EPPC-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
11
Rows
11
Columns
77

upsESystemInputTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.2.16 · 1 row entry · 5 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsESystemInputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsESystemInputTable'
A list of input table entries. The number of entries is given by the 
value of upsESystemInputNumPhase.
upsESystemInputEntry row .1.3.6.1.4.1.935.10.1.1.2.16.1
An entry containing information applicable to a particular input line.
Column Syntax OID
The number of the phase. Serves as index for input table
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.935.10.1.1.2.16.1.1
The measured input frquency from the UPS meters in 0.1Hz.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.16.1.2
The measured input voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.16.1.3
The measured input mandatory from the UPS meters in 0.1 amps.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.16.1.4
The measured input real power in watts.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.16.1.5

upsESystemOutputTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.2.18 · 1 row entry · 7 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsESystemOutputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsESystemOutputTable'
A list of output table entries. The number of entries is given 
by the value of upsESystemOutputNumPhase.
upsESystemOutputEntry row .1.3.6.1.4.1.935.10.1.1.2.18.1
An entry containing information applicable to a particular line.
Column Syntax OID
The number of the phase. Serves as index for output table
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.935.10.1.1.2.18.1.1
The measured output frequency from the UPS meters in 0.1Hz.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.2
The measured output voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.3
The measured output mandatory from the UPS meters in 0.1 amps.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.4
The measured output real power in watts.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.5
The measured output real complex power in VA.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.6
The UPS output load in percent of rated capacity.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.18.1.7

upsESystemBypassTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.2.20 · 1 row entry · 5 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsESystemBypassTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsESystemBypassTable'
A list of bypass table entries. The number of entries is given by the
value of upsESystemBypassNumPhase.
upsESystemBypassEntry row .1.3.6.1.4.1.935.10.1.1.2.20.1
An entry containing information applicable to a particular line.
Column Syntax OID
The number of the phase. Serves as index for bypass table
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.935.10.1.1.2.20.1.1
The measured bypass frequency from the UPS meters in 0.1 Hz.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.20.1.2
The measured bypass voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.20.1.3
The measured bypass mandatory from the UPS meters in 0.1 amps
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.20.1.4
The measured bypass input real power in watts.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.2.20.1.5

upsEChargerModulesTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.3.12 · 1 row entry · 8 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsEChargerModulesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEChargerModulesTable'
A list of charger modules entries. The number of entries is given 
by the value of upsEchargerModulesNum.
upsEChargerModulesEntry row .1.3.6.1.4.1.935.10.1.1.3.12.1
An entry containing information applicable to a particular charger module.
Column Syntax OID
The number of charger modules. Serves as index for charger module table
Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.935.10.1.1.3.12.1.1
Charger Modules' address.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.2
The measured positive charger voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.3
The measured nepositive charger voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.4
The measured positive charger mandatory from the UPS meters in in 0.1 amps.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.5
The measured nepositive charger mandatory from the UPS meters in 0.1 amps.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.6
The measured charger temperature from the UPS meters in 0.1 degree.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.3.12.1.7
The working mode of charger modules.
Enumeration
Enumerated Values:
1powerOn
2standyby
3fault
4shutdown
5running
6suicide
7unknown
.1.3.6.1.4.1.935.10.1.1.3.12.1.8

upsEModulesTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.4.2 · 1 row entry · 22 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsEModulesTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEModulesTable'
A list of UPS modules entries. The number of entries is 
given by the value of upsEModulesNum.
upsEModulesEntry row .1.3.6.1.4.1.935.10.1.1.4.2.1
An entry containing information applicable to a particular upsE module.
Indexes
Column Syntax OID
The number of UPS modules. Serves as index for UPS module table
Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.935.10.1.1.4.2.1.1
the address of UPS modules.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.2
The measured positive upsE module voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.3
The measured nepositive upsE module voltage from the UPS meters in 0.1 volts
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.4
The measured upsE module temperature from the UPS meters in 0.1 degree.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.5
The working mode of UPS modules.
Enumeration
Enumerated Values:
1power-on
2stand-by
3by-pass
4line
5battery
6battery-test
7fault
8converter
9eco
10shutdown
11on-booster
12on-reducer
13other
.1.3.6.1.4.1.935.10.1.1.4.2.1.6
The measured upsE module output mandatory from the UPS meters in 0.1 A.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.7
The measured upsE module output watts from the UPS meters in watts.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.8
The output load of UPS modules in %.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.9
The warning code of ups modules.Please refer the warning table of 'QU,XX' for details.
OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.935.10.1.1.4.2.1.10
The fault code of ups modules.Please refer command 'QU,XX' for details.
OctetString
Constraints:
range: 0-15
.1.3.6.1.4.1.935.10.1.1.4.2.1.11
the values indicate the unrestored traps.
For example, after AC fail, so the value of upsETrapState should be '1'.
And then the AC restore, the value of upsEModuleTrapState
should change to empty.
OctetString
Constraints:
range: 0-127
.1.3.6.1.4.1.935.10.1.1.4.2.1.12
The magnitude of the nominal Volt-Amp rating presented in VA.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.13
The measured upsE module output mandatory from the UPS meters in 0.1 A.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.14
The measured upsE module output mandatory from the UPS meters in 0.1 A.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.15
The measured upsE module output watts from the UPS meters in watts.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.16
The measured upsE module output watts from the UPS meters in watts.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.17
The output load of UPS modules in %.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.18
The output load of UPS modules in %.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.19
The magnitude of the nominal Volt-Amp rating presented in VA.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.20
The magnitude of the nominal Volt-Amp rating presented in VA.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.21
The magnitude of the nominal Volt-Amp rating presented in VA.
UPS-MIBNonNegativeInteger
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.4.2.1.22

upsEEnvironmentContactTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.6.4 · 1 row entry · 4 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsEEnvironmentContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEEnvironmentContactTable'
A list of contacts table entries. The number of entries is given by the
value of upsEEnvironmentContactsNum
upsEEnvironmentContactEntry row .1.3.6.1.4.1.935.10.1.1.6.4.1
An entry containing information applicable to a particular contact
Column Syntax OID
The number of environment contacts. Serves as index for environment contact table
UPS-MIBPositiveInteger
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.6.4.1.1
operation type
Enumerationr/w
Enumerated Values:
1normallyOpen
2normallyClosed
3notUsed
.1.3.6.1.4.1.935.10.1.1.6.4.1.2
The mandatory status.
Enumeration
Enumerated Values:
1open
2closed
3openWithNotice
4closedWithNotice
.1.3.6.1.4.1.935.10.1.1.6.4.1.3
Description of environment contact.
OctetStringr/w
Constraints:
range: 0-31
.1.3.6.1.4.1.935.10.1.1.6.4.1.4
.1.3.6.1.4.1.935.10.1.1.7.6 · 1 row entry · 6 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsEBatteryTestScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEBatteryTestScheduleTable'
This table describes the schedule for automatically battery
test.
upsEBatteryTestScheduleEntry row .1.3.6.1.4.1.935.10.1.1.7.6.1
An entry containing information applicable to schedule test.
Column Syntax OID
The index of battery test scheduled.
UPS-MIBPositiveInteger
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.7.6.1.1
The weekday or specaial day on which the UPS should start battery test.
Enumerationr/w
Enumerated Values:
1monday
2tuesday
3wednsday
4thusday
5friday
6saturday
7sunday
8specialday
9none
.1.3.6.1.4.1.935.10.1.1.7.6.1.2
The time that the battery test will be initiated in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.7.6.1.3
The type of battery test.
Enumerationr/w
Enumerated Values:
1none
2batteryTest10sec
3batteryTestUntilLow
4batteryTestWithTime
.1.3.6.1.4.1.935.10.1.1.7.6.1.5
The battery time of setting time test in seconds.
UPS-MIBNonNegativeIntegerr/w
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.7.6.1.6
The special day that the battery test will be initiated in dd/mm/yyyy format.
OctetStringr/w
Constraints:
range: 10-10
.1.3.6.1.4.1.935.10.1.1.7.6.1.7

upsEShutdownEventsTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.8.4 · 1 row entry · 4 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsEShutdownEventsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEShutdownEventsTable'
This table describes the parametes for shutdown process
when shutdown event occurs
upsEShutdownEventsEntry row .1.3.6.1.4.1.935.10.1.1.8.4.1
An entry containing information applicable to a particular shutdown
event line
Column Syntax OID
The shutdown event identification
Enumeration
Enumerated Values:
1acFail
2batteryLow
3upsEOverLoad
4upsEOverTemperature
5upsEWeeklySchedule
6upsESpecialSchedule
7environmentTemperatureOverThreshold
8environmentHumidityOverThreshold
9environmentContact1Alarm
10environmentContact2Alarm
11belowCapacityLimit
12belowRemainTimeLimit
.1.3.6.1.4.1.935.10.1.1.8.4.1.1
Status of the corresponding shutdown Event.
When set to disable(), shutdown process will not start when
corresponding event occured.
Enumerationr/w
Enumerated Values:
1disable
2warning
3shutdownClient
4shutdownUPS
.1.3.6.1.4.1.935.10.1.1.8.4.1.2
The Delay in seconds after the occurance of the curresponding shutdown
event, and warning message should be popped in this period.
UPS-MIBNonNegativeIntegerr/w
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.8.4.1.3
The frequency of sending warning messages to the connected
clients when the curresponding shutdown event occurs.
The value is in units of seconds.
UPS-MIBNonNegativeIntegerr/w
Type Constraints:
range: 0..2147483647
.1.3.6.1.4.1.935.10.1.1.8.4.1.4
.1.3.6.1.4.1.935.10.1.1.8.5 · 1 row entry · 5 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsEControlWeeklyScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEControlWeeklyScheduleTable'
The table to schedule shutting down the ups by weekly
upsEControlWeeklyScheduleEntry row .1.3.6.1.4.1.935.10.1.1.8.5.1
An entry containing information applicable to a particular line
Column Syntax OID
the index of schedule events.
UPS-MIBPositiveInteger
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.8.5.1.1
the weekday on which upsE shoud shutdown
Enumerationr/w
Enumerated Values:
1monday
2tuesday
3wednesday
4thursday
5friday
6saturday
7sunday
8none
.1.3.6.1.4.1.935.10.1.1.8.5.1.2
The time that the process of shutting down the UPS will be initiated
in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.8.5.1.3
the weekday on which the UPS should restart.
Enumerationr/w
Enumerated Values:
1monday
2tuesday
3wednesday
4thursday
5friday
6saturday
7sunday
8none
.1.3.6.1.4.1.935.10.1.1.8.5.1.4
The time the UPS will restart in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.8.5.1.5
.1.3.6.1.4.1.935.10.1.1.8.6 · 1 row entry · 5 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsEControlSpecialDayScheduleTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsEControlSpecialDayScheduleTable'
The table to schedule shutting down the ups.
upsEControlSpecialDayScheduleEntry row .1.3.6.1.4.1.935.10.1.1.8.6.1
An entry containing information applicable to a particular line.
Column Syntax OID
The index of special day schedule.
UPS-MIBPositiveInteger
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.8.6.1.1
The special day on which UPS should shutdown with the format
of DD/MM/YYYY.
OctetStringr/w
Constraints:
range: 10-10
.1.3.6.1.4.1.935.10.1.1.8.6.1.2
The time that the process of shutting down the UPS will be initiated
in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.8.6.1.3
The special day on which the UPS should restart with the format
of DD/MM/YYYY.
OctetStringr/w
Constraints:
range: 10-10
.1.3.6.1.4.1.935.10.1.1.8.6.1.4
The time the UPS will restart in hh:mm format.
OctetStringr/w
Constraints:
range: 5-5
.1.3.6.1.4.1.935.10.1.1.8.6.1.5

upsETrapsReceiversTable

table mandatory
.1.3.6.1.4.1.935.10.1.1.9.1 · 1 row entry · 6 columns
Uses the powerwalker variant from /opt/observium/mibs/powerwalker.
Command help
Walk upsETrapsReceiversTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EPPC-MIB' -M '/opt/observium/mibs/powerwalker:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EPPC-MIB::upsETrapsReceiversTable'
This table list the managers'IP to send traps to.
upsETrapsReceiversEntry row .1.3.6.1.4.1.935.10.1.1.9.1.1
An entry containing information applicable to a particular input line.
Column Syntax OID
The index to a trap receiver entry
UPS-MIBPositiveInteger
Type Constraints:
range: 1..2147483647
.1.3.6.1.4.1.935.10.1.1.9.1.1.1
The IP address of the manager to send a trap to.
OctetStringr/w
Constraints:
range: 0-45
.1.3.6.1.4.1.935.10.1.1.9.1.1.2
The community name to use in the trap when
sent to the manager.
OctetStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.935.10.1.1.9.1.1.3
upsETrapTypemandatory
The type of trap to be received by the manager.
Enumerationr/w
Enumerated Values:
1none
2rfc1628Trap
3eppcTrap
.1.3.6.1.4.1.935.10.1.1.9.1.1.4
The severity level of traps to be received by this manager.
Enumerationr/w
Enumerated Values:
1informational
2warning
3severe
.1.3.6.1.4.1.935.10.1.1.9.1.1.5
Description of trap receivers
OctetStringr/w
Constraints:
range: 0-63
.1.3.6.1.4.1.935.10.1.1.9.1.1.6