HAWK-I2-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
33
Rows
33
Columns
396

ipTHATable

table
.1.3.6.1.4.1.3711.24.1.1.1.2.2 · 1 row entry · 10 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk ipTHATable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::ipTHATable'
A table giving data for all enabled inputs with analogue-type monitoring.
ipTHAEntry row .1.3.6.1.4.1.3711.24.1.1.1.2.2.1
A conceptual row containing information about one analogue-type input.
Indexes
Column Syntax OID
ipTHAChanThe input number.Integer32
Constraints:
range: 0-48
.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.1
ipTHARSThe analogue-type input table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.2
ipTHANameThe name of this inputDisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.3
ipTHALocnA system-defined name for the physical location of this input, e.g. MCU.DisplayString.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.4
ipTHAAutoDetectIndicates that the type of data this input is monitoring is selected automatically.SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.5
ipTHATypeIndicates the type of data this input is monitoring.InputDataType
Type Values:
1autodetect
2temperature
3humidity
4analogue
5contact
255inactive
.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.6
ipTHAValueThe current reading in the relevant measurement units.
-999999999 - Input Data Uninitialised
-99999999 - Input Data Under Range
-17999680 - Temperature Data Under Range in F
-10000000 - Temperature Data Under Range i…
Integer32
Constraints:
range: -999999999--999999999
range: -99999999--99999999
range: -17999680--17999680
range: -10000000--10000000
range: -9997268--9997268
range: -580-120000
range: 10000000-10000000
range: 10002732-10002732
range: 18000320-18000320
range: 99999999-99999999
.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.7
ipTHAScalingScaling factor for ipTHAValue in units of 0.1 when ipTHAType=analogue.Integer32r/w
Constraints:
range: 0-1
range: 10-10
range: 100-100
range: 1000-1000
range: 10000-10000
.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.8
ipTHAOffsetCalibration offset in the same units as for ipTHAValue.Integer32r/w
Constraints:
range: -1479-2119
.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.9
ipTHAHysteresisHysteresis on threshold levels in the same units as for ipTHAValue.Integer32r/w
Constraints:
range: -1479-2119
.1.3.6.1.4.1.3711.24.1.1.1.2.2.1.10
.1.3.6.1.4.1.3711.24.1.1.1.2.3.1 · 1 row entry · 8 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk ipTHAThreshTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::ipTHAThreshTable'
A table listing the trap threshold levels for all enabled inputs with analogue-type monitoring.
ipTHAThreshEntry row .1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1
A conceptual row containing threshold information for one analogue-type input.
Indexes
Column Syntax OID
ipTHAThreshChanThe input number.Integer32
Constraints:
range: 0-48
.1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.1
ipTHAThreshRSThe analogue-type input table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.2
ipTHAUCLThe Upper Critical Limit for this input in the same units as for ipTHAValue.Integer32r/w
Constraints:
range: -300-100000
.1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.3
ipTHAUWLThe Upper Warning Limit for this input in the same units as for ipTHAValue.Integer32r/w
Constraints:
range: -300-100000
.1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.4
ipTHALWLThe Lower Warning Limit for this input in the same units as for ipTHAValue.Integer32r/w
Constraints:
range: -300-100000
.1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.5
ipTHALCLThe Lower Critical Limit for this input in the same units as for ipTHAValue.Integer32r/w
Constraints:
range: -300-100000
.1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.6
ipTHADeltaPosRising rate of change threshold for ipTHAValue in 0.1 units per minute.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.7
ipTHADeltaNegFalling rate of change threshold for ipTHAValue in 0.1 units per minute.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.1.2.3.1.1.8
.1.3.6.1.4.1.3711.24.1.1.1.2.3.2 · 1 row entry · 8 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk ipTHATrapEnTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::ipTHATrapEnTable'
The table that controls trap enabling for all enabled inputs with analogue-type monitoring.
ipTHATrapEnEntry row .1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1
A conceptual row containing trap enabling information for one analogue-type input.
Indexes
Column Syntax OID
ipTHATrapEnChanThe input number.Integer32
Constraints:
range: 0-48
.1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.1
ipTHATrapEnRSThe analogue-type input table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.2
ipTHAUCLTrapEnEnables and disables input UCL alarm traps.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.3
ipTHAUWLTrapEnEnables and disables input UWL alarm traps.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.4
ipTHALWLTrapEnEnables and disables input LWL alarm traps.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.5
ipTHALCLTrapEnEnables and disables input LCL alarm traps.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.6
ipTHADeltaPosTrapEnTrap enable flag for ipTHADeltaPos.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.7
ipTHADeltaNegTrapEnTrap enable flag for ipTHADeltaNeg.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.1.2.3.2.1.8
.1.3.6.1.4.1.3711.24.1.1.1.2.3.3 · 1 row entry · 8 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk ipTHATrapPerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::ipTHATrapPerTable'
The table that controls trap repetition for all enabled inputs with analogue-type monitoring.
ipTHATrapPerEntry row .1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1
A conceptual row containing trap repetition information for one analogue-type input.
Column Syntax OID
ipTHATrapPerChanThe input number.Integer32
Constraints:
range: 0-48
.1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.1
ipTHATrapPerRSThe table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.2
ipTHATrapUCLPerTrap repetition period for ipTHATrapUCL in seconds. A value of 0 disables trap repetition.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.3
ipTHATrapUWLPerTrap repetition period for ipTHATrapUWL in seconds. A value of 0 disables trap repetition.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.4
ipTHATrapLWLPerTrap repetition period for ipTHATrapLWL in seconds. A value of 0 disables trap repetition.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.5
ipTHATrapLCLPerTrap repetition period for ipTHATrapLCL in seconds. A value of 0 disables trap repetition.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.6
ipTHATrapDeltaPosPerTrap repetition period for ipTHADeltaPos in seconds. A value of 0 disables trap repetition.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.7
ipTHATrapDeltaNegPerTrap repetition period for ipTHADeltaNeg in seconds. A value of 0 disables trap repetition.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.1.2.3.3.1.8

ipContTable

table
.1.3.6.1.4.1.3711.24.1.1.1.3.1 · 1 row entry · 11 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk ipContTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::ipContTable'
A table listing the parameters and data for all enabled inputs with contact-type monitoring.
ipContEntry row .1.3.6.1.4.1.3711.24.1.1.1.3.1.1
A conceptual row containing information about one contact input.
Indexes
Column Syntax OID
ipContChanThe input number.Integer32
Constraints:
range: 0-48
.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.1
ipContRSThe contact input table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.2
ipContNameThe name of this inputDisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.3
ipContLocnA system-defined name for the physical location of this input, e.g. MCU.DisplayString.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.4
ipContAutoDetectIndicates that the type of data this input is monitoring is selected automatically.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.5
ipContNormStateThe normal state for this contact.ContactStater/w
Type Values:
1open
2closed
.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.6
ipContCurrStateThe current state of this contact.InputContactState
Type Values:
1open
2closed
3armed
4triggered
255unknown
.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.7
ipContTrigModeThe contact trigger mode, level, +ve edge, -ve edge.Enumerationr/w
Enumerated Values:
1positiveEdge
2negativeEdge
3level
.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.8
ipContResetResets the contact after triggering in edge mode.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.9
ipContTrapEnConfigure contact input traps.Enumerationr/w
Enumerated Values:
1critical
2warning
3information
255disabled
.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.10
ipContTrapPeriodSet to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in secondsInteger32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.1.3.1.1.11

opTable

table
.1.3.6.1.4.1.3711.24.1.1.2.2 · 1 row entry · 12 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk opTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::opTable'
A table listing the parameters and data for all outputs.
opEntry row .1.3.6.1.4.1.3711.24.1.1.2.2.1
A conceptual row containing information about one output.
Indexes
Column Syntax OID
opChanThe output number.Integer32
Constraints:
range: 0-19
.1.3.6.1.4.1.3711.24.1.1.2.2.1.1
opRSThe contact input table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.2.2.1.2
opNameA user-defined name for this output.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.2.2.1.3
opLocnA system-defined name for the physical location of this output, e.g. MCU.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.2.2.1.4
opNormStateSets or reads the required normal state of this output.RelayStater/w
Type Values:
1on
2off
.1.3.6.1.4.1.3711.24.1.1.2.2.1.5
opCurrStateReads the current state of this output.RelayState
Type Values:
1on
2off
.1.3.6.1.4.1.3711.24.1.1.2.2.1.6
opOnDelTimeSets the 'on' delay time for this output.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.2.2.1.7
opOffDelTimeSets the 'off' delay time for this output.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.2.2.1.8
opBooleanEqnBoolean equation stringDisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.2.2.1.9
opTrapEnConfigure output traps.Enumerationr/w
Enumerated Values:
1critical
2warning
3information
255disabled
.1.3.6.1.4.1.3711.24.1.1.2.2.1.10
opTrapPeriodSet to 0 disables trap repetition, a value of 30 or higher sets the interval between traps in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.2.2.1.11
opControlStateReads the current control state of an output.OutputControlStater/w
Type Values:
1activate
2deactivate
3logic
.1.3.6.1.4.1.3711.24.1.1.2.2.1.12

kpCtlTable

table
.1.3.6.1.4.1.3711.24.1.1.4.2 · 1 row entry · 10 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk kpCtlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::kpCtlTable'
A table listing the parameters and data for the keypads.
kpCtlEntry row .1.3.6.1.4.1.3711.24.1.1.4.2.1
A conceptual row containing information about one keypad.
Indexes
Column Syntax OID
kpNumberThe keypad number.Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.3711.24.1.1.4.2.1.1
kpRSThe keypad table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.4.2.1.2
kpManufacturerThe name of the manufacturer of the keypad.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.4.2.1.3
kpNameA name identifying the keypad.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.4.2.1.4
kpDoorLatchTimeOutTime-out value in seconds for which the door latch is held open.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.4.2.1.5
kpRtnToStndbyTimeOutTime-out value in seconds for Return to Standby ModeInteger32r/w
Constraints:
range: 0-99
.1.3.6.1.4.1.3711.24.1.1.4.2.1.6
kpEntryCodeValidSet if previous keypad entry was valid.SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.4.2.1.7
kpDoorOpenTimeOutTime-out value in seconds for Door Open.Integer32r/w
Constraints:
range: 0-99
.1.3.6.1.4.1.3711.24.1.1.4.2.1.8
kpRemoteDoorOpenSet to open the door.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.4.2.1.9
kpInUseTrapEn'keypad in use' trap enableEnumerationr/w
Enumerated Values:
1critical
2warning
3information
255disabled
.1.3.6.1.4.1.3711.24.1.1.4.2.1.10

acuCtlTable

table
.1.3.6.1.4.1.3711.24.1.1.5.2 · 1 row entry · 13 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk acuCtlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::acuCtlTable'
A table listing the parameters and data for the ACUs.
acuCtlEntry row .1.3.6.1.4.1.3711.24.1.1.5.2.1
A conceptual row containing information about one ACU.
Indexes
Column Syntax OID
acuNumberThe ACU number.Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.3711.24.1.1.5.2.1.1
acuCtlRSThe ACU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.5.2.1.2
acuManufacturerThe name of the manufacturer of the ACU.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.5.2.1.3
acuNameA name identifying the ACU.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.5.2.1.4
acuDoorLatchTimeOutTime-out value in seconds for which the door latch is held open.Unsigned32r/w
Constraints:
range: 0-999
.1.3.6.1.4.1.3711.24.1.1.5.2.1.5
acuRtnToStndbyTimeOutTime-out value in seconds for Return to Standby ModeInteger32r/w
Constraints:
range: 0-999
.1.3.6.1.4.1.3711.24.1.1.5.2.1.6
acuEntryCodeValidSet if previous ACU entry was valid.SNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.5.2.1.7
acuDoorOpenTimeOutTime-out value in seconds for Door Open.Integer32r/w
Constraints:
range: 0-3600
.1.3.6.1.4.1.3711.24.1.1.5.2.1.8
acuRemoteDoorOpenSet to open the door.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.5.2.1.9
acuInUseTrapEn'ACU in use' trap enableEnumerationr/w
Enumerated Values:
1critical
2warning
3information
255disabled
.1.3.6.1.4.1.3711.24.1.1.5.2.1.10
acuTypeA string identifying the ACU type.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.5.2.1.11
acuAlarmsA bit field flagging ACU alarms.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.5.2.1.12
acuLastCodeThe last key code read from the ACU. After this is consumed, write an empty string to clear the contents.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.5.2.1.13

accUserTable

table
.1.3.6.1.4.1.3711.24.1.1.6.1.2 · 1 row entry · 6 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk accUserTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::accUserTable'
A table controlling the access users.
accUserEntry row .1.3.6.1.4.1.3711.24.1.1.6.1.2.1
A conceptual row containing information about one ACU user.
Indexes
Column Syntax OID
accUserNumberThe the access user-table entry number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.6.1.2.1.1
accUserRSThe access user table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.6.1.2.1.2
accUserNameA name identifying the access user.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.6.1.2.1.3
accUserCodeThe user's access code.OctetStringr/w
Constraints:
range: 0-15
.1.3.6.1.4.1.3711.24.1.1.6.1.2.1.4
accUserPrivilegesThe ACUs and keypads that the user is allowed to gain access through - comma-separated numerical strings.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.6.1.2.1.5
accUserExpiresA text string which specifies when the access code in the row expires. The format is defined by the application.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.6.1.2.1.6

pduTable

table
.1.3.6.1.4.1.3711.24.1.1.7.1.2 · 1 row entry · 14 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduTable'
A table containing information about each enabled PDU.
pduEntry row .1.3.6.1.4.1.3711.24.1.1.7.1.2.1
A conceptual row containing information about one PDU.
Indexes
Column Syntax OID
pduNumberThe PDU number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.1
pduRSThe PDU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.2
pduNameA string identifying the PDU.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.3
pduOutEnEnables/disables PDU power outlet control - causes an entry for outlets to be created in each relevant PDU table.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.4
pduMonEnEnables/disables PDU power monitoring - causes an entry for monitoring to be created in each relevant PDU table.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.5
pduCommsFailIndicates comms. status for the PDU.Enumeration
Enumerated Values:
1commsGood
2commsFailed
3commsBadData
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.6
pduTypeIndicates the type of device connected.Enumeration
Enumerated Values:
1rs232PduMk1
2rs232PduTpt
3rs485PduTpt
4rs232CLAmp
5rs485CLAmp
6rs232PduMk2
7rs485PduMk2
8rs485PduMk3
9rs232G5
253virtual
254none
255unknown
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.7
pduModeIndicates the phase circuit topology.Enumeration
Enumerated Values:
1singlePhase
2twoPhase
3threePhaseStar
4threePhaseDelta
253aggregate
254none
255unknown
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.8
pduNumControlIndicates the number of controlled outlets.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.9
pduOutletMonModeIndicates the monitor mode.Enumeration
Enumerated Values:
1currentOnly
2allParameters
254none
255unknown
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.10
pduNumOutletsIndicates the number of monitored outlets.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.11
pduFwVersCPUA string identifying the PDU processor firmware version.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.12
pduFwVersMeterA string identifying the PDU meter firmware version.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.13
pduNumOfCctBrksIndicates the number of monitored branch circuits.Integer32r/w
Constraints:
range: 0-9
.1.3.6.1.4.1.3711.24.1.1.7.1.2.1.14
.1.3.6.1.4.1.3711.24.1.1.7.2.2 · 1 row entry · 7 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduOutCmnTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduOutCmnTable'
A table containing information about the power outlets of all PDUs enabled for outlet control.
pduOutCmnEntry row .1.3.6.1.4.1.3711.24.1.1.7.2.2.1
A conceptual row containing information about the power outlets of one PDU.
Column Syntax OID
pduOutCmnPduNumberThe PDU number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.2.1.1
pduOutCmnRSThe PDU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.7.2.2.1.2
pduNumOfOutletsThe number of switchable outlets on the PDU - determines the number of entries to be created in the outlet table for the relevant PDU.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.2.1.3
pduOutCycleSets the required state of all power outlets on the PDU.Enumerationr/w
Enumerated Values:
1up
2down
255unknown
.1.3.6.1.4.1.3711.24.1.1.7.2.2.1.4
pduOutCyclePwdPassword controling access to setting the required state of all power outlets on the PDU.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.7.2.2.1.5
pduOutCycleAbortTaskAbort power outlet setting task.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.2.1.6
pduOutCycleAbortTimeTime delay to abort power outlet setting task.Unsigned32r/w
Constraints:
range: 0-60
.1.3.6.1.4.1.3711.24.1.1.7.2.2.1.7

pduOutTable

table
.1.3.6.1.4.1.3711.24.1.1.7.2.3 · 1 row entry · 21 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduOutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduOutTable'
A table listing the states and descriptions for each outlet on the PDU.
pduOutEntry row .1.3.6.1.4.1.3711.24.1.1.7.2.3.1
A row containing information about one PDU outlet.
Column Syntax OID
pduOutPduNumberThe PDU number on which the outlet resides.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.1
pduOutNumberThe outlet number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.2
pduOutRSThe PDU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.3
pduOutNameA name identifying the outlet.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.4
pduOutOnThe current state for this outlet.Enumerationr/w
Enumerated Values:
1on
2off
3reboot
4unknown
5failedStuck
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.5
pduOutPwdThe password for this outlet.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.6
pduOutCycleDelayThe on/off delay for this outlet in seconds.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.7
pduOutRebootPeriodThe pduOutOn reboot off period for this outlet in seconds.Unsigned32
Constraints:
range: 5-300
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.8
pduOutRMSAmpsValueRMS current value at the outlet in 0.1 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.9
pduOutRMSAmpsSurgeMaximum value of pduOutRMSAmpsValue for another outlet to be switched on in 0.1 AmpsSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.10
pduOutRMSAmpsPeakMaximum value of pduOutRMSAmpsValue since reset in 0.1 AmpsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.11
pduOutRMSAmpsPkRstResets value of pduOutRMSAmpsPeak to current value of pduOutRMSAmpsValueSNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.12
pduOutMeanKVAValueMean kVA value at the outlet in 0.1 kVASNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.13
pduOutKWHrValuekWhr value at the outlet in 0.1 kWhrSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.14
pduOutPFactorValuePower factor value at the outlet in 0.01 unitsSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.15
pduOutRMSAmpsUTLUpper threshold of pduOutRMSAmpsValue in 0.1 AmpsInteger32r/w
Constraints:
range: -10-500
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.16
pduOutRMSAmpsLTLLower threshold of pduOutRMSAmpsValue in 0.1 AmpsInteger32r/w
Constraints:
range: -10-500
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.17
pduOutRMSAmpsUTLTrapEnTrap enable flag for pduOutRMSAmpsUTL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.18
pduOutRMSAmpsLTLTrapEnTrap enable flag for pduOutRMSAmpsLTL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.19
pduOutRMSAmpsUTLTrapPerTrap repetition period for pduOutRMSAmpsUTL.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.20
pduOutRMSAmpsLTLTrapPerTrap repetition period for pduOutRMSAmpsLTL.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.2.3.1.21

pduMonTable

table
.1.3.6.1.4.1.3711.24.1.1.7.3.1 · 1 row entry · 37 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduMonTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduMonTable'
A table containing monitor information for all PDUs enabled for monitoring.
pduMonEntry row .1.3.6.1.4.1.3711.24.1.1.7.3.1.1
A conceptual row containing monitor information for one PDU.
Indexes
Column Syntax OID
pduMonPduNumberThe PDU number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.1
pduMonRSThe PDU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.2
pduRMSVoltsValueRMS Volts across load in VoltsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.3
pduRMSAmpsValueRMS current through load in 0.1 AmpsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.4
pduTotalEnergyValueTotal energy supplied to load in 0.1 kWhInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.5
pduMeanKVAValueKilo Volt-Amperes supplied to load in 0.1 kVAInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.6
pduMeanKWattsValueKilo Watts supplied to load in 0.1 kWInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.7
pduPwrFactorValuePower factor of load in 0.01Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.8
pduPwrSupplyFreqPower supply frequency in 0.1HzInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.9
pduPhaseVoltsValueRMS Volts across phase in VoltsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.10
pduPhaseAmpsValueRMS current supplied by phase in 0.1 AmpsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.11
pduPhaseEnergyValueTotal energy supplied by phase in 0.1 kWhInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.12
pduPhaseKVAValueApparent power supplied by phase in 0.1 kVAInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.13
pduPhaseKWattsValueTrue power supplied by phase in 0.1 kWInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.14
pduPhasePwrFactorValuePower factor of phase in 0.01Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.15
pduCircuitNameA string identifying the circuit.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.16
pduCctKVAMaxMaximum apparent power in circuit for measurment period in 0.1 kVAInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.17
pduCctKVAMaxTimeTimestamp for maximum apparent power in circuitDisplayString.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.18
pduCctKVAMinMinimum apparent power in circuit for measurment period in 0.1 kVAInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.19
pduCctKVAMinTimeTimestamp for mniimum apparent power in circuitDisplayString.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.20
pduCctAmpsMaxMaximum current in circuit for measurment period in 0.1 kVAInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.21
pduCctAmpsMaxTimeTimestamp for maximum current in circuitDisplayString.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.22
pduCctAmpsMinMinimum current in circuit for measurment period in 0.1 kVAInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.23
pduCctAmpsMinTimeTimestamp for minimum current in circuitDisplayString.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.24
pduCctStatSagSetSag status is set in this circuitSNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.25
pduCctStatSagCountSag status count in this circuitSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.26
pduCctStatSagTimeTimestamp for sag status in this circuitDisplayString.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.27
pduCctStatPkVoltsSetPeak Volts status is set in this circuitSNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.28
pduCctStatPkVoltsCountPeak Volts status count in this circuitSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.29
pduCctStatPkVoltsTimeTimestamp for Peak Volts status in this circuitDisplayString.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.30
pduCctStatPwrLossSetPower Loss status is set in this circuitSNMPv2-TCTruthValue
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.31
pduCctStatPwrLossCountPower Loss status count in this circuitSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.32
pduCctStatPwrLossTimeTimestamp for Power Loss status in this circuitDisplayString.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.33
pduCctPermKVAMaxMaximum apparent power in circuit since last reset in 0.1 kVAInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.34
pduCctPermKVAMaxTimeTimestamp for maximum apparent power in circuit since last resetDisplayString.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.35
pduCctPermAmpsMaxMinimum apparent power in circuit since last reset in 0.1 kVAInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.36
pduCctPermAmpsMaxTimeTimestamp for minimum apparent power in circuit since last resetDisplayString.1.3.6.1.4.1.3711.24.1.1.7.3.1.1.37
.1.3.6.1.4.1.3711.24.1.1.7.3.2 · 1 row entry · 22 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduTrapThreshTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduTrapThreshTable'
A table containing information about the trap threshold values for all PDUs enabled for monitoring.
pduTrapThreshEntry row .1.3.6.1.4.1.3711.24.1.1.7.3.2.1
A conceptual row containing information about the trap threshold values for one PDU.
Column Syntax OID
pduTrapThreshPduNumberThe PDU number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.1
pduTrapThreshRSThe PDU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.2
pduRMSVoltsUCLrms UCL value in voltsInteger32r/w
Constraints:
range: -10-500
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.3
pduRMSVoltsUWLrms UWL value in voltsInteger32r/w
Constraints:
range: -10-500
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.4
pduRMSVoltsLWLrms LWL value in voltsInteger32r/w
Constraints:
range: -10-500
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.5
pduRMSVoltsLCLrms LCL value in voltsInteger32r/w
Constraints:
range: -10-500
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.6
pduRMSAmpsUCLrms UCL value in 0.1 ampsInteger32r/w
Constraints:
range: -10-5000
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.7
pduRMSAmpsUWLrms UWL value in 0.1 ampsInteger32r/w
Constraints:
range: -10-5000
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.8
pduRMSAmpsLWLrms LWL value in 0.1 ampsInteger32r/w
Constraints:
range: -10-5000
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.9
pduRMSAmpsLCLrms LCL value in 0.1 ampsInteger32r/w
Constraints:
range: -10-5000
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.10
pduEnergyUCLTotal energy UCL value in 0.1 kWhUnsigned32r/w
Constraints:
range: 0-4294967290
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.11
pduEnergyUWLTotal energy UWL value in 0.1 kWhUnsigned32r/w
Constraints:
range: 0-4294967290
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.12
pduMeanKVAUCLMean kVA UCL value in 0.1 kVAInteger32r/w
Constraints:
range: 0-999990
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.13
pduMeanKVAUWLMean kVA UWL value in 0.1 kVAInteger32r/w
Constraints:
range: 0-999990
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.14
pduMeanKVALWLMean kVA LWL value in 0.1 kVAInteger32r/w
Constraints:
range: 0-999990
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.15
pduMeanKVALCLMean kVA LCL value in 0.1 kVAInteger32r/w
Constraints:
range: 0-999990
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.16
pduMeanKWattsUCLMean power UCL value in 0.1 kWInteger32r/w
Constraints:
range: 0-100000
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.17
pduMeanKWattsUWLMean power UWL value in 0.1 kWInteger32r/w
Constraints:
range: 0-100000
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.18
pduMeanKWattsLWLMean power LWL value in 0.1 kWInteger32r/w
Constraints:
range: 0-100000
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.19
pduMeanKWattsLCLMean power LCL value in 0.1 kWInteger32r/w
Constraints:
range: 0-100000
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.20
pduPwrFactorUTLPower factor UTL value in 0.01Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.21
pduPwrFactorLTLPower factor LTL value in 0.01Integer32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.3711.24.1.1.7.3.2.1.22
.1.3.6.1.4.1.3711.24.1.1.7.3.3 · 1 row entry · 22 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduTrapEnTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduTrapEnTable'
The table which controls threshold value trap enabling for all PDUs enabled for monitoring.
pduTrapEnEntry row .1.3.6.1.4.1.3711.24.1.1.7.3.3.1
A conceptual row containing information about one PDU.
Column Syntax OID
pduTrapEnPduNumberThe PDU number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.1
pduTrapEnRSThe PDU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.2
pduRMSVoltsUCLTrapEnEnables Volts UCL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.3
pduRMSVoltsUWLTrapEnEnables UWL Volts trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.4
pduRMSVoltsLWLTrapEnEnables LWL Volts trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.5
pduRMSVoltsLCLTrapEnEnables LCL Volts trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.6
pduRMSAmpsUCLTrapEnEnables UCL current trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.7
pduRMSAmpsUWLTrapEnEnables UWL current trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.8
pduRMSAmpsLWLTrapEnEnables LWL current trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.9
pduRMSAmpsLCLTrapEnEnables LCL current trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.10
pduEnergyUCLTrapEnEnables UCL total energy trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.11
pduEnergyUWLTrapEnEnables UWL total energy trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.12
pduMeanKVAUCLTrapEnEnables mean kVA UCL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.13
pduMeanKVAUWLTrapEnEnables mean kVA UWL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.14
pduMeanKVALWLTrapEnEnables mean kVA LWL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.15
pduMeanKVALCLTrapEnEnables mean kVA LCL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.16
pduMeanKWattsUCLTrapEnEnables mean power UCL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.17
pduMeanKWattsUWLTrapEnEnables mean power UWL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.18
pduMeanKWattsLWLTrapEnEnables mean power LWL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.19
pduMeanKWattsLCLTrapEnEnables mean power LCL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.20
pduPwrFactorUTLTrapEnEnables power factor UTL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.21
pduPwrFactorLTLTrapEnEnables power factor LTL trap.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.7.3.3.1.22
.1.3.6.1.4.1.3711.24.1.1.7.3.4 · 1 row entry · 22 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduTrapPerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduTrapPerTable'
The table which controls threshold value trap repetition for all PDUs enabled for monitoring.
pduTrapPerEntry row .1.3.6.1.4.1.3711.24.1.1.7.3.4.1
A conceptual row containing information about one PDU.
Column Syntax OID
pduTrapPduNumberThe PDU number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.1
pduTrapPerRSThe PDU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.2
pduRMSVoltsUCLTrapPerSets UCL Volts trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.3
pduRMSVoltsUWLTrapPerSets UWL Volts trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.4
pduRMSVoltsLWLTrapPerSets LWL Volts trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.5
pduRMSVoltsLCLTrapPerSets LCL Volts trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.6
pduRMSAmpsUCLTrapPerSets UCL current trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.7
pduRMSAmpsUWLTrapPerSets UWL current trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.8
pduRMSAmpsLWLTrapPerSets LWL current trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.9
pduRMSAmpsLCLTrapPerSets LCL current trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.10
pduEnergyUCLTrapPerSets UCL total energy trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.11
pduEnergyUWLTrapPerSets UWL total energy trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.12
pduMeanKVAUCLTrapPerSets mean kVA UCL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.13
pduMeanKVAUWLTrapPerSets mean kVA UWL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.14
pduMeanKVALWLTrapPerSets mean kVA LWL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.15
pduMeanKVALCLTrapPerSets mean kVA LCL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.16
pduMeanKWattsUCLTrapPerSets mean power UCL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.17
pduMeanKWattsUWLTrapPerSets mean power UWL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.18
pduMeanKWattsLWLTrapPerSets mean power LWL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.19
pduMeanKWattsLCLTrapPerSets mean power LCL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.20
pduPwrFactorUTLTrapPerSets power factor UTL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.21
pduPwrFactorLTLTrapPerSets power factor LTL trap repeat rate in secondsUnsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.7.3.4.1.22
.1.3.6.1.4.1.3711.24.1.1.7.3.5 · 1 row entry · 14 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduMon3PhTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduMon3PhTable'
A table containing monitor information for all 3-phase PDUs enabled for monitoring.
pduMon3PhEntry row .1.3.6.1.4.1.3711.24.1.1.7.3.5.1
A conceptual row containing monitor information for one 3-phase PDU.
Indexes
Column Syntax OID
pdu3PhPduNumberThe PDU number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.1
pdu3PhRSThe PDU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.2
pdu3PhModeThree phase topologyEnumeration
Enumerated Values:
1star
2delta
253aggregate
254none
255unknown
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.3
pdu3PhVoltsC1Line RMS Volts value in voltsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.4
pdu3PhAmpsL1Phase RMS current value in 0.1 AmpsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.5
pdu3PhVoltsC2Line RMS Volts value in voltsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.6
pdu3PhAmpsL2Phase RMS current value in 0.1 AmpsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.7
pdu3PhVoltsC3Line RMS Volts value in voltsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.8
pdu3PhAmpsL3Phase RMS current value in 0.1 AmpsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.9
pdu3PhAmpsAggTotal RMS current value in 0.1 AmpsInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.10
pdu3PhkVAAggTotal apparent power value in 0.1 kVAInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.11
pdu3PhkWAggTotal true power value in 0.1 kVWInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.12
pdu3PhkVArhAggTotal re-active energy value in 0.1 kVArhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.13
pdu3PhkWhAggTotal true energy value in 0.1 kWhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.3.5.1.14

pduGangTable

table
.1.3.6.1.4.1.3711.24.1.1.7.4.2 · 1 row entry · 8 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduGangTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduGangTable'
A table containing information about each pdu gang.
pduGangEntry row .1.3.6.1.4.1.3711.24.1.1.7.4.2.1
A conceptual row containing information about one pdu gang.
Indexes
Column Syntax OID
pduGangNumberThe pdu gang number.Integer32
Constraints:
range: 1-24
.1.3.6.1.4.1.3711.24.1.1.7.4.2.1.1
pduGangRSThe gang table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.7.4.2.1.2
pduGangEnShows whether the gang is enabled(1), disabled(2) or suspended(3) this may have been disabled
by the application e.g. disabled pdu's in the gang, or bad pdu outlet CRC.
Enumerationr/w
Enumerated Values:
1enabled
2disabled
3suspended
.1.3.6.1.4.1.3711.24.1.1.7.4.2.1.3
pduGangNameThe name of this gang.OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.3711.24.1.1.7.4.2.1.4
pduGangOnThe current state for this gang.
Only states 1(on) ,2(off) and 4(reboot) can be set.
Enumerationr/w
Enumerated Values:
1on
2off
3mixed
4reboot
5na
.1.3.6.1.4.1.3711.24.1.1.7.4.2.1.5
pduGangPasswordThe password required to control this gang.OctetStringr/w
Constraints:
range: 0-16
.1.3.6.1.4.1.3711.24.1.1.7.4.2.1.6
pduGangAbortTaskAbort gang setting task.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.7.4.2.1.7
pduGangMembersA string representing the members of a gang.
The format is PDU:OUTLET; e.g. 1:3;4:2;5:12;3:18; up to 6 member pairs
OctetStringr/w
Constraints:
range: 0-37
.1.3.6.1.4.1.3711.24.1.1.7.4.2.1.8

expTable

table
.1.3.6.1.4.1.3711.24.1.1.8.2 · 1 row entry · 5 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk expTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::expTable'
A table containing information about each enabled Expansion Port.
expEntry row .1.3.6.1.4.1.3711.24.1.1.8.2.1
A conceptual row containing information about one Expansion Port.
Indexes
Column Syntax OID
expNumberThe Expansion Port number; maps to the specific Expansion Port connector.Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.3711.24.1.1.8.2.1.1
expRSThe Expansion Port table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.8.2.1.2
expNameA string identifying the Expansion Port.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.8.2.1.3
expTypeIndicates the External Unit type.ExternalUnitTyper/w
Type Values:
0unknown
1acu
2keypad
3pduEU
4enviroHawk2
5idm
253autoWithTraps
254auto
255inactive
.1.3.6.1.4.1.3711.24.1.1.8.2.1.4
expCommsFailIndicates Comms. Status for the Expansion Port.Enumeration
Enumerated Values:
1commsGood
2commsFailed
3commsBadData
.1.3.6.1.4.1.3711.24.1.1.8.2.1.5

clampTable

table
.1.3.6.1.4.1.3711.24.1.1.9.1 · 1 row entry · 7 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk clampTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::clampTable'
A table containing information about each detected CL-amp unit.
clampEntry row .1.3.6.1.4.1.3711.24.1.1.9.1.1
A conceptual row containing information about one CL-amp unit.
Indexes
Column Syntax OID
clampNumberThe CL-Amp number; maps to the specific CL-Amp Port.Integer32
Constraints:
range: 1-24
.1.3.6.1.4.1.3711.24.1.1.9.1.1.1
clampRSThe CL-Amp table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.9.1.1.2
clampBValueStores the value of the CL-amp unit B Value configuration. This may have been set
by the management station or read from the CL-amp unit depending on recent history.
Value is x 1000.
Unsigned32r/w
Constraints:
range: 20000-150000
.1.3.6.1.4.1.3711.24.1.1.9.1.1.3
clampVoltsStores the value of the CL-amp unit Volts configuration. This may have been set
by the management station or read from the CL-amp unit depending on recent history.
Value is in Volts.
Unsigned32r/w
Constraints:
range: 90-250
.1.3.6.1.4.1.3711.24.1.1.9.1.1.4
clampPwrFactorStores the value of the CL-amp unit Power Factor configuration. This may have been set
by the management station or read from the CL-amp unit depending on recent history.
Value is x100.
Unsigned32r/w
Constraints:
range: 0-100
.1.3.6.1.4.1.3711.24.1.1.9.1.1.5
clampFrequencyStores the value of the CL-amp unit Frequency configuration. This may have been set
by the management station or read from the CL-amp unit depending on recent history.
Value is Hz x10.
Unsigned32r/w
Constraints:
range: 450-650
.1.3.6.1.4.1.3711.24.1.1.9.1.1.6
clampWriteParamsWhen written to, sends the configuration values stored in this table for writing to the CL-amp unit.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.9.1.1.15

idmTable

table
.1.3.6.1.4.1.3711.24.1.1.10.1 · 1 row entry · 4 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk idmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::idmTable'
A table containing information about IDMs
idmEntry row .1.3.6.1.4.1.3711.24.1.1.10.1.1
A conceptual row containing information about one IDM.
Indexes
Column Syntax OID
idmNumberThe IDM number; maps to the specific IDM Port.Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.3711.24.1.1.10.1.1.1
idmRSThe IDM table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.10.1.1.2
idmVersionVersion information returned by the IDM.DisplayString.1.3.6.1.4.1.3711.24.1.1.10.1.1.3
idmStatusIndicates status of the IDM.Enumeration
Enumerated Values:
1enabled
2disabled
255unknown
.1.3.6.1.4.1.3711.24.1.1.10.1.1.4
.1.3.6.1.4.1.3711.24.1.1.11.1.1 · 1 row entry · 26 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pduP2BrCctMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pduP2BrCctMonitorTable'
A table giving branch circuit monitoring information for all PDUs.
pduP2BrCctMonitorEntry row .1.3.6.1.4.1.3711.24.1.1.11.1.1.1
A conceptual row containing information about branch circuit monitoring.
Column Syntax OID
pduP2BrCktMonPduNumberThe PDU index number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.1
pduP2BrCktMonBrCctNumberThe PDU Branch Circuit Number.Unsigned32
Constraints:
range: 1-9
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.2
pduP2BrCktMonRSThe branch circuit monitor table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.3
pduP2BrCktMonBrCctIDThe PDU Branch Circuit ID.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.4
pduP2BrCktMonBrCctPhasesThe PDU Branch Circuit Phases.DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.5
pduP2BrCktMonBrCctCurrentThe PDU Branch Circuit Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.6
pduP2BrCktMonBrCctPeakCurrentThe PDU Branch Circuit Peak Current. The value precision is hundredths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.7
pduP2BrCktMonBrCctPeakCurrentTimestampThe PDU Branch Circuit Peak Current Timestamp.UnsignedTimeTicks.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.8
pduP2BrCktMonBrCctBreakerStatusThe PDU Branch Circuit Breaker Status.BranchCircuitStatusType
Type Values:
1closeOn
2openOff
255invalidFeature
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.9
pduP2BrCktMonBrCctBreakerConfigThe PDU Branch Circuit Breaker Config.BranchCircuitConfigTyper/w
Type Values:
1closeOn
2openOff
255invalidFeature
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.10
pduP2BrCktMonBrCctBreakerTripStateThe PDU Branch Circuit Breaker Trip State.BranchCircuitStatusType
Type Values:
1closeOn
2openOff
255invalidFeature
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.11
pduP2BrCktMonBrCctBreakerContinuousLoadRatingAmpsThe PDU Branch Circuit Breaker Continuous Load Rating Amps.The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.Unsigned32r/w
Constraints:
range: 1-100000
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.12
pduP2BrCktMonBrCctBreakerTripRatingAmpsThe PDU Branch Circuit Breaker Trip Rating Amps. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.Unsigned32r/w
Constraints:
range: 1-100000
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.13
pduP2BrCktMonBrCctBreakerOutletMapA string representing the outlets of a branch circuit.
The format is comma separated list of outlets; e.g. 8,9,10,11,12
DisplayStringr/w.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.14
pduP2BrCktCircuitCurrentUCLCircuit Current UCL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.Integer32r/w
Constraints:
range: -1000-100000
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.15
pduP2BrCktCircuitCurrentUWLCircuit Current UWL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.Integer32r/w
Constraints:
range: -1000-100000
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.16
pduP2BrCktCircuitCurrentLWLCircuit Current LWL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.Integer32r/w
Constraints:
range: -1000-100000
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.17
pduP2BrCktCircuitCurrentLCLCircuit Current LCL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.Integer32r/w
Constraints:
range: -1000-100000
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.18
pduP2BrCktCircuitCurrentUCLTrapEnTrap enable flag for pduP2BrCktCircuitCurrentUCL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.19
pduP2BrCktCircuitCurrentUWLTrapEnTrap enable flag for pduP2BrCktCircuitCurrentUWL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.20
pduP2BrCktCircuitCurrentLWLTrapEnTrap enable flag for pduP2BrCktCircuitCurrentLWL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.21
pduP2BrCktCircuitCurrentLCLTrapEnTrap enable flag for pduP2BrCktCircuitCurrentLCL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.22
pduP2BrCktCircuitCurrentUCLTrapPerTrap repetition period for pduP2BrCktCircuitCurrentUCL.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.23
pduP2BrCktCircuitCurrentUWLTrapPerTrap repetition period for pduP2BrCktCircuitCurrentUWL.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.24
pduP2BrCktCircuitCurrentLWLTrapPerTrap repetition period for pduP2BrCktCircuitCurrentLWL.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.25
pduP2BrCktCircuitCurrentLCLTrapPerTrap repetition period for pduP2BrCktCircuitCurrentLCL.Unsigned32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.3711.24.1.1.11.1.1.1.26

pdu2Table

table
.1.3.6.1.4.1.3711.24.2.1.1.1.1 · 1 row entry · 4 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2Table
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2Table'
A table giving data for all PDUs.
pdu2Entry row .1.3.6.1.4.1.3711.24.2.1.1.1.1.1
A conceptual row containing information about all PDUs.
Indexes
Column Syntax OID
pdu2PduNumberThe PDU index number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.1.1.1
pdu2RSThe PDU table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.1.1.2
pdu2WiringTopologyThe PDU wiring topology description.WiringTopologyType
Type Values:
1disabled
2singlePhase
3twoPhase
4threePhaseStar
5threePhaseDelta
6deltaWithNeutral
254none
255unknown
.1.3.6.1.4.1.3711.24.2.1.1.1.1.1.3
pdu2PhaseTopologyThe PDU phase topology description.DisplayStringr/w.1.3.6.1.4.1.3711.24.2.1.1.1.1.1.4
.1.3.6.1.4.1.3711.24.2.1.1.1.2 · 1 row entry · 6 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2CustDataTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2CustDataTable'
A table giving customer entered metadata for all PDUs
pdu2CustDataEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.2.1
A conceptual row containing information about customer metadata.
Column Syntax OID
pdu2CustDataPduNumberThe PDU index number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.2.1.1
pdu2CustDataRSThe customer metadata table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.2.1.2
pdu2CustDataMainCktRefOverallOverall reference stringCktRefNamer/w
Type Constraints:
range: 0..31
.1.3.6.1.4.1.3711.24.2.1.1.1.2.1.3
pdu2CustDataMainCktRefCktACircuit-A reference stringCktRefNamer/w
Type Constraints:
range: 0..31
.1.3.6.1.4.1.3711.24.2.1.1.1.2.1.4
pdu2CustDataMainCktRefCktBCircuit-B reference stringCktRefNamer/w
Type Constraints:
range: 0..31
.1.3.6.1.4.1.3711.24.2.1.1.1.2.1.5
pdu2CustDataMainCktRefCktCCircuit-C reference stringCktRefNamer/w
Type Constraints:
range: 0..31
.1.3.6.1.4.1.3711.24.2.1.1.1.2.1.6
.1.3.6.1.4.1.3711.24.2.1.1.1.3 · 1 row entry · 9 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2InputAggregateTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2InputAggregateTable'
A table giving input aggregation information for all PDUs.
pdu2InputAggregateEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.3.1
A conceptual row containing information about input aggregation.
Column Syntax OID
pdu2IpAggPduNumberThe PDU index number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.3.1.1
pdu2IpAggRSThe input aggregate table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.3.1.2
pdu2IpAggAggregatekWhThe PDU Aggregate kWh. The value precision is hundredths e.g. a value of 101 is 1.01 kWh.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.3.1.3
pdu2IpAggAggregatekVAThe PDU Aggregate kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.3.1.4
pdu2IpAggAggregatekWThe PDU Aggregate kW. The value precision is hundredths e.g. a value of 101 is 1.01 kW.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.3.1.5
pdu2IpAggAggregatePFThe PDU Aggregate PF. The value precision is thousandths e.g. a value of 1001 is 1.001 PF.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.3.1.6
pdu2IpAggAggregateCurrentThe PDU Aggregate Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.3.1.7
pdu2IpAggAggregateNeutralCurrentThe PDU Aggregate Neutral Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.3.1.8
pdu2IpAggAggregateEarthCurrentThe PDU Aggregate Earth Current. The value precision is thousandths e.g. a value of 101 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.3.1.9
.1.3.6.1.4.1.3711.24.2.1.1.1.4 · 1 row entry · 15 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2PhaseMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2PhaseMonitorTable'
A table giving phase monitoring information data for all PDUs
pdu2PhaseMonitorEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.4.1
A conceptual row containing information about phase monitoring.
Column Syntax OID
pdu2PhMonPduNumberThe PDU index number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.1
pdu2PhMonPhaseNumberThe PDU phase Number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.2
pdu2PhMonRSThe phase monitor table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.3
pdu2PhMonLineIDThe PDU Line ID.DisplayString.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.4
pdu2PhMonPhaseToNeutralVoltageThe PDU Phase To Neutral Voltage. The value precision is tenths e.g. a value of 101 is 10.1 V.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.5
pdu2PhMonPhaseCurrentThe PDU Phase Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.6
pdu2PhMonPhasekVAThe PDU Phase kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.7
pdu2PhMonPhasePeakkVAThe PDU Phase Peak KVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.8
pdu2PhMonPhasePeakkVATimestampThe PDU Phase Peak KVA Timestamp.UnsignedTimeTicks.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.9
pdu2PhMonPhasekWThe PDU Phase hkW. The value precision is hundredths e.g. a value of 101 is 1.01 kW.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.10
pdu2PhMonPhasePFThe PDU Phase PF. The value precision is thousandths e.g. a value of 1001 is 1.001 PF.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.11
pdu2PhMonPhasekWhThe PDU Phase hkWh. The value precision is hundredths e.g. a value of 101 is 1.01 kWh.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.12
pdu2PhMonPhasekVArThe PDU Phase kVAr. The value precision is hundredths e.g. a value of 101 is 1.01 kVAr.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.13
pdu2PhMonPhaseCrestFactorThe PDU Phase Crest Factor. The value precision is thousandths of percent e.g. a value of 999 is 99.9%.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.14
pdu2PhMonPhaseTHDThe PDU Phase THD (Total Harmonic Distortion). The value precision is thousandths of percent e.g. a value of 999 is 99.9%.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.4.1.15
.1.3.6.1.4.1.3711.24.2.1.1.1.5 · 1 row entry · 12 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2CircuitMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2CircuitMonitorTable'
A table giving circuit monitoring information for all PDUs.
pdu2CircuitMonitorEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.5.1
A conceptual row containing information about circuit monitoring.
Column Syntax OID
pdu2CktMonPduNumberThe PDU index number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.1
pdu2CktMonCircuitNumberThe PDU Circuit Number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.2
pdu2CktMonRSThe circuit monitor table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.3
pdu2CktMonLineIDThe PDU Line ID.DisplayString.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.4
pdu2CktMonLineToLineVoltageThe PDU Circuit To Neutral Voltage. The value precision is tenths e.g. a value of 101 is 10.1 V.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.5
pdu2CktMonLineToLineCurrentThe PDU Circuit Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.6
pdu2CktMonLineToLineKVAThe PDU Circuit kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.7
pdu2CktMonLineToLinePeakkVAThe PDU Circuit Peak KVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.8
pdu2CktMonLineToLinePeakkVATimestampThe PDU Circuit Peak hKVA Timestamp.UnsignedTimeTicks.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.9
pdu2CktMonLineToLinekWThe PDU Circuit hkW. The value precision is hundredths e.g. a value of 101 is 1.01 kW.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.10
pdu2CktMonLineToLinePFThe PDU Circuit PF. The value precision is thousandths e.g. a value of 1001 is 1.001 PF.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.11
pdu2CktMonLineToLinekVArThe PDU Circuit kVAr. The value precision is hundredths e.g. a value of 101 is 1.01 kVAr.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.5.1.12
.1.3.6.1.4.1.3711.24.2.1.1.1.6 · 1 row entry · 13 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2BranchCircuitMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2BranchCircuitMonitorTable'
A table giving branch circuit monitoring information for all PDUs.
pdu2BranchCircuitMonitorEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.6.1
A conceptual row containing information about branch circuit monitoring.
Column Syntax OID
pdu2BrCktMonPduNumberThe PDU index number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.1
pdu2BrCktMonBranchCircuitNumberThe PDU Branch Circuit Number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.2
pdu2BrCktMonRSThe branch circuit monitor table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.3
pdu2BrCktMonBranchCircuitIDThe PDU Branch Circuit ID.DisplayString.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.4
pdu2BrCktMonBranchCircuitPhasesThe PDU Branch Circuit Phases.DisplayString.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.5
pdu2BrCktMonBranchCircuitCurrentThe PDU Branch Circuit Current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.6
pdu2BrCktMonBranchCircuitPeakCurrentThe PDU Branch Circuit Peak Current. The value precision is hundredths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.7
pdu2BrCktMonBranchCircuitPeakCurrentTimestampThe PDU Branch Circuit Peak Current Timestamp.UnsignedTimeTicks.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.8
pdu2BrCktMonBranchCircuitBreakerStatusThe PDU Branch Circuit Breaker Status.BranchCircuitStatusType
Type Values:
1closeOn
2openOff
255invalidFeature
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.9
pdu2BrCktMonBranchCircuitBreakerConfigThe PDU Branch Circuit Breaker Config.BranchCircuitConfigTyper/w
Type Values:
1closeOn
2openOff
255invalidFeature
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.10
pdu2BrCktMonBranchCircuitBreakerTripStateThe PDU Branch Circuit Breaker Trip State.BranchCircuitStatusType
Type Values:
1closeOn
2openOff
255invalidFeature
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.11
pdu2BrCktMonBranchCircuitBreakerContinuousLoadRatingAmpsThe PDU Branch Circuit Breaker Continuous Load Rating Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.12
pdu2BrCktMonBranchCircuitBreakerTripRatingAmpsThe PDU Branch Circuit Breaker Trip Rating Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.6.1.13
.1.3.6.1.4.1.3711.24.2.1.1.1.7 · 1 row entry · 14 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2OutletMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2OutletMonitorTable'
A table giving outlet monitoring information for all PDUs.
pdu2OutletMonitorEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.7.1
A conceptual row containing information about outlet monitoring.
Column Syntax OID
pdu2OutMonPduNumberThe PDU index number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.1
pdu2OutMonOutletNumberThe PDU outlet number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.2
pdu2OutMonRSThe outlet monitor table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.3
pdu2OutMonOutletIDThe PDU outlet ID.DisplayString.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.4
pdu2OutMonOutletVoltageThe PDU outlet voltage. The value precision is tenths e.g. a value of 101 is 1.01 V.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.5
pdu2OutMonOutletCurrentThe PDU outlet current. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.6
pdu2OutMonOutletkVAThe PDU outlet kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.7
pdu2OutMonOutletPeakkVAThe PDU outlet peak kVA. The value precision is hundredths e.g. a value of 101 is 1.01 kVA.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.8
pdu2OutMonOutletPeakkVATimestampThe PDU outlet peak kVA timestamp.UnsignedTimeTicks.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.9
pdu2OutMonOutletkWThe PDU outlet hkW. The value precision is hundredths e.g. a value of 101 is 1.01 kW.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.10
pdu2OutMonOutletPFThe PDU outlet PF. The value precision is thousandths e.g. a value of 1001 is 1.001 PF.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.11
pdu2OutMonOutletkWhThe PDU outlet kWh. The value precision is hundredths e.g. a value of 101 is 1.01 kWh.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.12
pdu2OutMonOutletBranchCircuitIDThe PDU outlet circuit ID.DisplayString.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.13
pdu2OutMonOutletPhaseIDThe PDU outlet phase ID.DisplayString.1.3.6.1.4.1.3711.24.2.1.1.1.7.1.14
.1.3.6.1.4.1.3711.24.2.1.1.1.8 · 1 row entry · 7 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2OutletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2OutletControlTable'
A table giving outlet control information for all PDUs.
pdu2OutletControlEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.8.1
A conceptual row containing information about outlet control.
Column Syntax OID
pdu2OutCtlPduNumberThe PDU index number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.8.1.1
pdu2OutCtlOutletNumberThe PDU outlet number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.8.1.2
pdu2OutCtlRSThe outlet control table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.8.1.3
pdu2OutCtlControlledOutletIDThe PDU controlled outlet ID.DisplayString.1.3.6.1.4.1.3711.24.2.1.1.1.8.1.4
pdu2OutCtlControlledOutletStateThe PDU controlled outlet state.ControlledOutletStatusType
Type Values:
1on
2off
3lastKnownState
4timeDelayOn
.1.3.6.1.4.1.3711.24.2.1.1.1.8.1.5
pdu2OutCtlControlledOutletPowerUpStateThe PDU controlled outlet power up state.ControlledOutletStatusType
Type Values:
1on
2off
3lastKnownState
4timeDelayOn
.1.3.6.1.4.1.3711.24.2.1.1.1.8.1.6
pdu2OutCtlControlledOutletPowerUpTimeDelayThe PDU controlled outlet power up time delay.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.8.1.7
.1.3.6.1.4.1.3711.24.2.1.1.1.9 · 1 row entry · 7 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2BranchCircuitThreshTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2BranchCircuitThreshTable'
A table listing the alarm threshold information for each branch circuit.
pdu2BranchCircuitThreshEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.9.1
A conceptual row containing alarm threshold information about one branch circuit.
Column Syntax OID
pdu2BrCktThreshPduNumberThe number of the PDU on which the branch circuit resides.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.9.1.1
pdu2BrCktThreshBranchCircuitNumberThe branch circuit number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.9.1.2
pdu2BrCktThreshRSThe table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.9.1.3
pdu2BrCktBranchCircuitCurrentUCLBranch Circuit Current UCL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.9.1.4
pdu2BrCktBranchCircuitCurrentUWLBranch Circuit Current UWL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.9.1.5
pdu2BrCktBranchCircuitCurrentLWLBranch Circuit Current LWL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.9.1.6
pdu2BrCktBranchCircuitCurrentLCLBranch Circuit Current LCL. The value precision is thousandths e.g. a value of 1001 is 1.001 Amps.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.9.1.7
.1.3.6.1.4.1.3711.24.2.1.1.1.10 · 1 row entry · 7 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2BranchCircuitTrapEnTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2BranchCircuitTrapEnTable'
A table listing the trap enabling information for each branch circuit.
pdu2BranchCircuitTrapEnEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.10.1
A conceptual row containing trap enabling information about one branch circuit.
Column Syntax OID
pdu2BrCktTrapEnPduNumberThe number of the PDU on which the branch circuit resides.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.10.1.1
pdu2BrCktTrapEnBranchCircuitNumberThe branch circuit number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.10.1.2
pdu2BrCktTrapEnRSThe table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.10.1.3
pdu2BrCktBranchCircuitCurrentUCLTrapEnTrap enable flag for pdu2BrCktBranchCircuitCurrentUCL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.2.1.1.1.10.1.4
pdu2BrCktBranchCircuitCurrentUWLTrapEnTrap enable flag for pdu2BrCktBranchCircuitCurrentUWL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.2.1.1.1.10.1.5
pdu2BrCktBranchCircuitCurrentLWLTrapEnTrap enable flag for pdu2BrCktBranchCircuitCurrentLWL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.2.1.1.1.10.1.6
pdu2BrCktBranchCircuitCurrentLCLTrapEnTrap enable flag for pdu2BrCktBranchCircuitCurrentLCL.SNMPv2-TCTruthValuer/w
Type Values:
1true
2false
Description:
Represents a boolean value.
.1.3.6.1.4.1.3711.24.2.1.1.1.10.1.7
.1.3.6.1.4.1.3711.24.2.1.1.1.11 · 1 row entry · 7 columns
Uses the panduit variant from /opt/observium/mibs/panduit.
Command help
Walk pdu2BranchCircuitTrapPerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'HAWK-I2-MIB' -M '/opt/observium/mibs/panduit:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'HAWK-I2-MIB::pdu2BranchCircuitTrapPerTable'
A table listing the trap repetition periods for each branch circuit on the PDUs.
pdu2BranchCircuitTrapPerEntry row .1.3.6.1.4.1.3711.24.2.1.1.1.11.1
A conceptual row containing trap repetition periods for one branch circuit.
Column Syntax OID
pdu2BrCktTrapPerPduNumberThe number of the PDU on which the branch circuit resides.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.11.1.1
pdu2BrCktTrapPerBranchCircuitNumberThe outlet number.SNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.11.1.2
pdu2BrCktTrapPerRSThe table row status.SNMPv2-TCRowStatus
Type Values:
1active
2notInService
3notReady
4createAndGo
5createAndWait
6destroy
Description:
The RowStatus textual convention is used to manage the
creation and deletion of conceptual rows, and is used as the
value of the SYNTAX clause for the status column of a
conceptual row (as described in Section 7.7.1 of …
.1.3.6.1.4.1.3711.24.2.1.1.1.11.1.3
pdu2BrCktBranchCircuitCurrentUCLTrapPerTrap repetition period for pdu2BrCktBranchCircuitCurrentUCL.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.11.1.4
pdu2BrCktBranchCircuitCurrentUWLTrapPerTrap repetition period for pdu2BrCktBranchCircuitCurrentUWL.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.11.1.5
pdu2BrCktBranchCircuitCurrentLWLTrapPerTrap repetition period for pdu2BrCktBranchCircuitCurrentLWL.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.11.1.6
pdu2BrCktBranchCircuitCurrentLCLTrapPerTrap repetition period for pdu2BrCktBranchCircuitCurrentLCL.SNMPv2-SMIUnsigned32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.3711.24.2.1.1.1.11.1.7