HM2-IOMODULE-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
4
Rows
4
Columns
19
.1.3.6.1.4.1.248.11.100.1.1.2
·
1 row entry
·
4 columns
Uses the hirschmann variant from
Command help
/opt/observium/mibs/hirschmann.
Walk hm2IOModConfigDigInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HM2-IOMODULE-MIB' -M '/opt/observium/mibs/hirschmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HM2-IOMODULE-MIB::hm2IOModConfigDigInputTable'
IO module config table for inputs
IO module config entry for inputs
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
The module ID of an input.
Module ID 0 corresponds to the power supply module. |
Integer32 Constraints: range: 0-7 |
.1.3.6.1.4.1.248.11.100.1.1.2.1.1 |
||||
|
The ID of an input.
|
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.248.11.100.1.1.2.1.2 |
||||
|
Trigger an event log when input status changes.
If the value is disable (2), no event log entry will be written. If the value is enable (1), an event log entry will be written when the input state changes. The input sta… |
HM2-TC-MIBHmEnabledStatusr/w Type Values:
|
.1.3.6.1.4.1.248.11.100.1.1.2.1.3 |
||||
|
Trigger an SNMP trap log when input status changes.
If the value is disable (2), no SNMP trap will be sent. If the value is enable (1), a SNMP trap will be sent when the input state changes. The SNMP trap will be sent t… |
HM2-TC-MIBHmEnabledStatusr/w Type Values:
|
.1.3.6.1.4.1.248.11.100.1.1.2.1.4 |
.1.3.6.1.4.1.248.11.100.1.1.3
·
1 row entry
·
9 columns
Uses the hirschmann variant from
Command help
/opt/observium/mibs/hirschmann.
Walk hm2IOModConfigDigOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HM2-IOMODULE-MIB' -M '/opt/observium/mibs/hirschmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HM2-IOMODULE-MIB::hm2IOModConfigDigOutputTable'
IO module config table for outputs.
IO module config entry for outputs
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
The module ID of an output.
Module ID 0 corresponds to the power supply module. |
Integer32 Constraints: range: 0-7 |
.1.3.6.1.4.1.248.11.100.1.1.3.1.1 |
||||||||||||||
|
The ID of an output.
|
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.248.11.100.1.1.3.1.2 |
||||||||||||||
|
Trigger an event log when output status changes.
If the value is disable (2), no event log entry will be written. If the value is enable (1), an event log entry will be written when the output state changes. The output … |
HM2-TC-MIBHmEnabledStatusr/w Type Values:
|
.1.3.6.1.4.1.248.11.100.1.1.3.1.3 |
||||||||||||||
|
Trigger an SNMP trap log when output status changes.
If the value is disable (2), no SNMP trap will be sent. If the value is enable (1), a SNMP trap will be sent when the output state changes. The SNMP trap will be sent… |
HM2-TC-MIBHmEnabledStatusr/w Type Values:
|
.1.3.6.1.4.1.248.11.100.1.1.3.1.4 |
||||||||||||||
|
Address type of an input mirrored to the output.
Currently, only ipv4 is supported. |
INET-ADDRESS-MIBInetAddressTyper/w Type Values:
|
.1.3.6.1.4.1.248.11.100.1.1.3.1.5 |
||||||||||||||
|
The IP address of an input mirrored to the output.
Use 0.0.0.0 if the output should not be set. In this case hm2IOModValueDigOutputValue is not-configured(4). Use 127.0.0.1 if a local input should be used. |
INET-ADDRESS-MIBInetAddressr/w Type Constraints: range: 0..255 |
.1.3.6.1.4.1.248.11.100.1.1.3.1.6 |
||||||||||||||
|
The SNMP port number being used by the input mirrored to the output.
This port would be the destination of the SNMP requests for polling the state of the input. |
INET-ADDRESS-MIBInetPortNumberr/w Type Constraints: range: 0..65535 |
.1.3.6.1.4.1.248.11.100.1.1.3.1.7 |
||||||||||||||
|
The module ID of an input mirrored to the output.
Module ID 0 corresponds to the power supply module. Ignored when hm2IOModConfigDigOutputSourceIP is 0.0.0.0. |
Integer32r/w Constraints: range: 0-7 |
.1.3.6.1.4.1.248.11.100.1.1.3.1.8 |
||||||||||||||
|
The ID of an input mirrored to the output.
Ignored when hm2IOModConfigDigOutputSourceIP is 0.0.0.0. |
Integer32r/w Constraints: range: 1-4 |
.1.3.6.1.4.1.248.11.100.1.1.3.1.9 |
.1.3.6.1.4.1.248.11.100.1.2.1
·
1 row entry
·
3 columns
Uses the hirschmann variant from
Command help
/opt/observium/mibs/hirschmann.
Walk hm2IOModValueDigInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HM2-IOMODULE-MIB' -M '/opt/observium/mibs/hirschmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HM2-IOMODULE-MIB::hm2IOModValueDigInputTable'
IO module value table for inputs
IO module value entry for inputs
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
The module ID of an input.
Module ID 0 corresponds to the power supply module. |
Integer32 Constraints: range: 0-7 |
.1.3.6.1.4.1.248.11.100.1.2.1.1.1 |
||||||
|
The ID of an input.
|
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.248.11.100.1.2.1.1.2 |
||||||
|
Status of the input.
If the value is not-available(0), then the IO module is not plugged in, if the value is high(1), the input has high (+24V) value, if the value is low(2), the input has low (0V) value. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.248.11.100.1.2.1.1.3 |
.1.3.6.1.4.1.248.11.100.1.2.2
·
1 row entry
·
3 columns
Uses the hirschmann variant from
Command help
/opt/observium/mibs/hirschmann.
Walk hm2IOModValueDigOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HM2-IOMODULE-MIB' -M '/opt/observium/mibs/hirschmann:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HM2-IOMODULE-MIB::hm2IOModValueDigOutputTable'
IO module value table for outputs
IO module value entry for outputs
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
The module ID of an Output.
Module ID 0 corresponds to the power supply module. |
Integer32 Constraints: range: 0-7 |
.1.3.6.1.4.1.248.11.100.1.2.2.1.1 |
||||||||||
|
The ID of an Output.
|
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.248.11.100.1.2.2.1.2 |
||||||||||
|
Status of the output.
If the value is not-available(0), then the IO module is not plugged in, if the value is high(1), the output has high (+24V) value, if the value is low(2), the output has low (0V) value. If the valu… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.248.11.100.1.2.2.1.3 |