PowerNet-PDU Table View
Table-centric layout grouping table, row, and column objects.
Tables
28
Rows
28
Columns
249
.1.3.6.1.4.1.318.1.1.26.2
·
1 row entry
·
13 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2IdentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2IdentTable'
A table of Rack PDU identification data
Identification data from Rack PDU being queried
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2IdentIndexmandatory The index to the Rack PDU identification tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.2.1.1 |
rPDU2IdentModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.2.1.2 |
rPDU2IdentNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.3 |
rPDU2IdentLocationmandatory A user-defined string identifying the locationof the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.4 |
rPDU2IdentHardwareRevmandatory The Rack PDU hardware version | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.5 |
rPDU2IdentFirmwareRevmandatory The Rack PDU firmware version | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.6 |
rPDU2IdentDateOfManufacturemandatory The date the Rack PDU was manufacturedin mm/dd/yyyy format | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.7 |
rPDU2IdentModelNumbermandatory The Rack PDU model number | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.8 |
rPDU2IdentSerialNumbermandatory The Rack PDU serial number | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.9 |
rPDU2IdentContactmandatory A user-defined string identifying theperson to contact regarding the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.10 |
rPDU2IdentBootMonitorRevmandatory The Rack PDU Boot Monitor version | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.11 |
rPDU2IdentLongDescriptionmandatory The Rack PDU Long Description name | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.12 |
rPDU2IdentNMCSerialNumbermandatory The Rack PDU Network Management Card (NMC) serial number | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.2.1.13 |
.1.3.6.1.4.1.318.1.1.26.4.1
·
1 row entry
·
14 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2DeviceConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2DeviceConfigTable'
A table of Rack PDU configuration data
Configuration data from Rack PDU being queried
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
rPDU2DeviceConfigIndexmandatory The index to the Rack PDU table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.1 | ||||||
rPDU2DeviceConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.2 | ||||||
rPDU2DeviceConfigNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.4.1.1.3 | ||||||
rPDU2DeviceConfigLocationmandatory A user-defined string identifying the locationof the Rack PDU | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.4.1.1.4 | ||||||
rPDU2DeviceConfigDisplayOrientationmandatory Indicates the intended physical orientationof the display. displayNormal(1) indicates normal orientation displayReverse(2) indicates upside down orientation | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.5 | ||||||
rPDU2DeviceConfigColdstartDelaymandatory The amount of delay, measured in seconds, betweenwhen power is provided to the Rack PDU and when the Rack PDU provides basic master power to the outlets. Allowed values are: -1 - never apply power automatically. … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.6 | ||||||
| User-defined low power draw alarm threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.7 | ||||||
| User-defined near power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.8 | ||||||
| User-defined power overload threshold, measured in tenths of kilowatts. Models that do not support this feature will respond to this OID with a value of -1. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.1.1.9 | ||||||
| Setting this OID to reset (2) will cause the existing peak power value to be replaced by the current load power value. Getting this OID will do nothing and return the noOperation(1) value. Models that do … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.10 | ||||||
rPDU2DeviceConfigDeviceEnergyResetmandatory Setting this OID to reset (2) will cause the device energy meter valueto be reset to zero. Getting this OID in models that support this feature will do nothing and return the noOperation(1) value. … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.11 | ||||||
rPDU2DeviceConfigOutletsEnergyResetmandatory Setting this OID to reset (2) will cause the all outlet energy meter valuesto be reset to zero. Getting this OID will do nothing and return the noOperation(1) value. Models that do not sup… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.12 | ||||||
| Setting this OID to reset (2) will cause the all outlet peak load values to be reset to zero. Getting this OID will do nothing and return the noOperation(1) value. Models that do not suppor… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.1.1.13 | ||||||
rPDU2DeviceConfigContactmandatory A user-defined string identifying theperson to contact regarding the Rack PDU | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.4.1.1.14 |
.1.3.6.1.4.1.318.1.1.26.4.2
·
1 row entry
·
13 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2DevicePropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2DevicePropertiesTable'
A table of Rack PDU properties
Properties of the Rack PDU being queried
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2DevicePropertiesIndexmandatory The index to the Rack PDU properties table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.1 | ||||||||||||||||||||
rPDU2DevicePropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.2 | ||||||||||||||||||||
rPDU2DevicePropertiesNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.2.1.3 | ||||||||||||||||||||
rPDU2DevicePropertiesNumOutletsmandatory The number of outlets on the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.4 | ||||||||||||||||||||
| The number of switched outlets on the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.5 | ||||||||||||||||||||
| The number of metered outlets on the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.6 | ||||||||||||||||||||
rPDU2DevicePropertiesNumPhasesmandatory The number of phases present in the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.7 | ||||||||||||||||||||
rPDU2DevicePropertiesNumMeteredBanksmandatory The number of metered banks present in the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.8 | ||||||||||||||||||||
| The maximum current rating, measured in Amps, for the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.9 | ||||||||||||||||||||
rPDU2DevicePropertiesOrientationmandatory Rack PDU orientation | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.2.1.10 | ||||||||||||||||||||
rPDU2DevicePropertiesOutletLayoutmandatory Getting this OID will return outlet layout for the device.seqPhaseToNeutral(1) indicates outlet layout as follows: 1:1-N,2:2-N,3:3-N,4:1-N,5:2-N,... or for single phase SKUs, all outlets 1-N … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.2.1.11 | ||||||||||||||||||||
| The maximum current rating, measured in Amps, for the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.12 | ||||||||||||||||||||
| The maximum power rating, measured in tenths of kilowatts, for the Rack PDU | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.2.1.13 |
.1.3.6.1.4.1.318.1.1.26.4.3
·
1 row entry
·
20 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2DeviceStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2DeviceStatusTable'
A table of Rack PDU status information
Status information from the Rack PDU being queried
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2DeviceStatusIndexmandatory The index to the Rack PDU status table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.1 | ||||||||||
rPDU2DeviceStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.2 | ||||||||||
rPDU2DeviceStatusNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.3 | ||||||||||
rPDU2DeviceStatusLoadStatemandatory Indicates the present load status of the Rack PDU.Models that do not support this feature will respond to this OID with a value of notsupported (5). | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.4 | ||||||||||
rPDU2DeviceStatusPowermandatory The power consumption of the Rack PDU load in hundredths of kilowatts.Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.5 | ||||||||||
rPDU2DeviceStatusPeakPowermandatory The peak power consumption of the Rack PDU load in hundredths of kilowatts.Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.6 | ||||||||||
rPDU2DeviceStatusPeakPowerTimestampmandatory Indicates the date and time that peak power consumption occurred.Models that do not support this feature will respond to this OID with string 'notsupported'. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.7 | ||||||||||
rPDU2DeviceStatusPeakPowerStartTimemandatory Indicates the date and time of the last device peak power reset.Models that do not support this feature will respond to this OID with string 'notsupported'. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.8 | ||||||||||
rPDU2DeviceStatusEnergymandatory A user resettable energy meter measuring Rack PDU loadenergy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.9 | ||||||||||
rPDU2DeviceStatusEnergyStartTimemandatory Indicates the date and time of the last device energymeter reset. Models that do not support this feature will respond to this OID with string 'notsupported'. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.10 | ||||||||||
rPDU2DeviceStatusCommandPendingmandatory Indicates whether or not the deviceis processing a pending command. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU should be shut down. The Rack PDU's power should then be cyc… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.11 | ||||||||||
rPDU2DeviceStatusPowerSupplyAlarmmandatory Indicates a power supply alarm is active when valueequals alarm (2) | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.12 | ||||||||||
rPDU2DeviceStatusPowerSupply1Statusmandatory Indicates whether or not an alarm is active in PowerSupply 1 | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.13 | ||||||||||
rPDU2DeviceStatusPowerSupply2Statusmandatory Indicates whether or not an alarm is active in PowerSupply 2 | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.14 | ||||||||||
| Indicates the date and time of the last outlets energy meter reset. Models that do not support this feature will respond to this OID with string 'notsupported'. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.3.1.15 | ||||||||||
rPDU2DeviceStatusApparentPowermandatory The apparent power consumption of the Rack PDU load in hundredths of kiloVoltAmps (kVA).Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.16 | ||||||||||
rPDU2DeviceStatusPowerFactormandatory The power factor of the Rack PDU load in hundredths. Models that do not support this featurewill respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.17 | ||||||||||
rPDU2DeviceStatusNPSTypemandatory The device NPS status:notNPS (1) indicates the Rack PDU is not in an NPS group. host (2) indicates the Rack PDU has been designated as a host in an NPS group. Only one Rack PDU in an NPS group is allowed to be the ho… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.3.1.18 | ||||||||||
rPDU2DeviceStatusResidualPowermandatory The measured device residual power from the PDU meters in hundredths of kiloVoltAmps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.19 | ||||||||||
rPDU2DeviceStatusFrequencymandatory The measured device frequency from the PDU meters in tenths of Hz. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.3.1.20 |
.1.3.6.1.4.1.318.1.1.26.4.4
·
1 row entry
·
4 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2DeviceControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2DeviceControlTable'
A table of Rack PDU control data
Control data from Rack PDU being queried
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2DeviceControlIndexmandatory The index to the Rack PDU control table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.4.1.1 | ||||||||||||||||
rPDU2DeviceControlModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.4.4.1.2 | ||||||||||||||||
rPDU2DeviceControlNamemandatory A user-defined string identifying the Rack PDU | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.4.4.1.3 | ||||||||||||||||
rPDU2DeviceControlCommandmandatory Setting this OID to immediateAllOn (1) will turn all outletson immediately. Setting this OID to delayedAllOn (2) will turn all outlets on as defined by each outlet's rPDU2OutletSwitchedConfigPowerOnTime … | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.4.4.1.4 |
.1.3.6.1.4.1.318.1.1.26.6.1
·
1 row entry
·
8 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2PhaseConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2PhaseConfigTable'
A table of Rack PDU phase configuration data
Configuration data from currently queried Rack
PDU phase
PDU phase
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2PhaseConfigIndexmandatory The index to the Rack PDU phase configurationtable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.1 | ||||||||
rPDU2PhaseConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.2 | ||||||||
rPDU2PhaseConfigNumbermandatory The numeric phase ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.3 | ||||||||
rPDU2PhaseConfigOverloadRestrictionmandatory This OID controls the behavior of a Switched Rack PDUphase when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will alwa… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.6.1.1.4 | ||||||||
| User-defined low load phase current threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.5 | ||||||||
| User-defined near phase overload warning threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.6 | ||||||||
| User-defined phase overload current threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.1.1.7 | ||||||||
| Setting this OID to reset (2) will cause the existing peak current value to be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.6.1.1.8 |
.1.3.6.1.4.1.318.1.1.26.6.2
·
1 row entry
·
3 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2PhasePropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2PhasePropertiesTable'
A table of Rack PDU phase properties
Properties of the currently queried Rack
PDU phase
PDU phase
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2PhasePropertiesIndexmandatory The index to the Rack PDU phase propertiestable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.2.1.1 |
rPDU2PhasePropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.2.1.2 |
rPDU2PhasePropertiesNumbermandatory The numeric phase ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.2.1.3 |
.1.3.6.1.4.1.318.1.1.26.6.3
·
1 row entry
·
13 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2PhaseStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2PhaseStatusTable'
A table of Rack PDU phase status data
Status data from currently queried Rack PDU
phase
phase
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2PhaseStatusIndexmandatory The index to the Rack PDU phase status tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.1 | ||||||||
rPDU2PhaseStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.2 | ||||||||
rPDU2PhaseStatusNumbermandatory The numeric phase ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.3 | ||||||||
rPDU2PhaseStatusLoadStatemandatory Indicates the present load status of the Rack PDUphase being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.6.3.1.4 | ||||||||
rPDU2PhaseStatusCurrentmandatory Indicates the current draw, in tenths of Amps, of the loadon the Rack PDU phase being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.5 | ||||||||
rPDU2PhaseStatusVoltagemandatory Indicates the Voltage, in Volts, of the RackPDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.6 | ||||||||
rPDU2PhaseStatusPowermandatory Indicates the load power, in hundredths of kilowatts (kW),consumed on the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.7 | ||||||||
rPDU2PhaseStatusApparentPowermandatory Indicates the load apparent power, in hundredths of kiloVoltAmps (kVA),consumed on the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.8 | ||||||||
rPDU2PhaseStatusPowerFactormandatory Indicates the load power factor, in hundredths,of the Rack PDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.9 | ||||||||
rPDU2PhaseStatusPeakCurrentmandatory The peak current of the Rack PDU phase load in tenths of Amps | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.10 | ||||||||
rPDU2PhaseStatusPeakCurrentTimestampmandatory Indicates the date and time that the peak current occurred | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.6.3.1.11 | ||||||||
rPDU2PhaseStatusPeakCurrentStartTimemandatory Indicates the date and time of the last phase peak current reset | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.6.3.1.12 | ||||||||
rPDU2PhaseStatusEnergymandatory A user resettable energy meter measuring Rack PDU phase loadenergy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.6.3.1.13 |
.1.3.6.1.4.1.318.1.1.26.8.1
·
1 row entry
·
8 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2BankConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2BankConfigTable'
A table of Rack PDU bank configuration data
Configuration data from currently queried
Rack PDU bank
Rack PDU bank
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2BankConfigIndexmandatory The index to the Rack PDU bank configurationtable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.1 | ||||||||
rPDU2BankConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.2 | ||||||||
rPDU2BankConfigNumbermandatory The numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.3 | ||||||||
rPDU2BankConfigOverloadRestrictionmandatory This OID controls the behavior of a Switched Rack PDUbank when an overload condition is possible and additional outlets are requested to be turned on. Setting this OID to alwaysAllowTurnON (1) will alway… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.8.1.1.4 | ||||||||
| User-defined low load bank current threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.5 | ||||||||
| User-defined near bank overload current warning threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.6 | ||||||||
| User-defined bank overload current threshold in Amps | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.1.1.7 | ||||||||
rPDU2BankConfigBankPeakCurrentResetmandatory Setting this OID to reset (2) will cause the existing peak current valueto be replaced by the present load current value. Getting this OID will do nothing and return the noOperation(1) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.8.1.1.8 |
.1.3.6.1.4.1.318.1.1.26.8.2
·
1 row entry
·
5 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2BankPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2BankPropertiesTable'
A table of Rack PDU bank properties
Properties of the currently queried
Rack PDU bank
Rack PDU bank
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2BankPropertiesIndexmandatory The index to the Rack PDU bank propertiestable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.2.1.1 | ||||||||||||
rPDU2BankPropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.2.1.2 | ||||||||||||
rPDU2BankPropertiesNumbermandatory The numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.2.1.3 | ||||||||||||
rPDU2BankPropertiesPhaseLayoutmandatory This OID describes the outlet phase connections onthe referenced bank as follows: seqPhase1ToNeutral(1) indicates that bank outlets are wired from Phase 1 to Neutral. seqPhase2ToNeutral(2)… | Rpdu2OutletPhaseLayoutType Type Values:
| .1.3.6.1.4.1.318.1.1.26.8.2.1.4 | ||||||||||||
rPDU2BankPropertiesBreakerRatingmandatory If bank circuit breakers are present on the device, this OID will return the rating of the breaker in Amps. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.2.1.5 |
.1.3.6.1.4.1.318.1.1.26.8.3
·
1 row entry
·
11 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2BankStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2BankStatusTable'
A table of Rack PDU bank status data
Status data from currently queried Rack PDU
bank
bank
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2BankStatusIndexmandatory The index to the Rack PDU bank statustable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.1 | ||||||||
rPDU2BankStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.2 | ||||||||
rPDU2BankStatusNumbermandatory The numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.3 | ||||||||
rPDU2BankStatusLoadStatemandatory Indicates the present load status of the Rack PDUbank being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.8.3.1.4 | ||||||||
rPDU2BankStatusCurrentmandatory Indicates the current draw, in tenths of Amps, of the loadon the Rack PDU bank being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.5 | ||||||||
rPDU2BankStatusPeakCurrentmandatory The peak current of the Rack PDU bank load in tenths of Amps | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.6 | ||||||||
rPDU2BankStatusPeakCurrentTimestampmandatory Indicates the date and time the bank peak current occurred | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.8.3.1.7 | ||||||||
rPDU2BankStatusPeakCurrentStartTimemandatory Indicates the date and time of the last bank peak current reset | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.8.3.1.8 | ||||||||
rPDU2BankStatusVoltagemandatory Indicates the Voltage, in Volts, of the Rack PDU bank being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.9 | ||||||||
rPDU2BankStatusPowermandatory Indicates the load power, in hundredths of kilowatts (kW),consumed on the RackPDU phase being queried. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.10 | ||||||||
rPDU2BankStatusEnergymandatory A user resettable energy meter measuring Rack PDU phase loadenergy consumption in tenths of kilowatt-hours. Models that do not support this feature will respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.8.3.1.11 |
.1.3.6.1.4.1.318.1.1.26.9.2.1
·
1 row entry
·
8 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2OutletSwitchedConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2OutletSwitchedConfigTable'
A table of Rack PDU switched outlet configuration data
Configuration data from currently queried
Rack PDU switched outlet
Rack PDU switched outlet
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2OutletSwitchedConfigIndexmandatory The index to the Rack PDU switched outletconfiguration table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.1 |
rPDU2OutletSwitchedConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.2 |
rPDU2OutletSwitchedConfigNamemandatory The user-defined switched outlet ID string | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.3 |
rPDU2OutletSwitchedConfigNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.4 |
rPDU2OutletSwitchedConfigPowerOnTimemandatory The amount of delay, in seconds, between whenpower is provided to the Rack PDU and when this switched outlet starts providing power. Range -1...7200 where -1 = Never power on, 0 = immediate power on, and 1-7200 = secon… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.5 |
| The amount of time, in seconds, this outlet will delay powering off. Range -1...7200 where -1 = Never power off, 0 = immediate power off, and 1-7200 = seconds to delay. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.6 |
| After turning power off during a reboot sequence, the amount of time to wait before turning power to this outlet back on. Range 5-60 seconds delay. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.7 |
| User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page for convenient support such as user manuals, specifications… | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.9.2.1.1.8 |
.1.3.6.1.4.1.318.1.1.26.9.2.2
·
1 row entry
·
6 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2OutletSwitchedPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2OutletSwitchedPropertiesTable'
A table of Rack PDU switched outlet properties
Properties of the currently queried Rack PDU
switched outlet
switched outlet
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2OutletSwitchedPropertiesIndexmandatory The index to the Rack PDU switched outletproperties table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.1 | ||||||||||||
rPDU2OutletSwitchedPropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.2 | ||||||||||||
rPDU2OutletSwitchedPropertiesNamemandatory The user-defined switched outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.3 | ||||||||||||
rPDU2OutletSwitchedPropertiesNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.4 | ||||||||||||
| This OID describes the phase connections of the referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicat… | Rpdu2OutletPhaseLayoutType Type Values:
| .1.3.6.1.4.1.318.1.1.26.9.2.2.1.5 | ||||||||||||
rPDU2OutletSwitchedPropertiesBankmandatory The numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.2.1.6 |
.1.3.6.1.4.1.318.1.1.26.9.2.3
·
1 row entry
·
7 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2OutletSwitchedStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2OutletSwitchedStatusTable'
A table of Rack PDU switched outlet status information
Status information for currently queried
Rack PDU switched outlet
Rack PDU switched outlet
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
rPDU2OutletSwitchedStatusIndexmandatory The index to the Rack PDU switched outletstatus information table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.1 | ||||||
rPDU2OutletSwitchedStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.2 | ||||||
rPDU2OutletSwitchedStatusNamemandatory The user-defined switched outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.3 | ||||||
rPDU2OutletSwitchedStatusNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.4 | ||||||
rPDU2OutletSwitchedStatusStatemandatory Indicates the present switch state of the RackPDU switched outlet being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.9.2.3.1.5 | ||||||
| Indicates whether or not the device is processing a command for this outlet. If the commandPendingUnknown (3) value is returned, all devices powered by the Rack PDU should be shut down. The Rack PDU's po… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.9.2.3.1.6 | ||||||
| Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletSwitchedConfigExternalLink OID. When this link is clicked in the web interface, the linked URL will open in the web b… | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.2.3.1.7 |
.1.3.6.1.4.1.318.1.1.26.9.2.4
·
1 row entry
·
5 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2OutletSwitchedControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2OutletSwitchedControlTable'
A table of Rack PDU switched outlet control data
Control data for currently queried Rack
PDU switched outlet
PDU switched outlet
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2OutletSwitchedControlIndexmandatory The index to the Rack PDU switched outletcontrol data table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.4.1.1 | ||||||||||||||||
rPDU2OutletSwitchedControlModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.4.1.2 | ||||||||||||||||
rPDU2OutletSwitchedControlNamemandatory The user-defined switched outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.2.4.1.3 | ||||||||||||||||
rPDU2OutletSwitchedControlNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.2.4.1.4 | ||||||||||||||||
rPDU2OutletSwitchedControlCommandmandatory Getting this variable will return the outlet state. Ifthe outlet is on, the immediateOn (1) value will be returned. If the outlet is off, the immediateOff (2) value will be returned. If the state of the outlet cannot b… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.9.2.4.1.5 |
.1.3.6.1.4.1.318.1.1.26.9.4.1
·
1 row entry
·
8 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2OutletMeteredConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2OutletMeteredConfigTable'
A table of Rack PDU metered outlet configuration data
Configuration data from currently queried
Rack PDU metered outlet
Rack PDU metered outlet
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2OutletMeteredConfigIndexmandatory The index to the Rack PDU metered outletconfiguration table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.1 |
rPDU2OutletMeteredConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.2 |
rPDU2OutletMeteredConfigNamemandatory The user-defined metered outlet ID string | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.3 |
rPDU2OutletMeteredConfigNumbermandatory The numeric switched outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.4 |
| User-defined low load outlet current threshold in Watts | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.5 |
| User-defined near outlet overload warning threshold in Watts | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.6 |
| User-defined outlet overload current threshold in Watts | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.7 |
rPDU2OutletMeteredConfigExternalLinkmandatory User-defined external device web link. Possible use cases could be the IP address of the external device plugged into the outlet or its manufacturer web page for convenient support such as user manuals, specifications… | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.9.4.1.1.8 |
.1.3.6.1.4.1.318.1.1.26.9.4.2
·
1 row entry
·
7 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2OutletMeteredPropertiesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2OutletMeteredPropertiesTable'
A table of Rack PDU metered outlet properties
Properties of currently queried Rack PDU
metered outlet
metered outlet
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2OutletMeteredPropertiesIndexmandatory The index to the Rack PDU metered properties tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.1 | ||||||||||||
rPDU2OutletMeteredPropertiesModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.2 | ||||||||||||
rPDU2OutletMeteredPropertiesNamemandatory The user-defined metered outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.3 | ||||||||||||
rPDU2OutletMeteredPropertiesNumbermandatory The numeric metered outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.4 | ||||||||||||
rPDU2OutletMeteredPropertiesLayoutmandatory This OID describes the phase connections ofthe referenced outlet as follows: seqPhase1ToNeutral(1) indicates that the outlet is wired from Phase 1 to Neutral. seqPhase2ToNeutral(2) indicat… | Rpdu2OutletPhaseLayoutType Type Values:
| .1.3.6.1.4.1.318.1.1.26.9.4.2.1.5 | ||||||||||||
| Maximum power rating of Rack PDU metered outlet | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.6 | ||||||||||||
rPDU2OutletMeteredPropertiesBankmandatory This outlet's numeric bank ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.2.1.7 |
.1.3.6.1.4.1.318.1.1.26.9.4.3
·
1 row entry
·
14 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2OutletMeteredStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2OutletMeteredStatusTable'
A table of Rack PDU metered outlet status data
Status data from currently queried Rack PDU
metered outlet
metered outlet
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2OutletMeteredStatusIndexmandatory The index to the Rack PDU metered status tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.1 | ||||||||
rPDU2OutletMeteredStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.2 | ||||||||
rPDU2OutletMeteredStatusNamemandatory The user-defined metered outlet ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.3 | ||||||||
rPDU2OutletMeteredStatusNumbermandatory The numeric metered outlet ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.4 | ||||||||
rPDU2OutletMeteredStatusStatemandatory Indicates the present load status of the RackPDU metered outlet being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.9.4.3.1.5 | ||||||||
rPDU2OutletMeteredStatusCurrentmandatory Indicates the current draw, in tenthsof Amps, of the load on the Rack PDU outlet being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.6 | ||||||||
rPDU2OutletMeteredStatusPowermandatory Indicates the power draw of the loadon the Rack PDU outlet being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.7 | ||||||||
rPDU2OutletMeteredStatusPeakPowermandatory Indicates the peak power load drawon the Rack PDU outlet being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.8 | ||||||||
| Indicates the date and time that this metered outlet's peak power consumption occurred | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.9 | ||||||||
| Indicates the start date and time that this metered outlet began recording peak power observations | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.10 | ||||||||
rPDU2OutletMeteredStatusEnergymandatory A user resettable energy meter measuring Rack PDU loadenergy consumption in tenths of kilowatt-hours | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.11 | ||||||||
| Indicates receptacle type for the outlet. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.12 | ||||||||
rPDU2OutletMeteredStatusExternalLinkmandatory Each RPDU outlet can have its own external web URL link. This can be configured in the rPDU2OutletMeteredConfigExternalLink OID. When this link is clicked in the web interface, the linked URL will open in the web br… | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.13 | ||||||||
rPDU2OutletMeteredStatusPowerFactormandatory The power factor of the Rack PDU outlet in hundredths. Models that do not support this featurewill respond to this OID with a value of -1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.9.4.3.1.14 |
.1.3.6.1.4.1.318.1.1.26.10.2.1
·
1 row entry
·
16 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2SensorTempHumidityConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2SensorTempHumidityConfigTable'
A table of temperature-humidity sensor configuration data
Configuration data from temperature-humidity sensor
being queried
being queried
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
rPDU2SensorTempHumidityConfigIndexmandatory The index to the temperature-humidity sensorconfiguration data table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.1 | ||||
rPDU2SensorTempHumidityConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.2 | ||||
rPDU2SensorTempHumidityConfigNamemandatory The user-defined temperature-humiditysensor ID string | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.3 | ||||
rPDU2SensorTempHumidityConfigNumbermandatory The temperature-humidity sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.4 | ||||
| Setting this OID enables or disables generation of sensor temperature alarm. Getting this OID returns the current value of the temperature alarm enable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.1.1.5 | ||||
| Setting this OID enables or disables generation of sensor humidity alarm. Getting this OID returns the current value of the humidity alarm enable. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.1.1.6 | ||||
| Sensor maximum temperature alarm threshold in Fahrenheit. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHighThreshF will result in an error. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.7 | ||||
| Sensor high temperature warning alarm threshold in Fahrenheit. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigTempMaxThreshF will result in an error. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.8 | ||||
| Sensor temperature hysteresis setting in Fahrenheit | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.9 | ||||
| Sensor maximum temperature alarm threshold in Celsius. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigTempHighThreshC will result in an error. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.10 | ||||
| Sensor high temperature warning alarm threshold in Celsius. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigTempMaxThreshC will result in an error. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.11 | ||||
| Sensor temperature hysteresis setting in Celsius | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.12 | ||||
| Sensor low humidity warning alarm threshold in percent relative humidity. Attempting to set this OID to a value less than or equal to that of rPDU2SensorTempHumidityConfigHumidityMinThresh will result in an error. Must … | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.13 | ||||
| Sensor minimum humidity alarm threshold in percent relative humidity. Attempting to set this OID to a value greater than or equal to that of rPDU2SensorTempHumidityConfigHumidityLowThresh will result in an error. Must b… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.14 | ||||
| Sensor humidity hysteresis setting in percent relative humidity | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.1.1.15 | ||||
| Setting this OID to reset (2) will cause the existing peak temperature to be replaced by the present temperature reading. Getting this OID will do nothing and return the noOperation(1) value. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.1.1.16 |
.1.3.6.1.4.1.318.1.1.26.10.2.2
·
1 row entry
·
15 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2SensorTempHumidityStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2SensorTempHumidityStatusTable'
A table of temperature-humidity sensor status data
Status information from temperature-humidity sensor
being queried
being queried
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2SensorTempHumidityStatusIndexmandatory The index to the temperature-humiditystatus data table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.1 | ||||||||||||
rPDU2SensorTempHumidityStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.2 | ||||||||||||
rPDU2SensorTempHumidityStatusNamemandatory The user-defined temperature-humiditysensor ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.3 | ||||||||||||
rPDU2SensorTempHumidityStatusNumbermandatory The temperature-humidity sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.4 | ||||||||||||
rPDU2SensorTempHumidityStatusTypemandatory The type of the sensor | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.2.1.5 | ||||||||||||
| The communications status of the sensor | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.2.1.6 | ||||||||||||
rPDU2SensorTempHumidityStatusTempFmandatory Sensor temperature reading in tenths of degrees Fahrenheit | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.7 | ||||||||||||
rPDU2SensorTempHumidityStatusTempCmandatory Sensor temperature reading in tenths of degrees Celsius | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.8 | ||||||||||||
| This OID reports the current state of the temperature probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that the probe is present and its measured tem… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.2.1.9 | ||||||||||||
| Sensor humidity reading in percent relative humidity | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.10 | ||||||||||||
| This OID reports the current state of the humidity probe. A notPresent (1) response indicates that no probe is attached. A belowMin (2) response indicates that the probe is present and its measured humidi… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.2.2.1.11 | ||||||||||||
| Sensor peak temperature in tenths of degrees Fahrenheit | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.12 | ||||||||||||
| Sensor peak temperature in tenths of degrees Celsius | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.13 | ||||||||||||
| Indicates the date and time that the peak temperature occurred | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.14 | ||||||||||||
| Indicates the date and time of the last temperature peak reset | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.2.2.1.15 |
.1.3.6.1.4.1.318.1.1.26.10.4.1
·
1 row entry
·
6 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2SensorDiscreteConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2SensorDiscreteConfigTable'
A table of discrete sensor configuration data
Configuration data from discreste sensor
being queried
being queried
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
rPDU2SensorDiscreteConfigIndexmandatory The index to the discrete sensor configurationdata table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.1.1.1 | ||||||
rPDU2SensorDiscreteConfigModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.1.1.2 | ||||||
rPDU2SensorDiscreteConfigNamemandatory The user-defined discrete sensor ID string | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.1.26.10.4.1.1.3 | ||||||
rPDU2SensorDiscreteConfigNumbermandatory The discrete sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.1.1.4 | ||||||
rPDU2SensorDiscreteConfigNormalStatemandatory Indicates the normal state of the discrete inputcontact | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.1.1.5 | ||||||
| Indicates the severity of alarm triggered by abnormal discrete input contact state | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.1.1.6 |
.1.3.6.1.4.1.318.1.1.26.10.4.2
·
1 row entry
·
8 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2SensorDiscreteStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2SensorDiscreteStatusTable'
A table of discrete sensor status data
Status information from discrete sensor
being queried
being queried
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
rPDU2SensorDiscreteStatusIndexmandatory The index to the discrete sensor status datatable entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.2.1.1 | ||||||||||||||
rPDU2SensorDiscreteStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.2.1.2 | ||||||||||||||
rPDU2SensorDiscreteStatusNamemandatory The user-defined discrete sensor ID string | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.1.26.10.4.2.1.3 | ||||||||||||||
rPDU2SensorDiscreteStatusNumbermandatory The discrete sensor numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.10.4.2.1.4 | ||||||||||||||
rPDU2SensorDiscreteStatusTypemandatory The type of discrete sensor currently being queried | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.2.1.5 | ||||||||||||||
rPDU2SensorDiscreteStatusCommStatusmandatory The communications status of the sensor | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.2.1.6 | ||||||||||||||
| The current open/close state of the discrete sensor | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.2.1.7 | ||||||||||||||
rPDU2SensorDiscreteStatusAlarmStatemandatory Indicates alarm status of discrete sensor input | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.10.4.2.1.8 |
.1.3.6.1.4.1.318.1.1.26.13.1
·
1 row entry
·
5 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2PhaseToPhaseStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2PhaseToPhaseStatusTable'
A table of Rack PDU phase to phase status data. This table is only applicable to SKUs that have phase to phase outputs.
Status data from currently queried Rack PDU
phase to phase outputs
phase to phase outputs
Indexes
| Column | Syntax | OID |
|---|---|---|
rPDU2PhaseToPhaseStatusIndexmandatory The index to the Rack PDU phase to phase status tableentry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.1 |
rPDU2PhaseToPhaseStatusModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.2 |
rPDU2PhaseToPhaseStatusVoltage1to2mandatory Indicates the Voltage, in Volts, of the RackPDU phase 1 to phase 2 output being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.3 |
rPDU2PhaseToPhaseStatusVoltage2to3mandatory Indicates the Voltage, in Volts, of the RackPDU phase 2 to phase 3 output being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.4 |
rPDU2PhaseToPhaseStatusVoltage3to1mandatory Indicates the Voltage, in Volts, of the RackPDU phase 3 to phase 2 output being queried | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.13.1.1.5 |
.1.3.6.1.4.1.318.1.1.26.15.1
·
1 row entry
·
8 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk rPDU2RCMTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::rPDU2RCMTable'
A table of Rack PDU RCM.
RCM data from currently queried Rack PDU
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
rPDU2RCMIndexmandatory The index to the Rack PDU RCM table entry | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.1 | ||||||||
rPDU2RCMModulemandatory The user-defined Rack PDU numeric ID | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.2 | ||||||||
rPDU2RCMCurrentmandatory RCM RMS current. (mA) | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.3 | ||||||||
rPDU2RCMAlarmStatusmandatory RCM alarm status.Setting the selected variable to 1, will clear the over alarm. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.15.1.1.4 | ||||||||
rPDU2RCMSelfCheckCommandmandatory Getting this variable will return the RCM self checking status, 1: featureNotAvailable(-1) 2: success(1) 3: failed(2) 4: pending(3). Setting any of the selected pdu's rcm's variable to 1, will immediately start RCM Sel… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.1.26.15.1.1.5 | ||||||||
rPDU2RCMWarningThresholdmandatory Over Warning threshold of RCM current. (mA),threshold can be set in the range of 15-300mA, and must be lower or equal than Alarm threshold. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.6 | ||||||||
rPDU2RCMAlarmThresholdmandatory Over Alarm threshold of RCM current. (mA),threshold can be set in the range of 15~300 mA, and must be higher or equal than Warning threshold. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.7 | ||||||||
rPDU2RCMSelfCheckPeriodmandatory RCM Self-Checking Period. (day)period can be set in the range of 1~365 days, the rcm period on a single pdu is the same, setting one of the selected pdu's rcm's period, will change all rcm's period of this pdu. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.1.26.15.1.1.8 |
.1.3.6.1.4.1.318.1.2.1.2.2
·
1 row entry
·
4 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk powerNetSoftwareTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::powerNetSoftwareTable'
A list of the software monitoring the UPS.
An entry containing information on a software module.
Indexes
| Column | Syntax | OID |
|---|---|---|
moduleNumbermandatory The index into the Software Entry Table | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.2.1.2.2.1.1 |
moduleNamemandatory The name of the software module. | OctetString Constraints: range: 0-79 | .1.3.6.1.4.1.318.1.2.1.2.2.1.2 |
moduleVersionmandatory The version of the software module. | OctetString Constraints: range: 0-8 | .1.3.6.1.4.1.318.1.2.1.2.2.1.3 |
moduleDatemandatory The date of the software module represented as mm-dd-yy. | OctetString Constraints: range: 0-9 | .1.3.6.1.4.1.318.1.2.1.2.2.1.4 |
.1.3.6.1.4.1.318.1.2.3.3.4
·
1 row entry
·
3 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk pcnsNmcTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::pcnsNmcTable'
The Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown.
Details of the NMC.
Indexes
| Column | Syntax | OID |
|---|---|---|
pcnsNmcIndexmandatory Index of the NMC within PCNS setup. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.2.3.3.4.1.1 |
pcnsNmcAddrmandatory The IP address of the NMC. | RFC1155-SMIIpAddress Type Constraints: range: 4 | .1.3.6.1.4.1.318.1.2.3.3.4.1.2 |
pcnsNmcOutletmandatory The Outlet Group which PCNS is enrolled with on the NMC. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.2.3.3.4.1.3 |
.1.3.6.1.4.1.318.1.2.3.5.9
·
1 row entry
·
11 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk pcnsAdvancedShutdownTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::pcnsAdvancedShutdownTable'
The Network Management Cards in the UPS's which PCNS is monitoring to provide safe shutdown.
Details of the NMC.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
pcnsAdvancedGroupNomandatory Index of the Advanced Shutdown Group. | RFC1155-SMIGauge Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.318.1.2.3.5.9.1.1 | ||||
pcnsAdvancedGroupNamemandatory Name of the Advanced Shutdown Group. | OctetStringr/w Constraints: range: 0-32 | .1.3.6.1.4.1.318.1.2.3.5.9.1.2 | ||||
pcnsAdvancedGroupNMCmandatory List of NMCs in the Advanced Shutdown Group. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.318.1.2.3.5.9.1.3 | ||||
| Number of UPS's required to power load. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.2.3.5.9.1.4 | ||||
| Run a shutdown command file before performing graceful shutdown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.5 | ||||
pcnsAdvancedShutdownCommandFilemandatory Full name of the shutdown command file to run before graceful shutdown. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.1.2.3.5.9.1.6 | ||||
| How long in seconds shutdown command file takes to run. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.1.2.3.5.9.1.7 | ||||
pcnsAdvancedShutdownPowerchuteServermandatory Shut down PowerChute Server. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.8 | ||||
pcnsAdvancedShutdownOnLostRedundancymandatory Shut down if Redundancy lost. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.9 | ||||
pcnsAdvancedTurnOffUpsmandatory Turn off the UPS when performing a graceful shutdown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.10 | ||||
pcnsAdvancedTurnOffSOGmandatory Turn off the Outlet Group on the UPS when performing a graceful shutdown. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.1.2.3.5.9.1.11 |
.1.3.6.1.4.1.318.2.1.2
·
1 row entry
·
6 columns
Uses the inova variant from
Command help
/opt/observium/mibs/inova.
Walk mconfigTrapReceiverTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'PowerNet-PDU' -M '/opt/observium/mibs/inova:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'PowerNet-PDU::mconfigTrapReceiverTable'
A list of managers to send traps to. The number of entries is given by the value of mconfigNumTrapReceivers.
The managers to send traps to.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
trapIndexmandatory The index to a trap receiver entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.318.2.1.2.1.1 | ||||||
receiverAddrmandatory The IP address of the manager to send a trap to. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.318.2.1.2.1.2 | ||||||
communityStringmandatory The community name to use in the trap whensent to the manager. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.318.2.1.2.1.3 | ||||||
severityobsolete The severity threshold of traps to send to the manager.traps are labeled in severity as informational(1), warning(2), severe(3). Only traps of equal or greater severity than this value are sent to the manager. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.318.2.1.2.1.4 | ||||||
acceptThisReceivermandatory The value of yes(1) indicates that trap generation for this manager is enabled.The value of no(2) indicates that trap generation for this manager is disabled | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.318.2.1.2.1.5 | ||||||
receiveTrapTypeobsolete Type of trap. | Enumeration Enumerated Values: