GUDEADS-PDU8306-MIB

Monitored by Observium
        
    
Observium actively monitors this MIB
Observium uses this MIB in discovery or polling workflows on applicable devices.
Counters Sensors
Explore Observium network monitoring
Source file
GUDEADS-PDU8306-MIB
Last revised
Identity
gudeads
Base OID
1.3.6.1.4.1.28507
Imported Objects
SNMPv2-CONF NOTIFICATION-GROUP (no object page) OBJECT-GROUP (no object page)
SNMPv2-SMI enterprises Integer32 MODULE-IDENTITY (no object page) NOTIFICATION-TYPE (no object page) OBJECT-TYPE (no object page) Unsigned32
Net-SNMP examples using the gude MIB directory Show commands

These commands use the standard Observium installation path and load the selected MIB variant before the RFC and Net-SNMP directories.

Translate the module identity
/usr/bin/snmptranslate -Pud -Ir -On -m 'GUDEADS-PDU8306-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'GUDEADS-PDU8306-MIB::gudeads'
Walk the MIB subtree
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-PDU8306-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-PDU8306-MIB::gudeads'
How SNMP, Net-SNMP, MIB paths, and variants work
Objects (45)
6 directly used by Observium
gudeads.1.3.6.1.4.1.28507
.1.3.6.1.4.1.28507.44
.1.3.6.1.4.1.28507.44.0
.1.3.6.1.4.1.28507.44.1
.1.3.6.1.4.1.28507.44.1.1
.1.3.6.1.4.1.28507.44.1.1.1
Integer32.1.3.6.1.4.1.28507.44.1.1.1.1
pdu8306TrapIPTable.1.3.6.1.4.1.28507.44.1.1.1.2
pdu8306TrapIPEntry.1.3.6.1.4.1.28507.44.1.1.1.2.1
pdu8306TrapIPIndexInteger32.1.3.6.1.4.1.28507.44.1.1.1.2.1.1
OctetString.1.3.6.1.4.1.28507.44.1.1.1.2.1.2
.1.3.6.1.4.1.28507.44.1.2
.1.3.6.1.4.1.28507.44.1.3
.1.3.6.1.4.1.28507.44.1.4
.1.3.6.1.4.1.28507.44.1.5
.1.3.6.1.4.1.28507.44.1.5.1
pdu8306ActivePowerChanUnsigned32.1.3.6.1.4.1.28507.44.1.5.1.1
pdu8306PowerTable.1.3.6.1.4.1.28507.44.1.5.1.2
pdu8306PowerEntry.1.3.6.1.4.1.28507.44.1.5.1.2.1
pdu8306PowerIndexInteger32.1.3.6.1.4.1.28507.44.1.5.1.2.1.1
pdu8306PowerApparentVASNMPv2-SMIInteger32.1.3.6.1.4.1.28507.44.1.5.1.2.1.10
pdu8306PowerReactiveVARSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.44.1.5.1.2.1.11
pdu8306EnergyReactiveVARhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.44.1.5.1.2.1.12
pdu8306EnergyActiveResettableWhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.44.1.5.1.2.1.13
pdu8306EnergyReactiveResettableVARhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.44.1.5.1.2.1.14
pdu8306ResetTimesSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.44.1.5.1.2.1.15
pdu8306ChanStatusInteger32.1.3.6.1.4.1.28507.44.1.5.1.2.1.2
pdu8306AbsEnergyActiveOBS ✓WhSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.44.1.5.1.2.1.3
pdu8306PowerActiveOBS ✓WSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.44.1.5.1.2.1.4
pdu8306CurrentOBS ✓mASNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.44.1.5.1.2.1.5
pdu8306VoltageOBS ✓VSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.44.1.5.1.2.1.6
pdu8306FrequencyOBS ✓0.01 hzSNMPv2-SMIUnsigned32.1.3.6.1.4.1.28507.44.1.5.1.2.1.7
pdu8306PowerFactorOBS ✓0.001SNMPv2-SMIInteger32.1.3.6.1.4.1.28507.44.1.5.1.2.1.8
pdu8306Pangle0.1 degreeSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.44.1.5.1.2.1.9
pdu8306MeasurementBoxConnectedEnumeration.1.3.6.1.4.1.28507.44.1.5.12
.1.3.6.1.4.1.28507.44.1.6
pdu8306SensorTable.1.3.6.1.4.1.28507.44.1.6.1
pdu8306SensorEntry.1.3.6.1.4.1.28507.44.1.6.1.1
pdu8306SensorIndexInteger32.1.3.6.1.4.1.28507.44.1.6.1.1.1
pdu8306TempSensor0.1 degree CelsiusSNMPv2-SMIInteger32.1.3.6.1.4.1.28507.44.1.6.1.1.2
pdu8306HygroSensor0.1 percent humiditySNMPv2-SMIInteger32.1.3.6.1.4.1.28507.44.1.6.1.1.3
pdu8306InputSensorEnumeration.1.3.6.1.4.1.28507.44.1.6.1.1.4
.1.3.6.1.4.1.28507.44.2
.1.3.6.1.4.1.28507.44.2.1
.1.3.6.1.4.1.28507.44.2.2
Dependencies (2) 2 direct Show tree and compile order Hide dependency details

Each imported module is resolved in the importing module's source directory first, then through the normal default-variant rules.

Dependency tree
Dependency-first compile order
  1. SNMPv2-SMIrfc
  2. SNMPv2-CONFrfc
  3. GUDEADS-PDU8306-MIBgudeselected
Notifications / Traps (3)
NameOIDDescription
.1.3.6.1.4.1.28507.44.0.1
temperature limits exceeded
.1.3.6.1.4.1.28507.44.0.2
hygro limits exceeded
.1.3.6.1.4.1.28507.44.0.3
Signals a change of the connection to the
external Measurement Box.