.1.3.6.1.4.1.705.1.2.2
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgManagersTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgManagersTable'
The table of managers.
The description of a manager entry in the managers table.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
mgmanagerIndexmandatory
A unique value for each manager. Its value ranges between 1
and the value of upsmgManagersNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.2.2.1.1 |
||||||||||||||||||||
|
mgmanagerDeviceNumbermandatory
This object is the number of the manager device in the
DevicesTable of the Config group. This means that the manager is powered by the UPS. If not the default value is 0. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.2.2.1.2 |
||||||||||||||||||||
|
mgmanagerNMSTypemandatory
The type of manager according to the NMS platform. We
include in the manager class all systems which will be notified by the agent via receiving traps (e.g. basic to complex NMS software). |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.2.2.1.3 |
||||||||||||||||||||
|
mgmanagerCommTypemandatory
The level of communication protocol for that manager.
Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgManagersTable. It is an implementation-specific matter as … |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.2.2.1.4 |
||||||||||||||||||||
|
mgmanagerDescrmandatory
A textual string containing information about the manager.
(manufacturer and version description). |
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.2.2.1.5 |
||||||||||||||||||||
|
mgmanagerAddressmandatory
The IP address of the manager station receiving traps. The
value of this object is meaningful if and only if the value of the relevant mgmanagerCommType object is snmp type. |
RFC1155-SMIIpAddressr/w Type Constraints: range: 4 |
.1.3.6.1.4.1.705.1.2.2.1.6 |
||||||||||||||||||||
|
mgmanagerCommunitymandatory
The manager community string.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.2.2.1.7 |
||||||||||||||||||||
|
mgmanagerSeverityLevelmandatory
The severity level of traps to be received by this manager.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.2.2.1.8 |
||||||||||||||||||||
|
mgmanagerTrapAckmandatory
The manager Trap Acknowledgement status. Setting
this object to mgnoack(2) or stdnomg(3) or cpqnoack(5) disables the trap acknowledgement from the related manager. The MG enterprise specific trap should then be sent onl… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.2.2.1.9 |
.1.3.6.1.4.1.705.1.3.2
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgReceptaclesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgReceptaclesTable'
The table of receptacles that are controlled by the UPS.
The description of a receptacle in the table.
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
mgreceptacleIndexmandatory
A unique value for each receptacle. Its value ranges between
1 and the value of upsmgReceptaclesNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.3.2.1.1 |
||||||||||||||||
|
mgreceptacleLevelmandatory
The level of receptacle.
Setting this object to value invalid(2) has the effect of invalidating the corresponding entry in the upsmgReceptaclesTable. It is an implementation-specific matter as to wether t… |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.2 |
||||||||||||||||
|
mgreceptacleTypemandatory
A textual string for the receptacle type.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.3.2.1.3 |
||||||||||||||||
|
mgreceptacleIdentmandatory
A textual string identification for the user.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.3.2.1.4 |
||||||||||||||||
|
mgreceptacleStatemandatory
The ON/OFF status of the receptacle.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.3.2.1.5 |
||||||||||||||||
|
mgreceptacleReceptaclemandatory
The receptacle number of the second level receptacle father.
The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle cl… |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.6 |
||||||||||||||||
|
mgreceptaclePowerConsmandatory
The volt-ampere rating of the receptacle.
The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the … |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.7 |
||||||||||||||||
|
mgreceptacleOverloadmandatory
The overload status of the receptacle.
The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the def… |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.8 |
||||||||||||||||
|
mgreceptacleAutonomymandatory
The receptacle autonomy.
The value of this object is meaningful if and only if the value of the relevant mgreceptacleType object is related to a two-level receptacle class. Otherwise the default value is … |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.3.2.1.9 |
.1.3.6.1.4.1.705.1.4.22
·
1 row entry
·
8 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgConfigDevicesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgConfigDevicesTable'
The table of devices that are powered by the UPS.
The description of a device entry in the devices table.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
mgdeviceIndexmandatory
A unique value for each device. Its value ranges between 1
and the value of upsmgDevicesNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.4.22.1.1 |
|
mgdeviceReceptacleNummandatory
The receptacle number of the device plugged into the UPS.
This value gives index entry in the ReceptaclesTable object of the Receptacle group. A value of 0 invalidates the entry in the DevicesTable. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.2 |
|
mgdeviceIdentmandatory
A textual string for device user identification.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.4.22.1.3 |
|
mgdeviceVaRatingmandatory
The volt-ampere rating of the device plugged into the UPS.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.4 |
|
mgdeviceSequenceOffmandatory
To set the device position in the remote shutdown sequence.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.5 |
|
mgdeviceSequenceOnmandatory
To set the device position in the remote reboot sequence.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.6 |
|
mgdeviceShutdownDurationmandatory
To set the duration from start of computer shut-down
to complete. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.7 |
|
mgdeviceBootUpDurationmandatory
To set the duration from start of computer boot-up
to complete. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.22.1.8 |
.1.3.6.1.4.1.705.1.4.23
·
1 row entry
·
10 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgConfigReceptaclesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgConfigReceptaclesTable'
The table of receptacles.
The description of a receptacle entry in the table.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
mgreceptacleIndexbmandatory
A unique value for each receptacle. Its value ranges between 1
and the value of upsmgReceptaclesNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.4.23.1.1 |
||||||||
|
mgreceptacleStateTurnOnmandatory
Default return state at turn on.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.4.23.1.2 |
||||||||
|
mgreceptacleStateMainReturnmandatory
Default return state on main return.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.4.23.1.3 |
||||||||
|
mgreceptacleStateDischargemandatory
Default return state on main return from battery discharge.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.4.23.1.4 |
||||||||
|
mgreceptacleShutoffLevelmandatory
Battery level for starting shutoff sequence.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.5 |
||||||||
|
mgreceptacleShutoffTimermandatory
Time delay from on battery for starting shutoff sequence.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.6 |
||||||||
|
mgreceptacleRestartLevelmandatory
Battery level for starting restart sequence.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.7 |
||||||||
|
mgreceptacleRestartDelaymandatory
Time delay for starting restart sequence.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.8 |
||||||||
|
mgreceptacleShutdownDurationmandatory
Maximum Shutdown Duration for systems powered by this plug.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.9 |
||||||||
|
mgreceptacleBootUpDurationmandatory
Maximum Reboot Duration for systems powered by this plug.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.23.1.10 |
.1.3.6.1.4.1.705.1.4.25
·
1 row entry
·
2 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgConfigExtAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgConfigExtAlarmTable'
The table of environmental external alarms.
The description of an external alarm in the table.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
mgextAlarmIndexmandatory
A unique value for each external alarm. Its value ranges
between 1 and the value of upsmgConfigExtAlarmNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.4.25.1.1 |
|
mgextAlarmUIDmandatory
A textual string for alarm state user identification.
|
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.705.1.4.25.1.2 |
.1.3.6.1.4.1.705.1.4.29
·
1 row entry
·
3 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgConfigControlDayTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgConfigControlDayTable'
The table of daily on/off time.
The description of a daily on/off time schedule in the table.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
mgcontrolDayIndexmandatory
The day index. It is a number between 1 and 7, 1 for
Sunday, 2 for Monday, ... |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.4.29.1.1 |
|
mgcontrolDayOnmandatory
To set daily power on time. Any value greater than 86400
is to disable the Day On. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.29.1.2 |
|
mgcontrolDayOffmandatory
To set daily power off time. Any value greater than 86400
is to disable the Day Off. |
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.29.1.3 |
.1.3.6.1.4.1.705.1.4.34
·
1 row entry
·
14 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgConfigEnvironmentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgConfigEnvironmentTable'
The table containing the configuration of the environment sensor.
The description of an entry in the table.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
upsmgConfigSensorIndexmandatory
The sensor index, ranging from 1 to upsmgEnvironmentNum.
|
Integer32 Constraints: range: 0-50 |
.1.3.6.1.4.1.705.1.4.34.1.1 |
|
upsmgConfigSensorNamemandatory
The sensor user-friendly name.
|
OctetStringr/w Constraints: range: 0-42 |
.1.3.6.1.4.1.705.1.4.34.1.2 |
|
upsmgConfigTemperatureLowmandatory
The low temperature threshold in unit 0.1 Cel.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.3 |
|
upsmgConfigTemperatureHighmandatory
The high temperature threshold in unit 0.1 Cel.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.4 |
|
upsmgConfigTemperatureHysteresismandatory
The temperature hysteresys used for threshold test in unit 0.1 Cel.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.5 |
|
upsmgConfigHumidityLowmandatory
The low humidity threshold in unit 1 %.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.6 |
|
upsmgConfigHumidityHighmandatory
The high humidity threshold in unit 1 %.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.7 |
|
upsmgConfigHumidityHysteresismandatory
The humidity hysteresys used for threshold test in unit 1 %.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.4.34.1.8 |
|
upsmgConfigInput1Namemandatory
The Input #1 user-friendly name.
|
OctetStringr/w Constraints: range: 0-22 |
.1.3.6.1.4.1.705.1.4.34.1.9 |
|
upsmgConfigInput1ClosedLabelmandatory
The Input #1 label for closed position.
|
OctetStringr/w Constraints: range: 0-18 |
.1.3.6.1.4.1.705.1.4.34.1.10 |
|
upsmgConfigInput1OpenLabelmandatory
The Input #1 label for open position.
|
OctetStringr/w Constraints: range: 0-18 |
.1.3.6.1.4.1.705.1.4.34.1.11 |
|
upsmgConfigInput2Namemandatory
The Input #2 user-friendly name.
|
OctetStringr/w Constraints: range: 0-22 |
.1.3.6.1.4.1.705.1.4.34.1.12 |
|
upsmgConfigInput2ClosedLabelmandatory
The Input #2 label for closed position.
|
OctetStringr/w Constraints: range: 0-18 |
.1.3.6.1.4.1.705.1.4.34.1.13 |
|
upsmgConfigInput2OpenLabelmandatory
The Input #2 label for open position.
|
OctetStringr/w Constraints: range: 0-18 |
.1.3.6.1.4.1.705.1.4.34.1.14 |
.1.3.6.1.4.1.705.1.6.2
·
1 row entry
·
6 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgInputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgInputPhaseTable'
The table of input phases.
The description of an input phase.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
mginputIndexmandatory
The input phase voltage index. It is a number between 1
and upsmgInputPhaseNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.6.2.1.1 |
|
mginputVoltagemandatory
The input phase voltage.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.2 |
|
mginputFrequencymandatory
The input phase frequency.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.3 |
|
mginputMinimumVoltagemandatory
The input phase minimum voltage over the last minute.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.4 |
|
mginputMaximumVoltagemandatory
The input phase maximum voltage over the last minute.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.5 |
|
mginputCurrentmandatory
The input phase current.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.6.2.1.6 |
.1.3.6.1.4.1.705.1.7.2
·
1 row entry
·
5 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgOutputPhaseTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgOutputPhaseTable'
The table of output phases.
The description of an output phase.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
mgoutputPhaseIndexmandatory
The output phase voltage index. It is a number between 1
and upsmgOutputPhaseNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.7.2.1.1 |
|
mgoutputVoltagemandatory
The output phase voltage.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.7.2.1.2 |
|
mgoutputFrequencymandatory
The output phase frequency.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.7.2.1.3 |
|
mgoutputLoadPerPhasemandatory
The output load per phase.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.7.2.1.4 |
|
mgoutputCurrentmandatory
The output phase current.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.7.2.1.5 |
.1.3.6.1.4.1.705.1.8.3
·
1 row entry
·
2 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgEnvironExtAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgEnvironExtAlarmTable'
The table of external alarms.
The description of an external alarm.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
mgalarmNummandatory
The external alarm number. A number between 1 and
upsmgConfigExtAlarmNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.8.3.1.1 |
||||
|
mgalarmStatemandatory
The external alarm state (active or inactive).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.3.1.2 |
.1.3.6.1.4.1.705.1.8.5
·
1 row entry
·
3 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgEnvironSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgEnvironSensorTable'
The table of sensor units.
The description of a sensor unit.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
mgsensorNummandatory
The unit number. A number between 1 and 4.
|
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.8.5.1.1 |
|
mgsensorTempmandatory
The measured temperature of the unit.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.8.5.1.2 |
|
mgsensorHumiditymandatory
The measured humidity of the unit.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.8.5.1.3 |
.1.3.6.1.4.1.705.1.8.7
·
1 row entry
·
10 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgEnvironmentSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgEnvironmentSensorTable'
The table containing the measurements and alarms made by Environment sensor units.
The description of an entry in the measurement table.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
upsmgEnvironmentIndexmandatory
The sensor index, ranging from 1 to upsmgEnvironmentNum.
|
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.8.7.1.1 |
||||
|
upsmgEnvironmentComFailuremandatory
The sensor communication failure : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.2 |
||||
|
upsmgEnvironmentTemperaturemandatory
The temperature measurement in unit 0.1 Cel.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.8.7.1.3 |
||||
|
upsmgEnvironmentTemperatureLowmandatory
Temperature is below low theshold : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.4 |
||||
|
upsmgEnvironmentTemperatureHighmandatory
Temperature is above high threshold : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.5 |
||||
|
upsmgEnvironmentHumiditymandatory
The humidity measurement in unit 0.1 %.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.8.7.1.6 |
||||
|
upsmgEnvironmentHumidityLowmandatory
Humidity is below low threshold : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.7 |
||||
|
upsmgEnvironmentHumidityHighmandatory
Humidity is above high threshold : yes(1), no(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.8 |
||||
|
upsmgEnvironmentInput1Statemandatory
State of Input#1 : closed(1), open(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.9 |
||||
|
upsmgEnvironmentInput2Statemandatory
State of Input#2 : closed(1), open(2).
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.8.7.1.10 |
.1.3.6.1.4.1.705.1.9.1
·
1 row entry
·
11 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk upsmgControlReceptaclesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'MG-SNMP-UPS-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'MG-SNMP-UPS-MIB::upsmgControlReceptaclesTable'
The table of receptacles.
The description of a receptacle entry in the table.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
mgreceptacleIndexcmandatory
A unique value for each receptacle. Its value ranges between 1
and the value of upsmgReceptaclesNum. |
Integer32 Constraints: range: 1-50 |
.1.3.6.1.4.1.705.1.9.1.1.1 |
||||||||
|
mgreceptacleOnDelaymandatory
Turn on UPS receptacle w/delay=?.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.9.1.1.2 |
||||||||
|
mgreceptacleOnCtrlmandatory
The receptacle control on action.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.3 |
||||||||
|
mgreceptacleOnStatusmandatory
The receptacle control on status.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.4 |
||||||||
|
mgreceptacleOffDelaymandatory
Turn off UPS receptacle w/delay=?.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.9.1.1.5 |
||||||||
|
mgreceptacleOffCtrlmandatory
The receptacle control off action.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.6 |
||||||||
|
mgreceptacleOffStatusmandatory
The receptacle control off status.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.7 |
||||||||
|
mgreceptacleToggleDelaymandatory
Turn off then on UPS receptacle w/delay=?.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.705.1.9.1.1.8 |
||||||||
|
mgreceptacleToggleCtrlmandatory
The receptacle control toggle action.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.9 |
||||||||
|
mgreceptacleToggleStatusmandatory
The receptacle control toggle status.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.705.1.9.1.1.10 |
||||||||
|
mgreceptacleToggleDurationmandatory
Turn off then on UPS receptacle w/duration=?.
|
Integer32r/w Type Constraints: range: -2147483648..2147483647 |