GUDEADS-EPC8X-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
3
Rows
3
Columns
13
epc8TrapIPTable
table.1.3.6.1.4.1.28507.1.1.1.2
·
1 row entry
·
3 columns
Uses the gude variant from
Command help
/opt/observium/mibs/gude.
Walk epc8TrapIPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-EPC8X-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-EPC8X-MIB::epc8TrapIPTable'
list of all Trap receiver
an entry containing management
informations regarding the list of trap
receivers
informations regarding the list of trap
receivers
Indexes
| Column | Syntax | OID |
|---|---|---|
| epc8TrapIPIndexA unique value, greater than zero, for each receiver slot. | Integer32 Constraints: range: 1-8 | .1.3.6.1.4.1.28507.1.1.1.2.1.1 |
| epc8TrapIPAddrIP Address specifying one Trap receiver slot. A value of '00000000'H disables this slot. | SNMPv2-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.28507.1.1.1.2.1.2 |
| epc8TrapIPPortIP Port specifying one Trap receiver slot. A value of 0 disables this slot. | Integer32r/w Constraints: range: 0-1024 | .1.3.6.1.4.1.28507.1.1.1.2.1.3 |
epc8portTable
table.1.3.6.1.4.1.28507.1.1.2.2
·
1 row entry
·
7 columns
Uses the gude variant from
Command help
/opt/observium/mibs/gude.
Walk epc8portTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-EPC8X-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-EPC8X-MIB::epc8portTable'
list of all EPC Powerports
An entry containing management information applicable to a
particular powerport.
particular powerport.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
| epc8PortIndexA unique value, greater than zero, for each PowerPort. | Integer32 Constraints: range: 1-8 | .1.3.6.1.4.1.28507.1.1.2.2.1.1 | ||||||
| epc8PortNameA textual string containing name of a PowerPort. | OctetString Constraints: range: 0-15 | .1.3.6.1.4.1.28507.1.1.2.2.1.2 | ||||||
| epc8PortStatecurrent state a PowerPort | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.28507.1.1.2.2.1.3 | ||||||
| epc8PortSwitchCountThe total number of switch actions ocurred on a PowerPort. Does not count switch commands which will not switch the ralay state, so just real relay switches are displayed here. | SNMPv2-SMICounter32 Type Constraints: range: 0..4294967295 | .1.3.6.1.4.1.28507.1.1.2.2.1.4 | ||||||
| epc8PortStartupModeset Mode of startup sequence (off, on , remember last state) | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.28507.1.1.2.2.1.5 | ||||||
| epc8PortStartupDelayDelay in sec for startup action | secondsSNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.28507.1.1.2.2.1.6 | ||||||
| epc8PortRepowerTimeDelay in sec for repower port after switching off | secondsInteger32r/w Constraints: range: 0-65535 | .1.3.6.1.4.1.28507.1.1.2.2.1.7 |
epc8SensorTable
table.1.3.6.1.4.1.28507.1.1.3.2
·
1 row entry
·
3 columns
Uses the gude variant from
Command help
/opt/observium/mibs/gude.
Walk epc8SensorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GUDEADS-EPC8X-MIB' -M '/opt/observium/mibs/gude:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GUDEADS-EPC8X-MIB::epc8SensorTable'
Indexes
| Column | Syntax | OID |
|---|---|---|
| epc8SensorIndex | Integer32 Constraints: range: 1-2 | .1.3.6.1.4.1.28507.1.1.3.2.1.1 |
| epc8TempSensoractual temperature, a value of -9999 indicates that data is not available | 10th of degree CelsiusSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.28507.1.1.3.2.1.2 |
| epc8HygroSensoractual humidity, a value of -9999 indicates that data is not available | 10th of percentage humiditySNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.28507.1.1.3.2.1.3 |