ETA-RCI10-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
4
Rows
4
Columns
124

fusesATable

table
.1.3.6.1.4.1.44086.4.1.10.1.10 · 1 row entry · 26 columns
Uses the eta variant from /opt/observium/mibs/eta.
Command help
Walk fusesATable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ETA-RCI10-MIB' -M '/opt/observium/mibs/eta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ETA-RCI10-MIB::fusesATable'
fusesAEntry row .1.3.6.1.4.1.44086.4.1.10.1.10.1
Indexes
Column Syntax OID
Fuse index
Integer32
Constraints:
range: 1-20
.1.3.6.1.4.1.44086.4.1.10.1.10.1.1
Status of fuse: 0=no fuse, 1=fuse available
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.2
Type number of the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.3
Serial number of the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.4
Hardware version number of the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.5
Software version number of the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.6
Nominal current of the fuse in milliampere
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.7
No systemparameter available fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.8
Parameter CRC fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.9
Program memory CRC fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.10
Internal memory fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.11
Controller fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.12
Watchdog reset fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.13
Power supply voltage in millivolt
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.14
Current temperature of the fuse in millivolt
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.15
Output status of the fuse: 0=output off, 1=output on
Integer32r/w
Constraints:
range: 0-1
.1.3.6.1.4.1.44086.4.1.10.1.10.1.16
Short is detected by this fuse: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.17
Overload status: 0=no overload, 1=overload
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.18
Undervoltage status: 0=no undervoltage, 1=undervoltage
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.19
Overvoltage status: 0=no overvoltage, 1=overvoltage
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.20
Overtemperature status: 0=no overtemperature, 1=overtemperature
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.21
No VCC status: 0=no VCC, 1=VCC ok
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.22
Current in milliampere which flows throuth the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.23
Label given for this fuse
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.10.1.10.1.24
Polarity and nominal voltage of the fuse in volt. E.g.: -48
OctetString
Constraints:
range: 0-9
.1.3.6.1.4.1.44086.4.1.10.1.10.1.25
MultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.1.10.1.26

fusesBTable

table
.1.3.6.1.4.1.44086.4.1.10.2.10 · 1 row entry · 26 columns
Uses the eta variant from /opt/observium/mibs/eta.
Command help
Walk fusesBTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ETA-RCI10-MIB' -M '/opt/observium/mibs/eta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ETA-RCI10-MIB::fusesBTable'
fusesBEntry row .1.3.6.1.4.1.44086.4.1.10.2.10.1
Indexes
Column Syntax OID
Fuse index
Integer32
Constraints:
range: 11-20
.1.3.6.1.4.1.44086.4.1.10.2.10.1.1
Status of fuse: 0=no fuse, 1=fuse available
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.2
Type number of the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.3
Serial number of the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.4
Hardware version number of the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.5
Software version number of the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.6
Nominal current of the fuse in milliampere
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.7
No systemparameter available fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.8
Parameter CRC fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.9
Program memory CRC fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.10
Internal memory fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.11
Controller fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.12
Watchdog reset fault: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.13
Power supply voltage in millivolt
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.14
Current temperature of the fuse in millivolt
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.15
Output status of the fuse: 0=output off, 1=output on
Integer32r/w
Constraints:
range: 0-1
.1.3.6.1.4.1.44086.4.1.10.2.10.1.16
Short is detected by this fuse: 0=no fault, 1=fault
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.17
Overload status: 0=no overload, 1=overload
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.18
Undervoltage status: 0=no undervoltage, 1=undervoltage
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.19
Overvoltage status: 0=no overvoltage, 1=overvoltage
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.20
Overtemperature status: 0=no overtemperature, 1=overtemperature
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.21
No VCC status: 0=no VCC, 1=VCC ok
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.22
Load current in milliampere which flows throuth the fuse
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.23
Label given for this fuse
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.10.2.10.1.24
Polarity and nominal voltage of the fuse in volt. E.g.: -48
OctetString
Constraints:
range: 0-9
.1.3.6.1.4.1.44086.4.1.10.2.10.1.25
MultiEsx: Fuses are connected in parallel to protect higher nominal loads: 0=not connected, 1=connected to a lower slot index, 2=connected as first
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.10.2.10.1.26

eaATable

table
.1.3.6.1.4.1.44086.4.1.20.1.1 · 1 row entry · 36 columns
Uses the eta variant from /opt/observium/mibs/eta.
Command help
Walk eaATable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ETA-RCI10-MIB' -M '/opt/observium/mibs/eta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ETA-RCI10-MIB::eaATable'
eaAEntry row .1.3.6.1.4.1.44086.4.1.20.1.1.1
Indexes
Column Syntax OID
Device index (slot number)
Integer32
Constraints:
range: 1-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.1
Status of the device: 0=no EAI device, 1=EEAI device available
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.2
Type number of the device
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.3
Serial number of the device
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.4
Hardware version number of the device
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.5
Software version number of the device
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.6
Status of the relay output1: 0=output off, 1=output on (contact to normaly close is closed)
Integer32r/w
Constraints:
range: 0-1
.1.3.6.1.4.1.44086.4.1.20.1.1.1.7
Status of the relay output2: 0=output off, 1=output on (contact to normaly close is closed)
Integer32r/w
Constraints:
range: 0-1
.1.3.6.1.4.1.44086.4.1.20.1.1.1.8
Status digital input1: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.9
Status digital input2: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.10
Status digital input3: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.11
Status digital input4: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.12
Status digital input5: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.13
Status digital input6: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.14
Status digital input7: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.15
Status digital input8: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.16
Analog current input in mA
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.17
Label for output1 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.18
Label for output2 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.19
Label for input1 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.20
Label for input2 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.21
Label for input3 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.22
Label for input4 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.23
Label for input5 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.24
Label for input6 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.25
Label for input7 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.26
Label for input8 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.27
Label for the analog input of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.28
Signalling function for output1.
Syntax: 20 (for 20 slots) characters '0' or '1'.
'0'= signalling not active for this slot; '0'= signalling is active for this slot
OctetStringr/w
Constraints:
range: 20-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.29
Status of signalling function for output1: 0=not active, 1=active
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.30
Signalling function for output2.
Syntax: 20 (for 20 slots) characters '0' or '1'.
'0'= signalling not active for this slot; '0'= signalling is active for this slot
OctetStringr/w
Constraints:
range: 20-20
.1.3.6.1.4.1.44086.4.1.20.1.1.1.31
Status of signalling function for output2: 0=not active, 1=active
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.32
Logic function for output1.
Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation;
Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>'
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.44086.4.1.20.1.1.1.33
Status of logic function for output1: 0=not active, 1=active
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.34
Logic function for output2.
Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation;
Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>'
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.44086.4.1.20.1.1.1.35
Status of logic function for output2: 0=not active, 1=active
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.1.1.1.36

eaBTable

table
.1.3.6.1.4.1.44086.4.1.20.2.1 · 1 row entry · 36 columns
Uses the eta variant from /opt/observium/mibs/eta.
Command help
Walk eaBTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ETA-RCI10-MIB' -M '/opt/observium/mibs/eta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ETA-RCI10-MIB::eaBTable'
eaBEntry row .1.3.6.1.4.1.44086.4.1.20.2.1.1
Indexes
Column Syntax OID
Device index (slot number)
Integer32
Constraints:
range: 1-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.1
Status of the device: 0=no EAI device, 1=EEAI device available
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.2
Type number of the device
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.3
Serial number of the device
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.4
Hardware version number of the device
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.5
Software version number of the device
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.6
Status of the relay output1: 0=output off, 1=output on (contact to normaly close is closed)
Integer32r/w
Constraints:
range: 0-1
.1.3.6.1.4.1.44086.4.1.20.2.1.1.7
Status of the relay output2: 0=output off, 1=output on (contact to normaly close is closed)
Integer32r/w
Constraints:
range: 0-1
.1.3.6.1.4.1.44086.4.1.20.2.1.1.8
Status digital input1: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.9
Status digital input2: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.10
Status digital input3: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.11
Status digital input4: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.12
Status digital input5: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.13
Status digital input6: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.14
Status digital input7: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.15
Status digital input8: 0=low, 1=high
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.16
Analog current input in mA
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.17
Label for output1 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.18
Label for output2 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.19
Label for input1 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.20
Label for input2 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.21
Label for input3 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.22
Label for input4 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.23
Label for input5 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.24
Label for input6 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.25
Label for input7 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.26
Label for input8 of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.27
Label for the analog input of this EAI device
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.28
Signalling function for output1.
Syntax: 20 (for 20 slots) characters '0' or '1'.
'0'= signalling not active for this slot; '0'= signalling is active for this slot
OctetStringr/w
Constraints:
range: 20-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.29
Status of signalling function for output1: 0=not active, 1=active
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.30
Signalling function for output2.
Syntax: 20 (for 20 slots) characters '0' or '1'.
'0'= signalling not active for this slot; '0'= signalling is active for this slot
OctetStringr/w
Constraints:
range: 20-20
.1.3.6.1.4.1.44086.4.1.20.2.1.1.31
Status of signalling function for output2: 0=not active, 1=active
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.32
Logic function for output1.
Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation;
Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>'
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.44086.4.1.20.2.1.1.33
Status of logic function for output1: 0=not active, 1=active
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.34
Logic function for output2.
Length: 40 characters. Syntax: Logic connections '*'=AND, '+'=OR, '!'=Negation;
Signals: EAI digital input 'eai<slot address>in<input number>', ESX state 'esx<slot address><state>'
OctetStringr/w
Constraints:
range: 0-40
.1.3.6.1.4.1.44086.4.1.20.2.1.1.35
Status of logic function for output2: 0=not active, 1=active
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.44086.4.1.20.2.1.1.36