ETA-RCI10-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
4
Rows
4
Columns
124
fusesATable
table.1.3.6.1.4.1.44086.4.1.10.1.10
·
1 row entry
·
26 columns
Uses the eta variant from
Command help
/opt/observium/mibs/eta.
Walk fusesATable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ETA-RCI10-MIB' -M '/opt/observium/mibs/eta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ETA-RCI10-MIB::fusesATable'
Indexes
| Column | Syntax | OID |
|---|---|---|
| indexAFuse index | Integer32 Constraints: range: 1-20 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.1 |
| availableAStatus of fuse: 0=no fuse, 1=fuse available | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.2 |
| deviceTypeAType number of the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.3 |
| serialASerial number of the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.4 |
| hwVersionAHardware version number of the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.5 |
| swVersionASoftware version number of the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.6 |
| nominalCurrentANominal current of the fuse in milliampere | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.7 |
| errNoSysParANo systemparameter available fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.8 |
| errCrcParamAParameter CRC fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.9 |
| errCrcProgAProgram memory CRC fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.10 |
| errIntMemAInternal memory fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.11 |
| errControllerAController fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.12 |
| errWatchdogAWatchdog reset fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.13 |
| voltageAPower supply voltage in millivolt | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.14 |
| temperatureACurrent temperature of the fuse in millivolt | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.15 |
| loadOutputAOutput status of the fuse: 0=output off, 1=output on | Integer32r/w Constraints: range: 0-1 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.16 |
| statusShortAShort is detected by this fuse: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.17 |
| statusOverloadAOverload status: 0=no overload, 1=overload | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.18 |
| statusUvltAUndervoltage status: 0=no undervoltage, 1=undervoltage | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.19 |
| statusOvltAOvervoltage status: 0=no overvoltage, 1=overvoltage | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.20 |
| statusOtmpAOvertemperature status: 0=no overtemperature, 1=overtemperature | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.21 |
| statusNoVccANo VCC status: 0=no VCC, 1=VCC ok | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.22 |
| loadACurrent in milliampere which flows throuth the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.23 |
| labelALabel given for this fuse | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.24 |
| nominalVoltageAPolarity and nominal voltage of the fuse in volt. E.g.: -48 | OctetString Constraints: range: 0-9 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.25 |
| multiEsxAMultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.1.10.1.26 |
fusesBTable
table.1.3.6.1.4.1.44086.4.1.10.2.10
·
1 row entry
·
26 columns
Uses the eta variant from
Command help
/opt/observium/mibs/eta.
Walk fusesBTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ETA-RCI10-MIB' -M '/opt/observium/mibs/eta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ETA-RCI10-MIB::fusesBTable'
Indexes
| Column | Syntax | OID |
|---|---|---|
| indexBFuse index | Integer32 Constraints: range: 11-20 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.1 |
| availableBStatus of fuse: 0=no fuse, 1=fuse available | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.2 |
| deviceTypeBType number of the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.3 |
| serialBSerial number of the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.4 |
| hwVersionBHardware version number of the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.5 |
| swVersionBSoftware version number of the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.6 |
| nominalCurrentBNominal current of the fuse in milliampere | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.7 |
| errNoSysParBNo systemparameter available fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.8 |
| errCrcParamBParameter CRC fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.9 |
| errCrcProgBProgram memory CRC fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.10 |
| errIntMemBInternal memory fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.11 |
| errControllerBController fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.12 |
| errWatchdogBWatchdog reset fault: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.13 |
| voltageBPower supply voltage in millivolt | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.14 |
| temperatureBCurrent temperature of the fuse in millivolt | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.15 |
| loadOutputBOutput status of the fuse: 0=output off, 1=output on | Integer32r/w Constraints: range: 0-1 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.16 |
| statusShortBShort is detected by this fuse: 0=no fault, 1=fault | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.17 |
| statusOverloadBOverload status: 0=no overload, 1=overload | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.18 |
| statusUvltBUndervoltage status: 0=no undervoltage, 1=undervoltage | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.19 |
| statusOvltBOvervoltage status: 0=no overvoltage, 1=overvoltage | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.20 |
| statusOtmpBOvertemperature status: 0=no overtemperature, 1=overtemperature | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.21 |
| statusNoVccBNo VCC status: 0=no VCC, 1=VCC ok | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.22 |
| loadBLoad current in milliampere which flows throuth the fuse | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.23 |
| labelBLabel given for this fuse | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.24 |
| nominalVoltageBPolarity and nominal voltage of the fuse in volt. E.g.: -48 | OctetString Constraints: range: 0-9 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.25 |
| multiEsxBMultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.10.2.10.1.26 |
eaATable
table.1.3.6.1.4.1.44086.4.1.20.1.1
·
1 row entry
·
36 columns
Uses the eta variant from
Command help
/opt/observium/mibs/eta.
Walk eaATable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ETA-RCI10-MIB' -M '/opt/observium/mibs/eta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ETA-RCI10-MIB::eaATable'
| Column | Syntax | OID |
|---|---|---|
| eaIndexADevice index (slot number) | Integer32 Constraints: range: 1-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.1 |
| eaAvailableAStatus of the device: 0=no EAI device, 1=EEAI device available | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.2 |
| eaDeviceTypeAType number of the device | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.3 |
| eaSerialASerial number of the device | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.4 |
| eaHwVersionAHardware version number of the device | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.5 |
| eaSwVersionASoftware version number of the device | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.6 |
| eaOutput1AStatus of the relay output1: 0=output off, 1=output on (contact to normaly close is closed) | Integer32r/w Constraints: range: 0-1 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.7 |
| eaOutput2AStatus of the relay output2: 0=output off, 1=output on (contact to normaly close is closed) | Integer32r/w Constraints: range: 0-1 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.8 |
| eaInput1AStatus digital input1: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.9 |
| eaInput2AStatus digital input2: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.10 |
| eaInput3AStatus digital input3: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.11 |
| eaInput4AStatus digital input4: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.12 |
| eaInput5AStatus digital input5: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.13 |
| eaInput6AStatus digital input6: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.14 |
| eaInput7AStatus digital input7: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.15 |
| eaInput8AStatus digital input8: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.16 |
| eaAnalogInputAAnalog current input in mA | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.17 |
| eaLabelOutput1ALabel for output1 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.18 |
| eaLabelOutput2ALabel for output2 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.19 |
| eaLabelInput1ALabel for input1 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.20 |
| eaLabelInput2ALabel for input2 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.21 |
| eaLabelInput3ALabel for input3 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.22 |
| eaLabelInput4ALabel for input4 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.23 |
| eaLabelInput5ALabel for input5 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.24 |
| eaLabelInput6ALabel for input6 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.25 |
| eaLabelInput7ALabel for input7 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.26 |
| eaLabelInput8ALabel for input8 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.27 |
| eaLabelAnalogInputALabel for the analog input of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.28 |
| eaSignallingGroupOutput1ASignalling function for output1. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this slot | OctetStringr/w Constraints: range: 20-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.29 |
| eaSignallingActiveOutput1AStatus of signalling function for output1: 0=not active, 1=active | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.30 |
| eaSignallingGroupOutput2ASignalling function for output2. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this slot | OctetStringr/w Constraints: range: 20-20 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.31 |
| eaSignallingActiveOutput2AStatus of signalling function for output2: 0=not active, 1=active | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.32 |
| eaLogicFunctionOutput1ALogic function for output1. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>' | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.33 |
| eaLogicFunctionActiveOutput1AStatus of logic function for output1: 0=not active, 1=active | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.34 |
| eaLogicFunctionOutput2ALogic function for output2. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>' | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.35 |
| eaLogicFunctionActiveOutput2AStatus of logic function for output2: 0=not active, 1=active | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.1.1.1.36 |
eaBTable
table.1.3.6.1.4.1.44086.4.1.20.2.1
·
1 row entry
·
36 columns
Uses the eta variant from
Command help
/opt/observium/mibs/eta.
Walk eaBTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ETA-RCI10-MIB' -M '/opt/observium/mibs/eta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ETA-RCI10-MIB::eaBTable'
| Column | Syntax | OID |
|---|---|---|
| eaIndexBDevice index (slot number) | Integer32 Constraints: range: 1-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.1 |
| eaAvailableBStatus of the device: 0=no EAI device, 1=EEAI device available | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.2 |
| eaDeviceTypeBType number of the device | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.3 |
| eaSerialBSerial number of the device | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.4 |
| eaHwVersionBHardware version number of the device | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.5 |
| eaSwVersionBSoftware version number of the device | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.6 |
| eaOutput1BStatus of the relay output1: 0=output off, 1=output on (contact to normaly close is closed) | Integer32r/w Constraints: range: 0-1 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.7 |
| eaOutput2BStatus of the relay output2: 0=output off, 1=output on (contact to normaly close is closed) | Integer32r/w Constraints: range: 0-1 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.8 |
| eaInput1BStatus digital input1: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.9 |
| eaInput2BStatus digital input2: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.10 |
| eaInput3BStatus digital input3: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.11 |
| eaInput4BStatus digital input4: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.12 |
| eaInput5BStatus digital input5: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.13 |
| eaInput6BStatus digital input6: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.14 |
| eaInput7BStatus digital input7: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.15 |
| eaInput8BStatus digital input8: 0=low, 1=high | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.16 |
| eaAnalogInputBAnalog current input in mA | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.17 |
| eaLabelOutput1BLabel for output1 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.18 |
| eaLabelOutput2BLabel for output2 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.19 |
| eaLabelInput1BLabel for input1 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.20 |
| eaLabelInput2BLabel for input2 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.21 |
| eaLabelInput3BLabel for input3 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.22 |
| eaLabelInput4BLabel for input4 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.23 |
| eaLabelInput5BLabel for input5 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.24 |
| eaLabelInput6BLabel for input6 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.25 |
| eaLabelInput7BLabel for input7 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.26 |
| eaLabelInput8BLabel for input8 of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.27 |
| eaLabelAnalogInputBLabel for the analog input of this EAI device | OctetStringr/w Constraints: range: 0-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.28 |
| eaSignallingGroupOutput1BSignalling function for output1. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this slot | OctetStringr/w Constraints: range: 20-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.29 |
| eaSignallingActiveOutput1BStatus of signalling function for output1: 0=not active, 1=active | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.30 |
| eaSignallingGroupOutput2BSignalling function for output2. Syntax: 20 (for 20 slots) characters '0' or '1'. '0'= signalling not active for this slot; '0'= signalling is active for this slot | OctetStringr/w Constraints: range: 20-20 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.31 |
| eaSignallingActiveOutput2BStatus of signalling function for output2: 0=not active, 1=active | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.32 |
| eaLogicFunctionOutput1BLogic function for output1. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>' | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.33 |
| eaLogicFunctionActiveOutput1BStatus of logic function for output1: 0=not active, 1=active | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.34 |
| eaLogicFunctionOutput2BLogic function for output2. Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation; Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>' | OctetStringr/w Constraints: range: 0-40 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.35 |
| eaLogicFunctionActiveOutput2BStatus of logic function for output2: 0=not active, 1=active | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.44086.4.1.20.2.1.1.36 |