EATON-SENSOR-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
14
Rows
14
Columns
82
.1.3.6.1.4.1.534.6.8.1.1.2 · 1 row entry · 10 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk sensorIdentificationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::sensorIdentificationTable'
A list of sensor devices identification data.
The number of entries is given by sensorCount.
sensorIdentificationEntry row .1.3.6.1.4.1.534.6.8.1.1.2.1
An entry for a sensor device identification.
Indexes
Column Syntax OID
sensorIndexA unique value for each sensor device. Its value
ranges from 1 to sensorCount.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.534.6.8.1.1.2.1.1
sensorUuidA unique uuid value for each sensor device.OctetString.1.3.6.1.4.1.534.6.8.1.1.2.1.2
sensorConnectionTypeSensor connection type with the device that monitors it.ProbeConnectionType
Type Values:
0undefined
1internal
2wired
3wireless
.1.3.6.1.4.1.534.6.8.1.1.2.1.3
sensorAddressDepending of the connection implementation : Modbus Slave Id, BT Mac address, ...OctetString.1.3.6.1.4.1.534.6.8.1.1.2.1.4
sensorMonitoredByParent oid device where the sensor is connected to and monitored by.ObjectIdentifier.1.3.6.1.4.1.534.6.8.1.1.2.1.5
sensorManufacturerThe vendor name of the sensor device.OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.6
sensorModelThe model name of the sensor device.OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.7
sensorPartNumberThe catalog part number of the sensor device.OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.8
sensorSerialNumberThe serial number of the sensor device.OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.9
sensorFirmwareVersionThe firmware version of the sensor device.OctetString
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.2.1.10
.1.3.6.1.4.1.534.6.8.1.1.3 · 1 row entry · 5 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk sensorConfigurationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::sensorConfigurationTable'
A list of sensor devices configuration data.
The number of entries is given by sensorCount.
sensorConfigurationEntry row .1.3.6.1.4.1.534.6.8.1.1.3.1
An entry for a sensor device configuration.
Indexes
Column Syntax OID
sensorNameThe friendly name of the sensor device.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.3.1.1
sensorLocationThe location of the sensor device.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.1.3.1.2
sensorPositionThe Position by reference to the data center aisle.PositionTyper/w
Type Values:
0undefined
1other
2rackRear
3rackFront
4batteryRoom
.1.3.6.1.4.1.534.6.8.1.1.3.1.3
sensorElevationThe Elevation in the rack.ElevationTyper/w
Type Values:
0undefined
1other
2bottom
3middle
4top
.1.3.6.1.4.1.534.6.8.1.1.3.1.4
sensorUElevationThe elevation in the rack in count of U position from the bottom.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.3.1.5
.1.3.6.1.4.1.534.6.8.1.1.4 · 1 row entry · 6 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk sensorMonitoringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::sensorMonitoringTable'
A list of sensor devices monitoring data.
The number of entries is given by sensorCount.
sensorMonitoringEntry row .1.3.6.1.4.1.534.6.8.1.1.4.1
An entry for a sensor device monitoring.
Indexes
Column Syntax OID
sensorStatusIndicates how the sensor is communicating or not.CommunicationStatus
Type Values:
0unknown
2communicationOK
3communicationLost
.1.3.6.1.4.1.534.6.8.1.1.4.1.1
sensorStatusSinceUTC time in seconds since 1970/01/01 dating the sensor status last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.1.4.1.2
sensorTemperatureCountNumber of temperature probes managed by the sensor device.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.4.1.3
sensorHumidityCountNumber of humidity probes managed by the sensor device.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.4.1.4
sensorDigitalInputCountNumber of digital input probes managed by the sensor device.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.4.1.5
sensorAnalogInputCountNumber of analog input probes managed by the sensor device.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.1.4.1.6
.1.3.6.1.4.1.534.6.8.1.2.1 · 1 row entry · 3 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk temperatureIdentificationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::temperatureIdentificationTable'
A list of temperature probe measurements. the number of entries
is given by the temperature count.
temperatureIdentificationEntry row .1.3.6.1.4.1.534.6.8.1.2.1.1
An entry for a temperature probe identification.
Column Syntax OID
temperatureIndexA unique value for each temperature probe measurement. Its value
ranges from 1 to sensorTemperatureCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.8.1.2.1.1.1
temperatureUuidA unique uuid value for each temperature.OctetString.1.3.6.1.4.1.534.6.8.1.2.1.1.2
temperatureConnectionTypeProbe connection type with the sensor that monitors it.ProbeConnectionType
Type Values:
0undefined
1internal
2wired
3wireless
.1.3.6.1.4.1.534.6.8.1.2.1.1.3
.1.3.6.1.4.1.534.6.8.1.2.2 · 1 row entry · 10 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk temperatureConfigurationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::temperatureConfigurationTable'
A list of temperature probe configuration.  The number of entries is
given by sensorTemperatureCount.
temperatureConfigurationEntry row .1.3.6.1.4.1.534.6.8.1.2.2.1
An entry for a temperature probe configuration.
Column Syntax OID
temperatureNameThe friendly name of the sensor temperature probe.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.2.2.1.1
temperatureEnableConfigure the temperature acquired or not.
0:disabled, 1:enabled
EnableTyper/w
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.2.2.1.2
temperatureOffsetConfigure the offset (Minus or Plus) to be added to the acquired value
in order to correct the probe measurement error.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.3
temperatureAlarmEnableConfigure the temperature alarm depending on the thresholds evaluated or not.
0:disabled, 1:enabled
EnableTyper/w
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.2.2.1.4
temperatureThresholdLowWarningLow warning temperature threshold.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.5
temperatureThresholdLowCriticalLow critical temperature threshold.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.6
temperatureThresholdHighWarningHigh warning temperature threshold.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.7
temperatureThresholdHighCriticalHigh critical temperature threshold.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.8
temperatureThresholdHysteresisTemperature threshold hysteresis.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.2.1.9
temperatureAlarmGracePeriodThe grace period the alarm triggers after the acquired value crosses
a trigger value (in seconds).
Integer32r/w
Constraints:
range: 1-60
.1.3.6.1.4.1.534.6.8.1.2.2.1.10
.1.3.6.1.4.1.534.6.8.1.2.3 · 1 row entry · 5 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk temperatureMonitoringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::temperatureMonitoringTable'
A list of temperature probe monitoring.  The number of entries is
given by sensorTemperatureCount.
temperatureMonitoringEntry row .1.3.6.1.4.1.534.6.8.1.2.3.1
An entry for a temperature probe monitoring.
Column Syntax OID
temperatureAlarmAlarm set according to the realtime measure compared to the thresholds.AlarmType
Type Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.8.1.2.3.1.1
temperatureAlarmChangeSinceUTC time in seconds since 1970/01/01 dating the temperature alarm last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.2.3.1.2
temperatureValueRealtime measured value after correction with the offset.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.3.1.3
temperatureCommunicationStatusIndicates how the temperature probe is communicating or not.CommunicationStatus
Type Values:
0unknown
2communicationOK
3communicationLost
.1.3.6.1.4.1.534.6.8.1.2.3.1.4
temperatureCommunicationStatusSinceUTC time in seconds since 1970/01/01 dating the temperature communication status last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.2.3.1.5
.1.3.6.1.4.1.534.6.8.1.2.4 · 1 row entry · 5 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk temperatureMonitoringMinMaxTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::temperatureMonitoringMinMaxTable'
A list of temperature probe monitoring Min and Max.  The number of entries is
given by sensorTemperatureCount.
temperatureMonitoringMinMaxEntry row .1.3.6.1.4.1.534.6.8.1.2.4.1
An entry for a temperature probe monitoring Min and Max.
Column Syntax OID
temperatureMinValueMinimum value registered since the 1st connection of the sensor or the last reset.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.4.1.1
temperatureMinValueSinceUTC time in seconds since 1970/01/01 dating the temperature min value last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.2.4.1.2
temperatureMaxValueMaximum value registered since the 1st connection of the sensor or the last reset.
See temperatureUnit data for the units.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.2.4.1.3
temperatureMaxValueSinceUTC time in seconds since 1970/01/01 dating the temperature max value last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.2.4.1.4
temperatureResetMinMaxCommand that resets the min and max data with the current measure.
0:None, 1:Reset
ResetCommandTyper/w
Type Values:
0none
1reset
.1.3.6.1.4.1.534.6.8.1.2.4.1.5
.1.3.6.1.4.1.534.6.8.1.3.1 · 1 row entry · 3 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk humidityIdentificationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::humidityIdentificationTable'
A list of humidity probe measurements. the number of entries
is given by the humidity count.
humidityIdentificationEntry row .1.3.6.1.4.1.534.6.8.1.3.1.1
An entry for a humidity probe identification.
Column Syntax OID
humidityIndexA unique value for each humidity probe measurement. Its value
ranges from 1 to sensorhumidityCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.8.1.3.1.1.1
humidityUuidA unique uuid value for each humidity.OctetString.1.3.6.1.4.1.534.6.8.1.3.1.1.2
humidityConnectionTypeProbe connection type with the sensor that monitors it.ProbeConnectionType
Type Values:
0undefined
1internal
2wired
3wireless
.1.3.6.1.4.1.534.6.8.1.3.1.1.3
.1.3.6.1.4.1.534.6.8.1.3.2 · 1 row entry · 10 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk humidityConfigurationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::humidityConfigurationTable'
A list of humidity probe configuration.  The number of entries is
given by sensorhumidityCount.
humidityConfigurationEntry row .1.3.6.1.4.1.534.6.8.1.3.2.1
An entry for a humidity probe configuration.
Column Syntax OID
humidityNameThe friendly name of the sensor humidity probe.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.3.2.1.1
humidityEnableConfigure the humidity acquired or not.
0:disabled, 1:enabled
EnableTyper/w
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.3.2.1.2
humidityOffsetConfigure the offset (Minus or Plus) to be added to the acquired value
in order to correct the probe measurement error. in tenth of % units.
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.3
humidityAlarmEnableConfigure the humidity alarm depending on the thresholds evaluated or not.
0:disabled, 1:enabled
EnableTyper/w
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.3.2.1.4
humidityThresholdLowWarningLow warning humidity threshold in tenth of % units.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.5
humidityThresholdLowCriticalLow critical humidity threshold in tenth of % units.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.6
humidityThresholdHighWarningHigh warning humidity threshold in tenth of % units.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.7
humidityThresholdHighCriticalHigh critical humidity threshold in tenth of % units.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.8
humidityThresholdHysteresishumidity threshold hysteresis in tenth of % units.SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.2.1.9
humidityAlarmGracePeriodThe grace period the alarm triggers after the acquired value crosses
a trigger value (in seconds).
Integer32r/w
Constraints:
range: 1-60
.1.3.6.1.4.1.534.6.8.1.3.2.1.10
.1.3.6.1.4.1.534.6.8.1.3.3 · 1 row entry · 5 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk humidityMonitoringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::humidityMonitoringTable'
A list of humidity probe monitoring.  The number of entries is
given by sensorhumidityCount.
humidityMonitoringEntry row .1.3.6.1.4.1.534.6.8.1.3.3.1
An entry for a humidity probe monitoring.
Column Syntax OID
humidityAlarmAlarm set according to the realtime measure compared to the thresholds.AlarmType
Type Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.8.1.3.3.1.1
humidityAlarmChangeSinceUTC time in seconds since 1970/01/01 dating the humidity alarm last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.3.3.1.2
humidityValueRealtime measured value after correction with the offset. in tenth of % units.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.3.1.3
humidityCommunicationStatusIndicates how the humidity probe is communicating or not.CommunicationStatus
Type Values:
0unknown
2communicationOK
3communicationLost
.1.3.6.1.4.1.534.6.8.1.3.3.1.4
humidityCommunicationStatusSinceUTC time in seconds since 1970/01/01 dating the humidity communication status last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.3.3.1.5
.1.3.6.1.4.1.534.6.8.1.3.4 · 1 row entry · 5 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk humidityMonitoringMinMaxTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::humidityMonitoringMinMaxTable'
A list of humidity probe monitoring Min and Max.  The number of entries is
given by sensorhumidityCount.
humidityMonitoringMinMaxEntry row .1.3.6.1.4.1.534.6.8.1.3.4.1
An entry for a humidity probe monitoring Min and Max.
Column Syntax OID
humidityMinValueMinimum value registered since the 1st connection of the sensor or the last reset.
in tenth of % units.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.4.1.1
humidityMinValueSinceUTC time in seconds since 1970/01/01 dating the humidity min value last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.3.4.1.2
humidityMaxValueMaximum value registered since the 1st connection of the sensor or the last reset.
in tenth of % units.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.8.1.3.4.1.3
humidityMaxValueSinceUTC time in seconds since 1970/01/01 dating the humidity max value last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.3.4.1.4
humidityResetMinMaxCommand that resets the min and max data with the current measure.
0:None, 1:Reset
ResetCommandTyper/w
Type Values:
0none
1reset
.1.3.6.1.4.1.534.6.8.1.3.4.1.5
.1.3.6.1.4.1.534.6.8.1.4.1 · 1 row entry · 3 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk digitalInputIdentificationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::digitalInputIdentificationTable'
A list of digital input probe measurements.  The number of entries is
given by sensorDigitalInputCount.
digitalInputIdentificationEntry row .1.3.6.1.4.1.534.6.8.1.4.1.1
An entry for a digital input identification.
Column Syntax OID
digitalInputIndexA unique value for each digital input probe measurement. Its value
ranges from 1 to sensorDigitalInputCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.8.1.4.1.1.1
digitalInputUuidA unique uuid value for each digital Input.OctetString.1.3.6.1.4.1.534.6.8.1.4.1.1.2
digitalInputConnectionTypeProbe connection type with the sensor that monitors it.ProbeConnectionType
Type Values:
0undefined
1internal
2wired
3wireless
.1.3.6.1.4.1.534.6.8.1.4.1.1.3
.1.3.6.1.4.1.534.6.8.1.4.2 · 1 row entry · 6 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk digitalInputConfigurationTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::digitalInputConfigurationTable'
A list of digital input probe configuration.  The number of entries is
given by sensorDigitalInputCount.
digitalInputConfigurationEntry row .1.3.6.1.4.1.534.6.8.1.4.2.1
An entry for a digital input probe configuration.
Column Syntax OID
digitalInputNameThe friendly name of the digital input probe.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.8.1.4.2.1.1
digitalInputEnableConfigure the digital input acquired or not.
0:disabled, 1:enabled
EnableTyper/w
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.4.2.1.2
digitalInputPolarityConfigure the digitalInput polarity.
0 : Normally opened, 1 : Normally closed
PolarityTyper/w
Type Values:
0normallyOpened
1normallyClosed
.1.3.6.1.4.1.534.6.8.1.4.2.1.3
digitalInputAlarmEnableConfigure the digitalInput alarm depending on the polarity evaluated or not.
0:disabled, 1:enabled
EnableTyper/w
Type Values:
0disabled
1enabled
.1.3.6.1.4.1.534.6.8.1.4.2.1.4
digitalInputAlarmSeverityConfigure the alarm severity.AlarmSeverityTyper/w
Type Values:
1informational
2warning
3critical
.1.3.6.1.4.1.534.6.8.1.4.2.1.5
digitalInputAlarmGracePeriodThe delay the alarm triggers when the state change event occurs (in seconds).Integer32r/w
Constraints:
range: 1-60
.1.3.6.1.4.1.534.6.8.1.4.2.1.6
.1.3.6.1.4.1.534.6.8.1.4.3 · 1 row entry · 6 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk digitalInputMonitoringTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-SENSOR-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-SENSOR-MIB::digitalInputMonitoringTable'
A list of digital input probee monitoring.  The number of entries is
given by sensorDigitalInputCount.
digitalInputMonitoringEntry row .1.3.6.1.4.1.534.6.8.1.4.3.1
An entry for a digital Input probe.
Column Syntax OID
digitalInputAlarmAlarm set according to the polarity and alarm severity configuration.AlarmLevelType
Type Values:
0good
1informational
2warning
3critical
.1.3.6.1.4.1.534.6.8.1.4.3.1.1
digitalInputAlarmChangeSinceUTC time in seconds since 1970/01/01 dating the digital input alarm last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.4.3.1.2
digitalInputStateMeasure of the digital input after applying the polarity configured.
0 : Inactive, 1 : Active
StateType
Type Values:
0inactive
1active
.1.3.6.1.4.1.534.6.8.1.4.3.1.3
digitalInputStateSinceUTC time in seconds since 1970/01/01 dating the digital input state last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.4.3.1.4
digitalInputCommunicationStatusIndicates how the digital input is communicating or not.CommunicationStatus
Type Values:
0unknown
2communicationOK
3communicationLost
.1.3.6.1.4.1.534.6.8.1.4.3.1.5
digitalInputCommunicationStatusSinceUTC time in seconds since 1970/01/01 dating the digital input communication status last change.UnixTimeStamp.1.3.6.1.4.1.534.6.8.1.4.3.1.6