GESINGLEUPS-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
7
Rows
7
Columns
30
upsInputGenTable
table.1.3.6.1.4.1.818.1.1.10.3.3
·
1 row entry
·
7 columns
Uses the ge variant from
Command help
/opt/observium/mibs/ge.
Walk upsInputGenTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GESINGLEUPS-MIB' -M '/opt/observium/mibs/ge:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GESINGLEUPS-MIB::upsInputGenTable'
A list of input table entries. The number of entries is given by the value of upsInputNumLines.(*)
An entry containing information applicable to a
particular input line.(*)
particular input line.(*)
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The input line identifier.(*)
|
PositiveInteger32 Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.818.1.1.10.3.3.1.1 |
|
The present input frequency.(*)
|
0.1 HertzNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.3.3.1.2 |
|
The magnitude of the present input voltage.(*)
|
RMS VoltsNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.3.3.1.3 |
|
The magnitude of the present input current.(*)
|
0.1 RMS AmpNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.3.3.1.4 |
|
The magnitude of the present input true power.(*)
|
WattsNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.3.3.1.5 |
|
The lowest magnitude of the input voltage since last read out.
|
RMS VoltsNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.3.3.1.6 |
|
The highest magnitude of the input voltage since last read out.
|
RMS VoltsNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.3.3.1.7 |
upsOutputGenTable
table.1.3.6.1.4.1.818.1.1.10.4.4
·
1 row entry
·
8 columns
Uses the ge variant from
Command help
/opt/observium/mibs/ge.
Walk upsOutputGenTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GESINGLEUPS-MIB' -M '/opt/observium/mibs/ge:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GESINGLEUPS-MIB::upsOutputGenTable'
A list of output table entries. The number of entries is given by the value of upsOutputNumLines.(*)
An entry containing information applicable to a
particular output line.(*)
particular output line.(*)
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The output line identifier.(*)
|
PositiveInteger32 Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.818.1.1.10.4.4.1.1 |
|
The present output voltage.(*)
|
RMS VoltsNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.4.4.1.2 |
|
The present output current.(*)
|
0.1 RMS AmpNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.4.4.1.3 |
|
The present output true power.(*)
|
WattsNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.4.4.1.4 |
|
The percentage of the UPS power capacity presently
being used on this output line, i.e., the greater of the percent load of true power capacity and the percent load of VA.(*) |
percentInteger32 Constraints: range: 0-200 |
.1.3.6.1.4.1.818.1.1.10.4.4.1.5 |
|
The present output power factor.
The returned value correspond to the cosf of the load. A positive value indicate an inductive load; a negative value indicate a capacitive load; value 1 indicate a resistive load. If… |
0.01 cos phiInteger32 Constraints: range: -99-100 |
.1.3.6.1.4.1.818.1.1.10.4.4.1.6 |
|
The present output peak current.(*)
|
AmpsSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.818.1.1.10.4.4.1.7 |
|
In a parallel system ideally all the UPS are requested to
contribute to the load with the same amount of current, i.e. with no current share. The current share occurs when an UPS exchanges some current with another UP… |
AmpsSNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.818.1.1.10.4.4.1.8 |
upsBypassGenTable
table.1.3.6.1.4.1.818.1.1.10.5.3
·
1 row entry
·
4 columns
Uses the ge variant from
Command help
/opt/observium/mibs/ge.
Walk upsBypassGenTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GESINGLEUPS-MIB' -M '/opt/observium/mibs/ge:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GESINGLEUPS-MIB::upsBypassGenTable'
A list of bypass table entries. The number of entries is given by the value of upsBypassNumLines.(*)
An entry containing information applicable to a
particular bypass input.(*)
particular bypass input.(*)
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The bypass line identifier.(*)
|
PositiveInteger32 Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.818.1.1.10.5.3.1.1 |
|
The present bypass voltage.(*)
|
RMS VoltsNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.5.3.1.2 |
|
The present bypass current.(*)
|
0.1 RMS AmpNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.5.3.1.3 |
|
The present true power conveyed by the bypass.(*)
|
WattsNonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.5.3.1.4 |
upsAlarmGenTable
table.1.3.6.1.4.1.818.1.1.10.6.2
·
1 row entry
·
3 columns
Uses the ge variant from
Command help
/opt/observium/mibs/ge.
Walk upsAlarmGenTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GESINGLEUPS-MIB' -M '/opt/observium/mibs/ge:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GESINGLEUPS-MIB::upsAlarmGenTable'
A list of alarm table entries. The table contains
zero, one, or many rows at any moment, depending upon
the number of alarm conditions in effect. The table
is initially empty at agent startup. The agent
creates a row in the table each time a condition is
detected and deletes that row when that condition no
longer pertains. The agent creates the first row with
upsAlarmId equal to 1, and increments the value of
upsAlarmId each time a new row is created, wrapping to
the first free value greater than or equal to 1 when
the maximum value of upsAlarmId would otherwise be
exceeded. Consequently, after multiple operations,
the table may become sparse, e.g., containing entries
for rows 95, 100, 101, and 203 and the entries should
not be assumed to be in chronological order because
upsAlarmId might have wrapped.
Alarms are named by an AutonomousType (OBJECT
IDENTIFIER), upsAlarmDescr, to allow a single table to
reflect well known alarms plus alarms defined by a
particular implementation, i.e., as documented in the
private enterprise MIB definition for the device. No
two rows will have the same value of upsAlarmDescr,
since alarms define conditions. In order to meet this
requirement, care should be taken in the definition of
alarm conditions to insure that a system cannot enter
the same condition multiple times simultaneously.
The number of rows in the table at any given time is
reflected by the value of upsAlarmsPresent.(*)
An entry containing information applicable to a
particular alarm.(*)
particular alarm.(*)
Indexes
| Column | Syntax | OID |
|---|---|---|
|
A unique identifier for an alarm condition. This
value must remain constant.(*) |
PositiveInteger32 Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.818.1.1.10.6.2.1.1 |
|
A reference to an alarm description object. The
object referenced should not be accessible, but rather be used to provide a unique description of the alarm condition.(*) |
SNMPv2-TCAutonomousType Description: Represents an independently extensible type identification value. It may, for example, indicate a particular sub-tree with further MIB definitions, or define a particular type of protocol or hardware. |
.1.3.6.1.4.1.818.1.1.10.6.2.1.2 |
|
The value of sysUpTime when the alarm condition was
detected. If the alarm condition was detected at the time of agent startup and presumably existed before agent startup, the value of upsAlarmTime shall equal 0.(*) |
SNMPv2-TCTimeStamp Based On: SNMPv2-SMITimeTicks Description: The value of the sysUpTime object at which a specific occurrence happened. The specific occurrence must be defined in the description of any object defined using this type. If sysUpTime is reset t… |
.1.3.6.1.4.1.818.1.1.10.6.2.1.3 |
upsReceptacleGenTable
table.1.3.6.1.4.1.818.1.1.10.8.7
·
1 row entry
·
2 columns
Uses the ge variant from
Command help
/opt/observium/mibs/ge.
Walk upsReceptacleGenTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GESINGLEUPS-MIB' -M '/opt/observium/mibs/ge:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GESINGLEUPS-MIB::upsReceptacleGenTable'
A list of receptacle table entries. The number of entries is given by the value of upsReceptacleNum.
An entry containing information applicable to a
particular receptacle.
particular receptacle.
Indexes
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
|
The receptacle line identifier.
|
PositiveInteger32 Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.818.1.1.10.8.7.1.1 |
||||
|
The present state of the receptacle. Setting this
object to 'on' will cause the receptacle to be turned on. Setting this object to 'off' will turn the receptacle off. If the receptacle is already in the desired state n… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.818.1.1.10.8.7.1.2 |
upsEventGenTable
table.1.3.6.1.4.1.818.1.1.10.10.6
·
1 row entry
·
4 columns
Uses the ge variant from
Command help
/opt/observium/mibs/ge.
Walk upsEventGenTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GESINGLEUPS-MIB' -M '/opt/observium/mibs/ge:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GESINGLEUPS-MIB::upsEventGenTable'
A list of event table entries. The number of entries is always
10, and the value of upsEventTableSize gives the number of valid
entries from the begging of the table. Invalid entries return 0.
To prevent problems with simultaneous queries from several agents,
these values MUST be accessed using several PDUs in the
same SNMP message (<number> is (1..10)):
PDU-SET upsSetStartingTimeStamp <time>
PDU-SET upsEventGetNext <number>
PDU-GET upsEventTableSize
PDU-GET upsEventCode,upsEventStatus,upsEventTime 1
PDU-GET upsEventCode,upsEventStatus,upsEventTime 2
..
PDU-GET upsEventCode,upsEventStatus,upsEventTime <number>
The table is read up to requested number of events and the
management software afterwards decides which entries are
valid, as indicated by the upsEventTableSize.
An entry containing information applicable to a
particular event.
particular event.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The event line identifier.
|
PositiveInteger32 Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.818.1.1.10.10.6.1.1 |
|
The event code in numerical format.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.818.1.1.10.10.6.1.2 |
|
The status of the UPS at the moment that the event was generated.
The format is specified at the 'upsStatus' command. If the UPS is not able to deliver status information, then SNMPNOSUCHNAME is returned. |
NonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.10.6.1.3 |
|
The timestamp of the moment the event was generated.
|
NonNegativeInteger32 Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.818.1.1.10.10.6.1.4 |
upsParameterGenTable
table.1.3.6.1.4.1.818.1.1.10.10.11
·
1 row entry
·
2 columns
Uses the ge variant from
Command help
/opt/observium/mibs/ge.
Walk upsParameterGenTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'GESINGLEUPS-MIB' -M '/opt/observium/mibs/ge:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'GESINGLEUPS-MIB::upsParameterGenTable'
A list of parameter entries. The number of entries is always
16, and the value of upsParameterTableSize gives the number of valid
entries from the begging of the table. Invalid entries return 0.
To prevent problems with simultaneous queries from several agents,
these values MUST be accessed using several PDUs in the
same SNMP message (<number> is (1..16)):
Read sequence:
PDU-SET upsSetStartingAddress <addr>
PDU-SET upsParametersRead <number>
PDU-GET upsParameterTableSize
PDU-GET upsParameterValue 1
PDU-GET upsParameterValue 2
..
PDU-GET upsParameterValue <number>
The table is read up to requested number of events and the
management software afterwards decides which entries are
valid, as indicated by the upsParameterTableSize.
Write sequence:
PDU-SET upsSetStartingAddress <addr>
PDU-SET upsParameterValue 1
PDU-SET upsParameterValue 2
..
PDU-SET upsParameterValue <number>
PDU-SET upsParametersWrite <number>
An entry containing information applicable to a
particular parameter.
particular parameter.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
The parameter line identifier.
|
PositiveInteger32 Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.818.1.1.10.10.11.1.1 |
|
The parameter value in numerical format.
|
SNMPv2-SMIInteger32r/w Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.818.1.1.10.10.11.1.2 |