EPPC-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
11
Rows
11
Columns
77
.1.3.6.1.4.1.935.10.1.1.2.16
·
1 row entry
·
5 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsESystemInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsESystemInputTable'
A list of input table entries. The number of entries is given by the value of upsESystemInputNumPhase.
An entry containing information applicable to a particular input line.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
upsESystemInputPhasemandatory
The number of the phase. Serves as index for input table
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.1 |
|
upsESystemInputFrequencymandatory
The measured input frquency from the UPS meters in 0.1Hz.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.2 |
|
upsESystemInputVoltagemandatory
The measured input voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.3 |
|
upsESystemInputCurrentmandatory
The measured input mandatory from the UPS meters in 0.1 amps.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.4 |
|
upsESystemInputWattsmandatory
The measured input real power in watts.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.16.1.5 |
.1.3.6.1.4.1.935.10.1.1.2.18
·
1 row entry
·
7 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsESystemOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsESystemOutputTable'
A list of output table entries. The number of entries is given by the value of upsESystemOutputNumPhase.
An entry containing information applicable to a particular line.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
upsESystemOutputPhasemandatory
The number of the phase. Serves as index for output table
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.1 |
|
upsESystemOutputFrequencymandatory
The measured output frequency from the UPS meters in 0.1Hz.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.2 |
|
upsESystemOutputVoltagemandatory
The measured output voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.3 |
|
upsESystemOutputCurrentmandatory
The measured output mandatory from the UPS meters in 0.1 amps.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.4 |
|
upsESystemOutputWattsmandatory
The measured output real power in watts.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.5 |
|
upsESystemOutputVAmandatory
The measured output real complex power in VA.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.6 |
|
upsESystemOutputLoadmandatory
The UPS output load in percent of rated capacity.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.18.1.7 |
.1.3.6.1.4.1.935.10.1.1.2.20
·
1 row entry
·
5 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsESystemBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsESystemBypassTable'
A list of bypass table entries. The number of entries is given by the value of upsESystemBypassNumPhase.
An entry containing information applicable to a particular line.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
upsESystemBypassPhasemandatory
The number of the phase. Serves as index for bypass table
|
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.1 |
|
upsESystemBypassFrequencymandatory
The measured bypass frequency from the UPS meters in 0.1 Hz.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.2 |
|
upsESystemBypassVoltagemandatory
The measured bypass voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.3 |
|
upsESystemBypassCurrentmandatory
The measured bypass mandatory from the UPS meters in 0.1 amps
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.4 |
|
upsESystemBypassWattsmandatory
The measured bypass input real power in watts.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.2.20.1.5 |
.1.3.6.1.4.1.935.10.1.1.3.12
·
1 row entry
·
8 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsEChargerModulesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEChargerModulesTable'
A list of charger modules entries. The number of entries is given by the value of upsEchargerModulesNum.
An entry containing information applicable to a particular charger module.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
chargerModulesNummandatory
The number of charger modules. Serves as index for charger module table
|
Integer32 Constraints: range: 1-32 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.1 |
||||||||||||||
|
chargerModulesAddressmandatory
Charger Modules' address.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.2 |
||||||||||||||
|
positiveChargeVotlagemandatory
The measured positive charger voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.3 |
||||||||||||||
|
negativeChargeVoltagemandatory
The measured nepositive charger voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.4 |
||||||||||||||
|
positiveChargeCurrentmandatory
The measured positive charger mandatory from the UPS meters in in 0.1 amps.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.5 |
||||||||||||||
|
negativeChargeCurrentmandatory
The measured nepositive charger mandatory from the UPS meters in 0.1 amps.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.6 |
||||||||||||||
|
chargerModulesTemperaturemandatory
The measured charger temperature from the UPS meters in 0.1 degree.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.3.12.1.7 |
||||||||||||||
|
chargerModulesModemandatory
The working mode of charger modules.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.3.12.1.8 |
.1.3.6.1.4.1.935.10.1.1.4.2
·
1 row entry
·
22 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsEModulesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEModulesTable'
A list of UPS modules entries. The number of entries is given by the value of upsEModulesNum.
An entry containing information applicable to a particular upsE module.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsEModulesNummandatory
The number of UPS modules. Serves as index for UPS module table
|
Integer32 Constraints: range: 1-32 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.1 |
||||||||||||||||||||||||||
|
upsEModuleAddressmandatory
the address of UPS modules.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.2 |
||||||||||||||||||||||||||
|
upsEModulePositiveBusVoltmandatory
The measured positive upsE module voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.3 |
||||||||||||||||||||||||||
|
upsEModuleNegativeBusVoltmandatory
The measured nepositive upsE module voltage from the UPS meters in 0.1 volts
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.4 |
||||||||||||||||||||||||||
|
upsEModuleTemperaturemandatory
The measured upsE module temperature from the UPS meters in 0.1 degree.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.5 |
||||||||||||||||||||||||||
|
upsEModuleWorkingModemandatory
The working mode of UPS modules.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.4.2.1.6 |
||||||||||||||||||||||||||
|
upsEModuleOutputCurrentRmandatory
The measured upsE module output mandatory from the UPS meters in 0.1 A.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.7 |
||||||||||||||||||||||||||
|
upsEModuleOutputWattRmandatory
The measured upsE module output watts from the UPS meters in watts.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.8 |
||||||||||||||||||||||||||
|
upsEModuleOutputLoadRmandatory
The output load of UPS modules in %.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.9 |
||||||||||||||||||||||||||
|
upsEModuleWarningCodemandatory
The warning code of ups modules.Please refer the warning table of 'QU,XX' for details.
|
OctetString Constraints: range: 0-15 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.10 |
||||||||||||||||||||||||||
|
upsEModuleFaultCodemandatory
The fault code of ups modules.Please refer command 'QU,XX' for details.
|
OctetString Constraints: range: 0-15 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.11 |
||||||||||||||||||||||||||
|
upsEModuleTrapStatemandatory
the values indicate the unrestored traps.
For example, after AC fail, so the value of upsETrapState should be '1'. And then the AC restore, the value of upsEModuleTrapState should change to empty. |
OctetString Constraints: range: 0-127 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.12 |
||||||||||||||||||||||||||
|
upsEModuleConfigOutputVAmandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.13 |
||||||||||||||||||||||||||
|
upsEModuleOutputCurrentSmandatory
The measured upsE module output mandatory from the UPS meters in 0.1 A.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.14 |
||||||||||||||||||||||||||
|
upsEModuleOutputCurrentTmandatory
The measured upsE module output mandatory from the UPS meters in 0.1 A.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.15 |
||||||||||||||||||||||||||
|
upsEModuleOutputWattSmandatory
The measured upsE module output watts from the UPS meters in watts.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.16 |
||||||||||||||||||||||||||
|
upsEModuleOutputWattTmandatory
The measured upsE module output watts from the UPS meters in watts.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.17 |
||||||||||||||||||||||||||
|
upsEModuleOutputLoadSmandatory
The output load of UPS modules in %.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.18 |
||||||||||||||||||||||||||
|
upsEModuleOutputLoadTmandatory
The output load of UPS modules in %.
|
Integer32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.19 |
||||||||||||||||||||||||||
|
upsEModuleOutputVARmandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.20 |
||||||||||||||||||||||||||
|
upsEModuleOutputVASmandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.21 |
||||||||||||||||||||||||||
|
upsEModuleOutputVATmandatory
The magnitude of the nominal Volt-Amp rating presented in VA.
|
UPS-MIBNonNegativeInteger Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.4.2.1.22 |
.1.3.6.1.4.1.935.10.1.1.6.4
·
1 row entry
·
4 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsEEnvironmentContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEEnvironmentContactTable'
A list of contacts table entries. The number of entries is given by the value of upsEEnvironmentContactsNum
An entry containing information applicable to a particular contact
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
upsEEnvironmentContactIndexmandatory
The number of environment contacts. Serves as index for environment contact table
|
UPS-MIBPositiveInteger Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.6.4.1.1 |
||||||||
|
upsEEnvironmentContactTypemandatory
operation type
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.6.4.1.2 |
||||||||
|
upsEEnvironmentContactStatemandatory
The mandatory status.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.6.4.1.3 |
||||||||
|
upsEEnvironmentContactDescriptionmandatory
Description of environment contact.
|
OctetStringr/w Constraints: range: 0-31 |
.1.3.6.1.4.1.935.10.1.1.6.4.1.4 |
.1.3.6.1.4.1.935.10.1.1.7.6
·
1 row entry
·
6 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsEBatteryTestScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEBatteryTestScheduleTable'
This table describes the schedule for automatically battery test.
An entry containing information applicable to schedule test.
Indexes
| Column | Syntax | OID | ||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsEBatteryTestScheduleIndexmandatory
The index of battery test scheduled.
|
UPS-MIBPositiveInteger Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.7.6.1.1 |
||||||||||||||||||
|
upsEBatteryTestScheduleDaymandatory
The weekday or specaial day on which the UPS should start battery test.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.7.6.1.2 |
||||||||||||||||||
|
upsEBatteryTestScheduleTimemandatory
The time that the battery test will be initiated in hh:mm format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.7.6.1.3 |
||||||||||||||||||
|
upsEBatteryTestScheduleTypemandatory
The type of battery test.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.7.6.1.5 |
||||||||||||||||||
|
upsEBatteryTestScheduleTestWithTimemandatory
The battery time of setting time test in seconds.
|
UPS-MIBNonNegativeIntegerr/w Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.7.6.1.6 |
||||||||||||||||||
|
upsEBatteryTestScheduleSpecialDaymandatory
The special day that the battery test will be initiated in dd/mm/yyyy format.
|
OctetStringr/w Constraints: range: 10-10 |
.1.3.6.1.4.1.935.10.1.1.7.6.1.7 |
.1.3.6.1.4.1.935.10.1.1.8.4
·
1 row entry
·
4 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsEShutdownEventsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEShutdownEventsTable'
This table describes the parametes for shutdown process when shutdown event occurs
An entry containing information applicable to a particular shutdown
event line
event line
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsEShutdownEventmandatory
The shutdown event identification
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.8.4.1.1 |
||||||||||||||||||||||||
|
upsEShutdownEventActionmandatory
Status of the corresponding shutdown Event.
When set to disable(), shutdown process will not start when corresponding event occured. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.8.4.1.2 |
||||||||||||||||||||||||
|
upsEShutdownwarningPeriodTimemandatory
The Delay in seconds after the occurance of the curresponding shutdown
event, and warning message should be popped in this period. |
UPS-MIBNonNegativeIntegerr/w Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.8.4.1.3 |
||||||||||||||||||||||||
|
upsEShutdownWarningPeriodIntervalmandatory
The frequency of sending warning messages to the connected
clients when the curresponding shutdown event occurs. The value is in units of seconds. |
UPS-MIBNonNegativeIntegerr/w Type Constraints: range: 0..2147483647 |
.1.3.6.1.4.1.935.10.1.1.8.4.1.4 |
.1.3.6.1.4.1.935.10.1.1.8.5
·
1 row entry
·
5 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsEControlWeeklyScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEControlWeeklyScheduleTable'
The table to schedule shutting down the ups by weekly
An entry containing information applicable to a particular line
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
upsEControlWeeklyScheduleIndexmandatory
the index of schedule events.
|
UPS-MIBPositiveInteger Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.8.5.1.1 |
||||||||||||||||
|
upsEWeeklyScheduleShutdownDaymandatory
the weekday on which upsE shoud shutdown
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.8.5.1.2 |
||||||||||||||||
|
upsEWeeklyScheduleShutdownTimemandatory
The time that the process of shutting down the UPS will be initiated
in hh:mm format. |
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.8.5.1.3 |
||||||||||||||||
|
upsEWeeklyScheduleRestartDaymandatory
the weekday on which the UPS should restart.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.8.5.1.4 |
||||||||||||||||
|
upsEWeeklyScheduleRestartTimemandatory
The time the UPS will restart in hh:mm format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.8.5.1.5 |
.1.3.6.1.4.1.935.10.1.1.8.6
·
1 row entry
·
5 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsEControlSpecialDayScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEControlSpecialDayScheduleTable'
The table to schedule shutting down the ups.
An entry containing information applicable to a particular line.
| Column | Syntax | OID |
|---|---|---|
|
upsEControlSpecialDayScheduleIndexmandatory
The index of special day schedule.
|
UPS-MIBPositiveInteger Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.1 |
|
upsESpecialDayScheduleShutdownDaymandatory
The special day on which UPS should shutdown with the format
of DD/MM/YYYY. |
OctetStringr/w Constraints: range: 10-10 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.2 |
|
upsESpecialDayScheduleShutdownTimemandatory
The time that the process of shutting down the UPS will be initiated
in hh:mm format. |
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.3 |
|
upsESpecialDayScheduleRestartDaymandatory
The special day on which the UPS should restart with the format
of DD/MM/YYYY. |
OctetStringr/w Constraints: range: 10-10 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.4 |
|
upsESpecialDayScheduleRestartTimemandatory
The time the UPS will restart in hh:mm format.
|
OctetStringr/w Constraints: range: 5-5 |
.1.3.6.1.4.1.935.10.1.1.8.6.1.5 |
.1.3.6.1.4.1.935.10.1.1.9.1
·
1 row entry
·
6 columns
Uses the powerwalker variant from
Command help
/opt/observium/mibs/powerwalker.
Walk upsETrapsReceiversTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsETrapsReceiversTable'
This table list the managers'IP to send traps to.
An entry containing information applicable to a particular input line.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
upsETrapsReceiversIndexmandatory
The index to a trap receiver entry
|
UPS-MIBPositiveInteger Type Constraints: range: 1..2147483647 |
.1.3.6.1.4.1.935.10.1.1.9.1.1.1 |
||||||
|
upsETrapsReceiverAddressmandatory
The IP address of the manager to send a trap to.
|
OctetStringr/w Constraints: range: 0-45 |
.1.3.6.1.4.1.935.10.1.1.9.1.1.2 |
||||||
|
upsETrapReceiverCommunityStringmandatory
The community name to use in the trap when
sent to the manager. |
OctetStringr/w Constraints: range: 0-32 |
.1.3.6.1.4.1.935.10.1.1.9.1.1.3 |
||||||
|
upsETrapTypemandatory
The type of trap to be received by the manager.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.9.1.1.4 |
||||||
|
upsETrapsSeverityLevelmandatory
The severity level of traps to be received by this manager.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.935.10.1.1.9.1.1.5 |
||||||
|
upsETrapReceiverDescriptionmandatory
Description of trap receivers
|
OctetStringr/w Constraints: range: 0-63 |
.1.3.6.1.4.1.935.10.1.1.9.1.1.6 |