ROOMALERT11E-MIB

Imported Objects

OBJECT-TYPERFC-1212
TRAP-TYPERFC-1215
enterprises, IpAddress, Counter, TimeTicksRFC1155-SMI

Objects

avtech .1.3.6.1.4.1.20916
products .1.3.6.1.4.1.20916.1
roomalert11E .1.3.6.1.4.1.20916.1.3
sensors .1.3.6.1.4.1.20916.1.3.1
channel1 .1.3.6.1.4.1.20916.1.3.1.1
sensor1-1 .1.3.6.1.4.1.20916.1.3.1.1.1
switch-label-2 .1.3.6.1.4.1.20916.1.3.1.1.10
switch-label-3 .1.3.6.1.4.1.20916.1.3.1.1.11
switch-label-4 .1.3.6.1.4.1.20916.1.3.1.1.12
switch-label-5 .1.3.6.1.4.1.20916.1.3.1.1.13
switch-label-6 .1.3.6.1.4.1.20916.1.3.1.1.14
switch-label-7 .1.3.6.1.4.1.20916.1.3.1.1.15
switch-label-8 .1.3.6.1.4.1.20916.1.3.1.1.16
sensor1-2 .1.3.6.1.4.1.20916.1.3.1.1.2
sensor1-3 .1.3.6.1.4.1.20916.1.3.1.1.3
sensor1-4 .1.3.6.1.4.1.20916.1.3.1.1.4
sensor1-5 .1.3.6.1.4.1.20916.1.3.1.1.5
sensor1-6 .1.3.6.1.4.1.20916.1.3.1.1.6
sensor1-7 .1.3.6.1.4.1.20916.1.3.1.1.7
sensor1-8 .1.3.6.1.4.1.20916.1.3.1.1.8
switch-label-1 .1.3.6.1.4.1.20916.1.3.1.1.9
channel2 .1.3.6.1.4.1.20916.1.3.1.2
sensor2-1 .1.3.6.1.4.1.20916.1.3.1.2.1
sensor2-2 .1.3.6.1.4.1.20916.1.3.1.2.2
sensor2-3 .1.3.6.1.4.1.20916.1.3.1.2.3
sensor2-4 .1.3.6.1.4.1.20916.1.3.1.2.4
sensor2-5 .1.3.6.1.4.1.20916.1.3.1.2.5
sensor2-6-label .1.3.6.1.4.1.20916.1.3.1.2.6
channel3 .1.3.6.1.4.1.20916.1.3.1.3
sensor3-1 .1.3.6.1.4.1.20916.1.3.1.3.1
sensor3-2 .1.3.6.1.4.1.20916.1.3.1.3.2
sensor3-3 .1.3.6.1.4.1.20916.1.3.1.3.3
sensor3-4 .1.3.6.1.4.1.20916.1.3.1.3.4
sensor3-5 .1.3.6.1.4.1.20916.1.3.1.3.5
sensor3-6-label .1.3.6.1.4.1.20916.1.3.1.3.6
channel4 .1.3.6.1.4.1.20916.1.3.1.4
sensor4-1 .1.3.6.1.4.1.20916.1.3.1.4.1
sensor4-2 .1.3.6.1.4.1.20916.1.3.1.4.2
sensor4-3 .1.3.6.1.4.1.20916.1.3.1.4.3
sensor4-4 .1.3.6.1.4.1.20916.1.3.1.4.4
sensor4-5 .1.3.6.1.4.1.20916.1.3.1.4.5
sensor4-6-label .1.3.6.1.4.1.20916.1.3.1.4.6
traps .1.3.6.1.4.1.20916.1.3.2
alarm1 .1.3.6.1.4.1.20916.1.3.2.1
alarm2 .1.3.6.1.4.1.20916.1.3.2.2
alarm3 .1.3.6.1.4.1.20916.1.3.2.3
alarm4 .1.3.6.1.4.1.20916.1.3.2.4
alarmMessage1 .1.3.6.1.4.1.20916.1.3.2.5
alarmMessage2 .1.3.6.1.4.1.20916.1.3.2.6
alarmMessage3 .1.3.6.1.4.1.20916.1.3.2.7
alarmMessage4 .1.3.6.1.4.1.20916.1.3.2.8
thresholds .1.3.6.1.4.1.20916.1.3.3
channels .1.3.6.1.4.1.20916.1.3.3.1
channels1 .1.3.6.1.4.1.20916.1.3.3.1.1
threshold1-1 .1.3.6.1.4.1.20916.1.3.3.1.1.1
threshold1-2 .1.3.6.1.4.1.20916.1.3.3.1.1.2
threshold1-3 .1.3.6.1.4.1.20916.1.3.3.1.1.3
threshold1-4 .1.3.6.1.4.1.20916.1.3.3.1.1.4
threshold1-5 .1.3.6.1.4.1.20916.1.3.3.1.1.5
threshold1-6 .1.3.6.1.4.1.20916.1.3.3.1.1.6
threshold1-7 .1.3.6.1.4.1.20916.1.3.3.1.1.7
threshold1-8 .1.3.6.1.4.1.20916.1.3.3.1.1.8
channels2 .1.3.6.1.4.1.20916.1.3.3.1.2
threshold2-1 .1.3.6.1.4.1.20916.1.3.3.1.2.1
threshold2-2 .1.3.6.1.4.1.20916.1.3.3.1.2.2
threshold2-3 .1.3.6.1.4.1.20916.1.3.3.1.2.3
threshold2-4 .1.3.6.1.4.1.20916.1.3.3.1.2.4
channels3 .1.3.6.1.4.1.20916.1.3.3.1.3
threshold3-1 .1.3.6.1.4.1.20916.1.3.3.1.3.1
threshold3-2 .1.3.6.1.4.1.20916.1.3.3.1.3.2
threshold3-3 .1.3.6.1.4.1.20916.1.3.3.1.3.3
threshold3-4 .1.3.6.1.4.1.20916.1.3.3.1.3.4
channels4 .1.3.6.1.4.1.20916.1.3.3.1.4
threshold4-1 .1.3.6.1.4.1.20916.1.3.3.1.4.1
threshold4-2 .1.3.6.1.4.1.20916.1.3.3.1.4.2
threshold4-3 .1.3.6.1.4.1.20916.1.3.3.1.4.3
threshold4-4 .1.3.6.1.4.1.20916.1.3.3.1.4.4

Notifications/Traps

NameOIDDescription
tempAlarm1-11e




.1.3.6.1.4.1.20916.1.3.0.1
A tempAlarm1 trap signifies that the current
temperature on external sensor 1 is outside the 
defined high or low threshold.
humidityClear2-11e




.1.3.6.1.4.1.20916.1.3.0.10
A humidityClear2 trap signifies that the current
humidity on external sensor 2 has returned to
a normal condition and is within the defined 
high or low threshold.
humidityAlarm3-11e




.1.3.6.1.4.1.20916.1.3.0.11
A humidityAlarm3 trap signifies that the current
humidity on external sensor 3 is outside the 
defined high or low threshold.
humidityClear3-11e




.1.3.6.1.4.1.20916.1.3.0.12
A humidityClear3 trap signifies that the current
humidity on external sensor 3 has returned to
a normal condition and is within the defined 
high or low threshold.
switchAlarm1-11e




.1.3.6.1.4.1.20916.1.3.0.13
A switchAlarm1 trap signifies that switch sensor 1
is in an alarm state.
switchClear1-11e




.1.3.6.1.4.1.20916.1.3.0.14
A switchClear1 trap signifies that the switch sensor 1
has returned to a normal state.
switchAlarm2-11e




.1.3.6.1.4.1.20916.1.3.0.15
A switchAlarm2 trap signifies that switch sensor 2
is in an alarm state.
switchClear2-11e




.1.3.6.1.4.1.20916.1.3.0.16
A switchClear2 trap signifies that the switch sensor 2
has returned to a normal state.
switchAlarm3-11e




.1.3.6.1.4.1.20916.1.3.0.17
A switchAlarm1 trap signifies that switch sensor 1
is in an alarm state.
switchClear3-11e




.1.3.6.1.4.1.20916.1.3.0.18
A switchClear3 trap signifies that the switch sensor 3
has returned to a normal state.
switchAlarm4-11e




.1.3.6.1.4.1.20916.1.3.0.19
A switchAlarm4 trap signifies that switch sensor 4
is in an alarm state.
room-alert-11E-SNMP-trap




.1.3.6.1.4.1.20916.1.3.0.2
A Room Alert 11E SNMP Trap indicates that an alarm
condition has occurred on the sensor inidcated
by the alarmMessage variable.
switchClear4-11e




.1.3.6.1.4.1.20916.1.3.0.20
A switchClear4 trap signifies that the switch sensor 4
has returned to a normal state.
switchAlarm5-11e




.1.3.6.1.4.1.20916.1.3.0.21
A switchAlarm5 trap signifies that switch sensor 5
is in an alarm state.
switchClear5-11e




.1.3.6.1.4.1.20916.1.3.0.22
A switchClear5 trap signifies that the switch sensor 5
has returned to a normal state.
switchAlarm6-11e




.1.3.6.1.4.1.20916.1.3.0.23
A switchAlarm6 trap signifies that switch sensor 6
is in an alarm state.
switchClear6-11e




.1.3.6.1.4.1.20916.1.3.0.24
A switchClear6 trap signifies that the switch sensor 6
has returned to a normal state.
switchAlarm7-11e




.1.3.6.1.4.1.20916.1.3.0.25
A switchAlarm7 trap signifies that switch sensor 7
is in an alarm state.
switchClear7-11e




.1.3.6.1.4.1.20916.1.3.0.26
A switchClear7 trap signifies that the switch sensor 7
has returned to a normal state.
switchAlarm8-11e




.1.3.6.1.4.1.20916.1.3.0.27
A switchAlarm8 trap signifies that switch sensor 8
is in an alarm state.
switchClear8-11e




.1.3.6.1.4.1.20916.1.3.0.28
A switchClear8 trap signifies that the switch sensor 8
has returned to a normal state.
tempAlarm2-11e




.1.3.6.1.4.1.20916.1.3.0.3
A tempAlarm2 trap signifies that the current
temperature on external sensor 2 is outside the 
defined high or low threshold.
tempClear2-11e




.1.3.6.1.4.1.20916.1.3.0.4
A tempClear2 trap signifies that the current
temperature on external sensor 2 has returned to
a normal condition and is within the defined 
high or low threshold.
tempAlarm3-11e




.1.3.6.1.4.1.20916.1.3.0.5
A tempAlarm3 trap signifies that the current
temperature on external sensor 3 is outside the 
defined high or low threshold.
tempClear3-11e




.1.3.6.1.4.1.20916.1.3.0.6
A tempClear3 trap signifies that the current
temperature on external sensor 3 has returned to
a normal condition and is within the defined 
high or low threshold.
humidityAlarm1-11e




.1.3.6.1.4.1.20916.1.3.0.7
A humidityAlarm1 trap signifies that the current
humidity on external sensor 1 is outside the 
defined high or low threshold.
humidityClear1-11e




.1.3.6.1.4.1.20916.1.3.0.8
A humidityClear1 trap signifies that the current
humidity on external sensor 1 has returned to
a normal condition and is within the defined 
high or low threshold.
humidityAlarm2-11e




.1.3.6.1.4.1.20916.1.3.0.9
A humidityAlarm2 trap signifies that the current
humidity on external sensor 2 is outside the 
defined high or low threshold.