, RMS current. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.7 | ||||
| totalApparentEnergyThe total apparent energy in VAh 100x. This value is not resetable. | 5645VAhSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.8 | ||||
| totalPeakCurrentSystem total peak apparent 100x, RMS current; highest value since last reset of the peaks. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.9 | ||||
| totalNeutralPeakPeak neutral current 100x. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.10 | ||||
| totalNeutralCurrentNeutral current measurement 100x. This is the sum of the neutral measurents channels: (only in three phase configs, one channel for all except 63A, then there will be two). | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.11 | ||||
| totalOvervoltageProtectOvervoltage protection module measurement (0 = OK, 1 = Overvoltage detected). | 1Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.10.1.1.12 | ||||
| totalResidualAcCurrentAC residual current measurement 100x. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.13 | ||||
| totalResidualPeakPeak residual current 100x. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.14 | ||||
| totalResidualCurrentResidual current measurement 100x. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.15 | ||||
| totalResidualDcCurrentDC residual current measurement 100x. | 0.01ASNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.10.1.1.16 |
deviceSensorsTable
table.1.3.6.1.4.1.44568.1.1.11.1
·
1 row entry
·
9 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceSensorsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceSensorsTable'
A list to display status of Sensors.
A list to display status of Sensor.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| sensorDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.11.1.1.1 | ||||||||||
| sensorIndexA port index in pdu. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.11.1.1.2 | ||||||||||
| sensorNameThe sensor port name. | OctetStringr/w Constraints: range: 0-36 | .1.3.6.1.4.1.44568.1.1.11.1.1.3 | ||||||||||
| sensorValueThe sensor value 10x. E.g. a temperature of 25.7 C is passed as 257. | 0.1SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44568.1.1.11.1.1.4 | ||||||||||
| sensorTypeThe sensor type string. | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.11.1.1.5 | ||||||||||
| sensorSerialNumberSerial number of the sensor. | OctetString Constraints: range: 0-8 | .1.3.6.1.4.1.44568.1.1.11.1.1.6 | ||||||||||
| sensorSourceSource of the sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.11.1.1.7 | ||||||||||
| sensorStateState of the sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.11.1.1.8 | ||||||||||
| sensorUnitSensor measurement unit. | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.11.1.1.9 |
deviceDigitalInputsTable
table.1.3.6.1.4.1.44568.1.1.40.1
·
1 row entry
·
7 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceDigitalInputsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceDigitalInputsTable'
A list to display status of Digital Input.
A list to display status of Digital Input.
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| digitalInputDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.40.1.1.1 | ||||||||||
| digitalInputIndexA port index in pdu. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.40.1.1.2 | ||||||||||
| digitalInputNameThe digital input name. | OctetStringr/w Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.40.1.1.3 | ||||||||||
| digitalInputSerialNumberSerial number of the digital input. | OctetString Constraints: range: 0-8 | .1.3.6.1.4.1.44568.1.1.40.1.1.6 | ||||||||||
| digitalInputSourceSource of the digital input. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.40.1.1.7 | ||||||||||
| digitalInputStateState of the digital input. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.40.1.1.8 | ||||||||||
| digitalInputValueThe digital input state | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.40.1.1.9 |
.1.3.6.1.4.1.44568.1.1.50.1
·
1 row entry
·
7 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk deviceDigitalOutputsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::deviceDigitalOutputsTable'
A list to display status of Digital Output.
A list to display status of Digital Output.
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| digitalOutputDeviceIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.50.1.1.1 | ||||||||||
| digitalOutputIndexDigital Output index in pdu. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.50.1.1.2 | ||||||||||
| digitalOutputNameThe digital output port name. | OctetStringr/w Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.50.1.1.3 | ||||||||||
| digitalOutputSerialNumberSerial number of the digital output. | OctetString Constraints: range: 0-8 | .1.3.6.1.4.1.44568.1.1.50.1.1.6 | ||||||||||
| digitalOutputSourceSource of the digital output. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.50.1.1.7 | ||||||||||
| digitalOutputStateState of the digital output. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.50.1.1.8 | ||||||||||
| digitalOutputValueThe digital outlet switch state. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.50.1.1.9 |
dcStatusTable
table.1.3.6.1.4.1.44568.1.1.100.1
·
1 row entry
·
16 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk dcStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::dcStatusTable'
A list to display status of Data center.
A list to display status of Data Center.
Indexes
| Column | Syntax | OID |
|---|---|---|
| dcStatusIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.100.1.1.1 |
| dcStatusNameThe datacenter name | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.100.1.1.2 |
| dcStatusStateThe datacenter state .e.g normal, etc. | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.100.1.1.3 |
| dcStatusKwhTotalThe data center KWhTotal. | KWhInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.4 |
| dcStatusPowerWattsThe datacenter power Watt. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.5 |
| dcStatusPowerVAThe daracenter power VA. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.6 |
| dcStatusCurrentThe data center current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.7 |
| dcStatusVoltageThe data center Voltage. 100x. | 0.01VInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.8 |
| dcStatusTempThe temperature. 10x. | 0.1CInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.9 |
| dcStatusHumidityThe humidity. 10x. | 0.1%Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.10 |
| dcStatusRcmCurrentThe residual current in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.11 |
| dcStatusRcmCurrentAcThe residual current AC component in mA | Integer32 Constraints: range: 0-512 | .1.3.6.1.4.1.44568.1.1.100.1.1.12 |
| dcStatusRcmCurrentDcThe residual current DC component in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.13 |
| dcStatusL1The data center L1current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.14 |
| dcStatusL2The data center L2 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.15 |
| dcStatusL3The data center L3 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.100.1.1.16 |
roomStatusTable
table.1.3.6.1.4.1.44568.1.1.110.1
·
1 row entry
·
17 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk roomStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::roomStatusTable'
A list to display status of rooms.
A list to display status of a room.
Indexes
| Column | Syntax | OID |
|---|---|---|
| roomStatusIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.110.1.1.1 |
| roomStatusNameThe room name | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.110.1.1.2 |
| roomStatusStateThe room statee.g. normal, degraded | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.110.1.1.3 |
| roomDcStatusNameThe datacenter name in which this room is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.110.1.1.4 |
| roomStatusKwhTotalThe room KWhTotal. | KWhInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.5 |
| roomStatusPowerWattsThe room power Watt. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.6 |
| roomStatusPowerVAThe room power VA. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.7 |
| roomStatusCurrentThe room current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.8 |
| roomStatusVoltageThe room Voltage. 100x. | 0.01VInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.9 |
| roomStatusTempThe temperature. 10x. | 0.1CInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.10 |
| roomStatusHumidityThe humidity. 10x. | 0.1%Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.11 |
| roomStatusRcmCurrentThe residual current in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.12 |
| roomStatusRcmCurrentAcThe residual current AC component in mA | Integer32 Constraints: range: 0-512 | .1.3.6.1.4.1.44568.1.1.110.1.1.13 |
| roomStatusRcmCurrentDcThe residual current DC component in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.14 |
| roomStatusL1The room L1current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.15 |
| roomStatusL2The room L2 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.16 |
| roomStatusL3The room L3 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.110.1.1.17 |
aisleStatusTable
table.1.3.6.1.4.1.44568.1.1.120.1
·
1 row entry
·
18 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk aisleStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::aisleStatusTable'
A list to display status of aisle.
A list to display status of an aisle.
Indexes
| Column | Syntax | OID |
|---|---|---|
| aisleStatusIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.120.1.1.1 |
| aisleStatusNameThe aisle name | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.120.1.1.2 |
| aisleStatusStateThe aisle statee.g. normal, degraded | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.120.1.1.3 |
| aisleDcStatusNameThe datacenter name in which this room is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.120.1.1.4 |
| aisleRoomStatusNameThe room name in which this aisle is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.120.1.1.5 |
| aisleStatusKwhTotalThe aisle KWhTotal. | KWhInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.6 |
| aisleStatusPowerWattsThe aisle power Watt. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.7 |
| aisleStatusPowerVAThe aisle power VA. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.8 |
| aisleStatusCurrentThe aisle current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.9 |
| aisleStatusVoltageThe aisle Voltage. 100x. | 0.01VInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.10 |
| aisleStatusTempThe aisle temperature. 10x. | 0.1CInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.11 |
| aisleStatusHumidityThe aisle humidity. 10x. | 0.1%Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.12 |
| aisleStatusRcmCurrentThe residual current in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.13 |
| aisleStatusRcmCurrentAcThe residual current AC component in mA | Integer32 Constraints: range: 0-512 | .1.3.6.1.4.1.44568.1.1.120.1.1.14 |
| aisleStatusRcmCurrentDcThe residual current DC component in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.15 |
| aisleStatusL1The aisle L1current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.16 |
| aisleStatusL2The aisle L2 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.17 |
| aisleStatusL3The aisle L3 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.120.1.1.18 |
rackStatusTable
table.1.3.6.1.4.1.44568.1.1.130.1
·
1 row entry
·
19 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk rackStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::rackStatusTable'
A list to display status of rack.
A list to display status of an rack.
Indexes
| Column | Syntax | OID |
|---|---|---|
| rackStatusIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.130.1.1.1 |
| rackStatusNameThe rack name | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.130.1.1.2 |
| rackStatusStateThe rack state.g. normal, degraded | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.130.1.1.3 |
| rackDcStatusNameThe datacenter name in which this room is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.130.1.1.4 |
| rackRoomStatusNameThe room name in which this aisle is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.130.1.1.5 |
| rackAisleStatusNameThe room name in which this aisle is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.130.1.1.6 |
| rackStatusKwhTotalThe rack KWhTotal. | KWhInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.7 |
| rackStatusPowerWattsThe rack power Watt. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.8 |
| rackStatusPowerVAThe rack power VA. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.9 |
| rackStatusCurrentThe rack current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.10 |
| rackStatusVoltageThe rack Voltage. 100x. | 0.01VInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.11 |
| rackStatusTempThe rack temperature. 10x. | 0.1CInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.12 |
| rackStatusHumidityThe rack humidity. 10x. | 0.1%Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.13 |
| rackStatusRcmCurrentThe residual current in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.14 |
| rackStatusRcmCurrentAcThe residual current AC component in mA | Integer32 Constraints: range: 0-512 | .1.3.6.1.4.1.44568.1.1.130.1.1.15 |
| rackStatusRcmCurrentDcThe residual current DC component in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.16 |
| rackStatusL1The rack L1current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.17 |
| rackStatusL2The rack L2 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.18 |
| rackStatusL3The rack L3 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.130.1.1.19 |
rackDeviceStatusTable
table.1.3.6.1.4.1.44568.1.1.140.1
·
1 row entry
·
21 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk rackDeviceStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::rackDeviceStatusTable'
A list to display status of rackDevice.
A list to display status of a rackDevice.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
| rackDeviceStatusIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.140.1.1.1 | ||||||
| rackDeviceStatusNameThe rack device name | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.140.1.1.2 | ||||||
| rackDeviceStatusStateThe rackDevice state.g. normal, degraded | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.140.1.1.3 | ||||||
| rackDeviceDcStatusNameThe datacenter name in which this rack Device is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.140.1.1.4 | ||||||
| rackDeviceRoomStatusNameThe rackDevice in tha rack inroom name in which this aisle is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.140.1.1.5 | ||||||
| rackDeviceAisleStatusNameThe rackDevice in tha rack inroom name in which this aisle is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.140.1.1.6 | ||||||
| rackDeviceRackStatusNameThe rackDevice in tha rack inroom name in which this aisle is | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.140.1.1.7 | ||||||
| rackDeviceStatusKwhTotalThe aisle KWhTotal. | KWhInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.8 | ||||||
| rackDeviceStatusPowerWattsThe aisle power Watt. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.9 | ||||||
| rackDeviceStatusPowerVAThe aisle power VA. 100x. | 0.01WInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.10 | ||||||
| rackDeviceStatusCurrentThe aisle current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.11 | ||||||
| rackDeviceStatusVoltageThe aisle Voltage. 100x. | 0.01VInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.12 | ||||||
| rackDeviceStatusTempThe aisle temperature. 10x. | 0.1CInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.13 | ||||||
| rackDeviceStatusHumidityThe aisle humidity. 10x. | 0.1%Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.14 | ||||||
| rackDeviceStatusSwitchStateThe port switch state. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.140.1.1.15 | ||||||
| rackDeviceStatusRcmCurrentThe residual current in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.16 | ||||||
| rackDeviceStatusRcmCurrentAcThe residual current AC component in mA | Integer32 Constraints: range: 0-512 | .1.3.6.1.4.1.44568.1.1.140.1.1.17 | ||||||
| rackDeviceStatusRcmCurrentDcThe residual current DC component in mA | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.18 | ||||||
| rackDeviceStatusL1The rack device L1 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.19 | ||||||
| rackDeviceStatusL2The rack device L2 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.20 | ||||||
| rackDeviceStatusL3The rack device L3 current. 100x. | 0.01AInteger32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.140.1.1.21 |
rackDeviceConfigTable
table.1.3.6.1.4.1.44568.1.1.141.1
·
1 row entry
·
2 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk rackDeviceConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::rackDeviceConfigTable'
A list to change status of RackDevice switch.
A list to edit status of Switch.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
| rackDeviceConfigPduIndexA unique value for each group. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.141.1.1.1 | ||||
| rackDeviceConfigSwitchStateThe rack Device switch state. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.44568.1.1.141.1.1.2 |
currentUserStatusTable
table.1.3.6.1.4.1.44568.1.1.600.1
·
1 row entry
·
3 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk currentUserStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::currentUserStatusTable'
A list to display of current logged in users.
A list to display status of Inlet.
Indexes
| Column | Syntax | OID |
|---|---|---|
| currentUserStatusIndexA unique value for each PDU. Its value ranges between 1 and the value of pduCount. | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.600.1.1.1 |
| currentUserStatusNameThe logged in user name. | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.600.1.1.2 |
| currentUserStatusRoleThe role of this user | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.600.1.1.3 |
warningsTable
table.1.3.6.1.4.1.44568.1.1.700.1
·
1 row entry
·
7 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk warningsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::warningsTable'
A list to display of current warnings.
A list to display warnings.
Indexes
| Column | Syntax | OID |
|---|---|---|
| warningsIndexA unique value for each warning | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.700.1.1.1 |
| warningsTopLevelTypeThis is a group or sensor | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.700.1.1.2 |
| warningsTopLevelNameThis is the group or device name | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.700.1.1.3 |
| warningsPortTypeThis is i, o s for device. | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.700.1.1.4 |
| warningsPortIndexThis is zero based port index | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.700.1.1.5 |
| warningsPortVariablevoltage, Current, etc. | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.700.1.1.6 |
| warningsValueThe value exceeding warning limit. 100x | 0.01Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.700.1.1.7 |
criticalsTable
table.1.3.6.1.4.1.44568.1.1.800.1
·
1 row entry
·
7 columns
Uses the schleifenbauer variant from
Command help
/opt/observium/mibs/schleifenbauer.
Walk criticalsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'SCHLEIFENBAUER-GENERIC-MIB' -M '/opt/observium/mibs/schleifenbauer:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'SCHLEIFENBAUER-GENERIC-MIB::criticalsTable'
A list to display of current criticals.
A list to display warnings.
Indexes
| Column | Syntax | OID |
|---|---|---|
| criticalsIndexA unique value for each critical | Integer32 Constraints: range: 1-256 | .1.3.6.1.4.1.44568.1.1.800.1.1.1 |
| criticalsTopLevelTypeThis is a group type or sensor | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.800.1.1.2 |
| criticalsTopLevelNameThis is the group or device name | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.800.1.1.3 |
| criticalsPortTypeThis is i, o s for device. | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.800.1.1.4 |
| criticalsPortIndexThis is zero based port index | Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.800.1.1.5 |
| criticalsPortVariablevoltage, Current, etc. | OctetString Constraints: range: 0-63 | .1.3.6.1.4.1.44568.1.1.800.1.1.6 |
| criticalsValueThe value exceeding critical limit. 100x | 0.01Integer32 Constraints: range: 0-2147483647 | .1.3.6.1.4.1.44568.1.1.800.1.1.7 |