GUDEADS-PDU835X-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
4
Rows
4
Columns
33
.1.3.6.1.4.1.28507.52.1.1.1.2 · 1 row entry · 2 columns
Uses the gude variant from /opt/observium/mibs/gude.
Command help
Walk pdu835XTrapIPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-PDU835X-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-PDU835X-MIB::pdu835XTrapIPTable'
list of all Trap receiver
pdu835XTrapIPEntry row .1.3.6.1.4.1.28507.52.1.1.1.2.1
an entry containing management
informations regarding the list of trap
receivers
Column Syntax OID
A unique value, greater than zero, for each receiver slot.
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.28507.52.1.1.1.2.1.1
DNS name or IP address specifying one Trap receiver slot.
A port can optionally be specified: 'name:port' An empty
string disables this slot.
OctetStringr/w
Constraints:
range: 0-99
.1.3.6.1.4.1.28507.52.1.1.1.2.1.2
.1.3.6.1.4.1.28507.52.1.5.1.2 · 1 row entry · 23 columns
Uses the gude variant from /opt/observium/mibs/gude.
Command help
Walk pdu835XPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-PDU835X-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-PDU835X-MIB::pdu835XPowerTable'
All available Channel Interfaces.
pdu835XPowerEntry row .1.3.6.1.4.1.28507.52.1.5.1.2.1
An entry containing management information
applicable to a particular Power Channel.
Column Syntax OID
Index of Power Channel entries
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.28507.52.1.5.1.2.1.1
0 = data not active, 1 = data valid
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.28507.52.1.5.1.2.1.2
Absolute Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.3
Active Power
WSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.52.1.5.1.2.1.4
Actual Curent on Power Channel.
mASNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.5
Actual Voltage on Power Channel
VSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.6
Frequency of Power Channel
0.01 hzSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.7
Power Factor of Channel between
-1.0 and 1.00
0.001SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.52.1.5.1.2.1.8
Phase Angle between Voltage
and L Line Current between
-180.0 and 180.0
0.1 degreeSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.52.1.5.1.2.1.9
L Line Mean Apparent Power
VASNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.52.1.5.1.2.1.10
L Line Mean Reactive Power
VARSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.52.1.5.1.2.1.11
Absolute Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.12
Resettable Absolute Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.13
Resettable Absolute Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.14
Time in seconds since last Energy
Counter reset.
sSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.15
Forward Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.16
Forward Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.17
Resettable Forward Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.18
Resettable Forward Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.19
Reverse Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.20
Reverse Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.21
Resettable Reverse Active Energy counter.
WhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.22
Resettable Reverse Reactive Energy counter.
VARhSNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.1.2.1.23
.1.3.6.1.4.1.28507.52.1.5.3.2 · 1 row entry · 4 columns
Uses the gude variant from /opt/observium/mibs/gude.
Command help
Walk pdu835XPowerGroupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-PDU835X-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-PDU835X-MIB::pdu835XPowerGroupTable'
pdu835XEntry row .1.3.6.1.4.1.28507.52.1.5.3.2.1
An entry containing management information
applicable to a particular Power Group.
Entries may not exist on every PDU model.
Column Syntax OID
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.28507.52.1.5.3.2.1.1
Actual Residual Current. Entry may not exist on models
that support not this type of measurement.
mASNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.3.2.1.2
Actual Current of the neutral wire. Entry may not exist
on models that support not this type of measurement.
mASNMPv2-SMIUnsigned32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.28507.52.1.5.3.2.1.3
Shows if the external Measurement Box is connected.
Enumeration
Enumerated Values:
0disconnected
1connected
.1.3.6.1.4.1.28507.52.1.5.3.2.1.4
.1.3.6.1.4.1.28507.52.1.6.1 · 1 row entry · 4 columns
Uses the gude variant from /opt/observium/mibs/gude.
Command help
Walk pdu835XSensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-PDU835X-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-PDU835X-MIB::pdu835XSensorTable'
pdu835XSensorEntry row .1.3.6.1.4.1.28507.52.1.6.1.1
Column Syntax OID
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.28507.52.1.6.1.1.1
actual temperature, a value of -9999 indicates
that data is not available
0.1 degree CelsiusSNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.52.1.6.1.1.2
actual humidity, a value of -9999 indicates
that data is not available
0.1 percent humiditySNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.28507.52.1.6.1.1.3
logical state of input sensor
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.28507.52.1.6.1.1.4