The MIB module defines MIB objects which include Environment Monitor Unit,
Analog Environment data, Digital Environment data, Out data and
Fan data Monitor management MIB interfaces.
The communication alarm of environment monitoring board,
reporting the environment monitoring unit ID.
This trap message is reported when the communication between the emu and control board is fault.
controlAlarmResume
.1.3.6.1.4.1.2011.6.1.2.0.10
The control alarm, reporting the environment monitoring unit ID.
This trap message is reported when emu control operation resumes.
digtalMeasureAlarm
.1.3.6.1.4.1.2011.6.1.2.0.11
The digital measure alarm, reporting the environment
monitoring unit ID and the channel ID of the digital sensor.
This trap message is reported when emu measure operation fails.
digtaleasureAlarmResume
.1.3.6.1.4.1.2011.6.1.2.0.12
The digital measure alarm recovery, reporting the environment
monitoring unit ID and the channel ID of the digital sensor.
This trap message is reported when emu measure operation resumes.
fanExistsAlarm
.1.3.6.1.4.1.2011.6.1.2.0.13
Fan nonexistance alarm.
This trap message is reported when there is no fan device connected to control board.
fanExistsAlarmResume
.1.3.6.1.4.1.2011.6.1.2.0.14
Fan nonexistance alarm recovery.
This trap message is reported when there is a fan device connected to control board.
fanRunStateAlarm
.1.3.6.1.4.1.2011.6.1.2.0.15
Fan running status alarm.
This trap message is reported when the fan run state gets abnormal.
envCommAlarmResume
.1.3.6.1.4.1.2011.6.1.2.0.2
The communication alarm recovery of the environment monitoring,
reporting the environment monitoring unit ID.
This trap message is reported when the communication between the emu and control board resumes.
anaFaultAlarm
.1.3.6.1.4.1.2011.6.1.2.0.3
The alarm recovery of the analog exception,
reporting the environment monitoring unit ID.
This trap message is reported when there is an analog exception in emu.
anaFaultAlarmResume
.1.3.6.1.4.1.2011.6.1.2.0.4
The alarm recovery of the analog exception,
reporting the environment monitoring unit ID.
This trap message is reported when the analog exception recovery in emu.
anaTooHighAlarm
.1.3.6.1.4.1.2011.6.1.2.0.5
The alarm of too high an analog, reporting the environment
monitoring unit ID and the channel ID of the analog sensor.
This trap message is reported when an analog value is too high.
anaTooHighAlarmResume
.1.3.6.1.4.1.2011.6.1.2.0.6
The alarm of too high analog resume,
reporting the environment monitoring unit ID.
This trap message is reported when an analog value
returns to normal range from the high value.
anaTooLowAlarm
.1.3.6.1.4.1.2011.6.1.2.0.7
The alarm of too low an analog, reporting the environment
monitoring unit ID and the channel ID of the analog sensor.
This trap message is reported when an analog value is too low.
anaTooLowAlarmResume
.1.3.6.1.4.1.2011.6.1.2.0.8
The alarm of too low an analog, reporting the
environment monitoring unit ID.
This trap message is reported when an analog value
returns to normal range from the low value.
controlAlarm
.1.3.6.1.4.1.2011.6.1.2.0.9
The control alarm, reporting the environment monitoring unit ID.
This trap message is reported when emu control operation fails.
hwEmmEmuAutofindTrap
.1.3.6.1.4.1.2011.6.1.4.1.0.1
The agent generates this trap when a new
EMU autofind.
hwEmmEmufailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.1
The agent generates this trap when the
communication of the EMU with the host
is abnormal.
hwOpticalReceiverPowerRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.10
The agent generates this trap when
the optical power of OpticalReceiver recovers to normal range.
hwOpticalReceiverRFPowerFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.11
The agent generates this trap when
the RF power of OpticalReceiver is abnormal.
hwOpticalReceiverRFPowerRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.12
The agent generates this trap when
the RF power of OpticalReceiver recovers to normal range.
hwOpticalTransmitterPowerFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.13
The agent generates this trap when
the optical power of OpticalTransmitter is abnormal.
hwOpticalTransmitterPowerRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.14
The agent generates this trap when
the optical power of OpticalTransmitter recovers to normal range.
hwOpticalTransmitterBiasFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.15
The agent generates this trap when
the optical bias of OpticalTransmitter is abnormal.
hwOpticalTransmitterBiasRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.16
The agent generates this trap when
the optical bias of OpticalTransmitter recovers to normal range.
hwOpticalDualChnProtectSwitchTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.17
The agent generates this trap when
the dual-channel optical occur protect-switch channel.
hwOpticalReceiverDualChnPowerFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.18
The agent generates this trap when
the optical power of dual-channel OpticalReceiver is abnormal.
hwOpticalReceiverDualChnPowerRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.19
The agent generates this trap when
the optical power of dual-channel OpticalReceiver recovers to normal range.
hwEmmEmuRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.2
The agent generates this trap when the
communication of the EMU with the host
recovers.
hwModuleOpticalTransmitterPowerFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.20
The agent generates this trap when
the optical power of OpticalTransmitter is abnormal.
hwModuleOpticalTransmitterPowerRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.21
The agent generates this trap when
the optical power of OpticalTransmitter recovers to normal range.
hwModuleOpticalTransmitterBiasRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.22
The agent generates this trap when
the optical bias of OpticalTransmitter recovers to normal range.
hwModuleOpticalTransmitterBiasFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.23
The agent generates this trap when
the optical bias of OpticalTransmitter is abnormal.
hwModuleOpticalCombinerRFPowerFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.24
The agent generates this trap when the dual-channel OpticalReceiver use the combiner protect-switch channel policy and
the RF power of dual-channel OpticalReceiver is abnormal.
hwModuleOpticalCombinerRFPowerRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.25
The agent generates this trap when the dual-channel OpticalReceiver use the combiner protect-switch channel policy and
the RF power of dual-channel OpticalReceiver recovers to normal range .
hwEmmDoorLockCommFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.26
The agent generates this trap when the door lock cannot communicate with the main board.
hwEmmDoorLockCommRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.27
The agent generates this trap when the door lock recover to communicate with the main board.
hwEmmDoorLockAbnormalUnlockTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.28
The agent generates this trap when the the door lock is abnormal unlocked.
hwEmmDoorLockAbnormalUnlockRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.29
The agent generates this trap when the the door lock recover to the normal state.
hwEmmEmuHardwareFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.3
The agent generates this trap when the following two faults occurs:
1. Power fault, which involves the following three scenarios:
1) Only one power board is installed on the MSAN.
2) Two power boards are detected on the device but only one power board is connected to the power supply.
3) Two power boards are detected on the device but one of them is faulty and cannot supply power.
2. Read temperature fault, which occurs when the fan temperature sensor is faulty.
hwOpticalModuleTypeMismatchTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.30
The agent generates this trap when the type of the inserted optical receiver or transmitter does not match that
supported by the slot.
hwOpticalModuleTypeMismatchRestoreTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.31
The agent generates this trap when mismatch between the type of the optical receiver or transmitter and that
supported by the slot is rectified.
hwEmmDoorLockOpenLockTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.32
The agent generates this trap when the electronic lock is opened.
hwOpticalReceiverRfChangeFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.33
The agent generates this trap when the RF output power change exceeds the alarm threshold.
hwOpticalModuleAbsenceTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.34
The agent generates this trap when the optical module plug out.
hwEmmEmuHardwareRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.4
The agent generates this trap when the
a Hardware exception Recover
hwEmmEmuAutofindFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.5
The agent generates this trap when the
emu autofind fail.
hwEmmEmuFanStateTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.6
The agent generates this trap when
the fan is not configured or fails.
hwOpticalNodeFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.7
The agent generates this trap when the
communication of the OpticalNode with the host
is abnormal.
hwOpticalNodeRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.8
The agent generates this trap when the
communication of the OpticalNode with the host
recovers.
hwOpticalReceiverPowerFailTrap
.1.3.6.1.4.1.2011.6.1.4.2.1.0.9
The agent generates this trap when
the optical power of OpticalReceiver is abnormal.
hwEmmAnaUnnamedFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.1
The agent generates this trap when an unnamed
analog alarm occurs.
hwEmmAnaCurrentRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.10
The agent generates this trap when the analog
current alarm recovers.
hwEmmAnaUnnamedRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.2
The agent generates this trap when an unnamed
analog alarm recovers.
hwEmmAnaTempFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.3
The agent generates this trap when the analog
temperature alarm occurs.
hwEmmAnaTempRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.4
The agent generates this trap when the analog
temperature alarm recovers.
hwEmmAnaHumyFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.5
The agent generates this trap when the analog
humidity alarm occurs.
hwEmmAnaHumyRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.6
The agent generates this trap when the analog
humidity alarm recovers.
hwEmmAnaVoltFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.7
The agent generates this trap when the analog
voltage alarm occurs.
hwEmmAnaVoltRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.8
The agent generates this trap when the analog
voltage alarm recovers.
hwEmmAnaCurrentFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.2.0.9
The agent generates this trap when the analog
current alarm occurs.
hwEmmDigFanBlockFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.1
The agent generates this trap when the
fan is blocked.
hwEmmDigAcvolFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.11
The agent generates this trap when
The AC voltage is out of the normal
range.
hwEmmDigAcvolRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.12
The agent generates this trap when
The AC voltage recovers to the
normal range.
hwEmmDigAcswitchFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.13
The agent generates this trap when
The AC switch is out of the normal
range.
hwEmmDigAcswitchRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.14
The agent generates this trap when
The AC switch recovers to the
normal range.
hwEmmDigBattvolFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.15
The agent generates this trap when
The batt vol is out of the normal
range.
hwEmmDigBattvolRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.16
The agent generates this trap when
The batt vol recovers to the
normal range.
hwEmmDigBattfuseFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.17
The agent generates this trap when
The battery fuse is out of the normal
range.
hwEmmDigBattfuseRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.18
The agent generates this trap when
The battery fuse recovers to the
normal range.
hwEmmDigLoadfuseFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.19
The agent generates this trap when
The load fuse is out of the normal
range.
hwEmmDigFanBlockRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.2
The agent generates this trap when the
fan is recovered from block.
hwEmmDigLoadfuseRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.20
The agent generates this trap when
The load fuse recovers to the
normal range.
hwEmmDigRectifierFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.21
The agent generates this trap when
The Rectifier is out of the normal
range.
hwEmmDigRectifierRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.22
The agent generates this trap when
The Rectifier recovers to the
normal range.
hwEmmDigDcpowerFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.23
The agent generates this trap when
The dc-power is out of the normal
range.
hwEmmDigDcpowerRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.24
The agent generates this trap when
The dc-power recovers to the
normal range.
hwEmmDigRoomdoorFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.25
The agent generates this trap when
The Roomdoor is out of the normal
range.
hwEmmDigRoomdoorRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.26
The agent generates this trap when
The Roomdoor recovers to the
normal range.
hwEmmDigTheftFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.27
The agent generates this trap when
The Roomdoor is out of the normal
range.
hwEmmDigTheftRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.28
The agent generates this trap when
The Roomdoor recovers to the
normal range.
hwEmmDigWiringFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.29
The agent generates this trap when
The WIRING is out of the normal
range.
hwEmmDigFanTempHighFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.3
The agent generates this trap when the
temperature of fan is too high.
hwEmmDigWiringRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.30
The agent generates this trap when
The WIRING recovers to the
normal range.
hwEmmDigFanFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.31
The agent generates this trap when
The FAN is out of the normal
range.
hwEmmDigFanRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.32
The agent generates this trap when
The FAN recovers to the normal
range.
hwEmmDigFireFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.33
The agent generates this trap when
The Fire is out of the normal
range.
hwEmmDigFireRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.34
The agent generates this trap when
The Fire recovers to the normal
range.
hwEmmDigFogFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.35
The agent generates this trap when
The Fog is out of the normal
range.
hwEmmDigFogRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.36
The agent generates this trap when
The Fog recovers to the normal
range.
hwEmmDigWaterFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.37
The agent generates this trap when
The Water is out of the normal
range.
hwEmmDigWaterRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.38
The agent generates this trap when
The Water recovers to the normal
range.
hwEmmDigDieselFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.39
The agent generates this trap when
The Diesel is out of the normal
range.
hwEmmDigFanTempHighRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.4
The agent generates this trap when the
temperature of fan recover from too high.
hwEmmDigDieselRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.40
The agent generates this trap when
The Diesel recovers to the normal
range.
hwEmmDigSmellFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.41
The agent generates this trap when
The Smell is out of the normal
range.
hwEmmDigSmellRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.42
The agent generates this trap when
The Smell recovers to the normal
range.
hwEmmDigAirconditionFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.43
The agent generates this trap when
The Air condition is out of the normal
range.
hwEmmDigAirconditionRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.44
The agent generates this trap when
The Air condition recovers to the normal
range.
hwEmmDigArrsterFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.45
The agent generates this trap when
The arrester is out of the normal
range.
hwEmmDigArrsterRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.46
The agent generates this trap when
The arrester recovers to the normal
range.
hwEmmDigDcvolFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.47
The agent generates this trap when
The DC VOL is out of the normal
range.
hwEmmDigDcvolRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.48
The agent generates this trap when
The DC VOL recovers to the normal
range.
hwEmmFanCriticalBlockFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.49
The agent generates this trap when more
than two fans are blocked.
hwEmmDigUnnamedFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.5
The agent generates this trap when a
unnamed digital fault occurs.
hwEmmFanCriticalBlockRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.50
The agent generates this trap when the
critical multi-fan blocking recovers.
hwEmmDigitalSwitchOpenTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.51
The agent generates this trap when the
48V input switch is closed.
hwEmmDigitalSwitchCloseTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.52
The agent generates this trap when the
48V input switch is opened.
hwEmmDigFanSpeedAbnormalTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.53
The agent generates this trap when the
fan rotation speed deteriorates.
hwEmmDigFanSpeedRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.54
The agent generates this trap when
fan rotation speed deterioration recovers.
hwEmmDigAcInputPowerOffTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.55
The agent generates this trap when
the AC power is off.
hwEmmDigAcInputPowerRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.56
The agent generates this trap when
the AC input power recovers.
hwEmmDigUnnamedRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.6
The agent generates this trap when a
unnamed digital recovers.
hwEmmDigOutputswitchFaultTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.7
The agent generates this trap when Output
switch digital fault occurs.
hwEmmDigOutputswitchRecoverTrap
.1.3.6.1.4.1.2011.6.1.4.2.3.0.8
The agent generates this trap when Output