EATON-PXG-MIB

        The MIB module for objects and notifications supported by 
Eaton's Toolkit-enabled Power Xpert Gateways.
        
Copyright (C) Eaton Corporation (2006-2007).
    

Imported Objects

powerChainEATON-OIDS
entPhysicalNameENTITY-MIB
SnmpAdminStringSNMP-FRAMEWORK-MIB
MODULE-COMPLIANCE, OBJECT-GROUP, NOTIFICATION-GROUPSNMPv2-CONF
MODULE-IDENTITY, OBJECT-TYPE, NOTIFICATION-TYPE, Gauge32, Integer32SNMPv2-SMI
TimeStampSNMPv2-TC

Objects

pxgMIB .1.3.6.1.4.1.534.8.1
pxgNotifications .1.3.6.1.4.1.534.8.1.0
pxgMIBObjects .1.3.6.1.4.1.534.8.1.1
eventInfo .1.3.6.1.4.1.534.8.1.1.1
eventID .1.3.6.1.4.1.534.8.1.1.1.1
eventSequenceIndex .1.3.6.1.4.1.534.8.1.1.1.2
eventDescription
.1.3.6.1.4.1.534.8.1.1.1.3
eventValue
.1.3.6.1.4.1.534.8.1.1.1.4
alarms .1.3.6.1.4.1.534.8.1.1.2
numAlarmsPresent
.1.3.6.1.4.1.534.8.1.1.2.1
activeAlarmsTable .1.3.6.1.4.1.534.8.1.1.2.2
activeAlarmsEntry .1.3.6.1.4.1.534.8.1.1.2.2.1
alarmID .1.3.6.1.4.1.534.8.1.1.2.2.1.1
alarmSequenceIndex .1.3.6.1.4.1.534.8.1.1.2.2.1.2
alarmDescription
.1.3.6.1.4.1.534.8.1.1.2.2.1.3
alarmValue
.1.3.6.1.4.1.534.8.1.1.2.2.1.4
alarmLevel .1.3.6.1.4.1.534.8.1.1.2.2.1.5
alarmTime
.1.3.6.1.4.1.534.8.1.1.2.2.1.6
pxgConformance .1.3.6.1.4.1.534.8.1.2

Notifications/Traps

NameOIDDescription
powerChainCriticalAlarmEvent.1.3.6.1.4.1.534.8.1.0.1
A Critical Alarm has occurred in a Power Chain Device.
Alarm and source information are contained in the OBJECTS.
powerChainAlarmCleared.1.3.6.1.4.1.534.8.1.0.10
The condition that raised the Alarm or Event no longer exists;
the three types of Events have different outcomes:
1) A latching Alarm is still considered active and will need to be 
   Closed by a user Close Acknowledgement.
2) A non-latching Alarm is closed and its Alarm sequence completed.
3) An Event is closed and its Event sequence completed.
Alarm and source information are contained in the OBJECTS.
powerChainAlarmClosed.1.3.6.1.4.1.534.8.1.0.11
A user has Closed a Critical or Cautionary Alarm.
This Close Acknowledgement has 'closed' a latched Alarm and
completed its sequence.
Alarm and source information are contained in the OBJECTS.
powerChainAlarmUpdated.1.3.6.1.4.1.534.8.1.0.12
An update to the alarm entry at alarmID has occurred;
however, the alarmLevel has not changed due to this update.
This is normally seen with latching alarms when condition that caused
the alarm is removed or recurs before the alarm has been closed.
Alarm and source information are contained in the OBJECTS.
powerChainCautionaryAlarmEvent.1.3.6.1.4.1.534.8.1.0.2
A Cautionary Alarm has occurred in a Power Chain Device.
Alarm and source information are contained in the OBJECTS.
powerChainAlarmEventAcknowledged.1.3.6.1.4.1.534.8.1.0.3
A user has Acknowledged a Critical or Cautionary Alarm.
This does NOT clear or 'close' a latched Alarm.
Alarm and source information are contained in the OBJECTS.
powerChainEventCleared.1.3.6.1.4.1.534.8.1.0.4
The condition that raised the Alarm or Event no longer exists;
the three types of Events have different outcomes:
1) A latching Alarm is still considered active and will need to be 
   Closed by a user Close Acknowledgement.
2) A non-latching Alarm is closed and its Alarm sequence completed.
3) An Event is closed and its Event sequence completed.
Alarm and source information are contained in the OBJECTS.
powerChainEvent.1.3.6.1.4.1.534.8.1.0.5
A non-alarming Event has occurred in a Power Chain Device.
Event and source information are contained in the OBJECTS.
powerChainAlarmEventClosed.1.3.6.1.4.1.534.8.1.0.6
A user has Closed a Critical or Cautionary Alarm.
This Close Acknowledgement has 'closed' a latched Alarm and
completed its sequence.
Alarm and source information are contained in the OBJECTS.
powerChainCriticalAlarm.1.3.6.1.4.1.534.8.1.0.7
A Critical Alarm has occurred in a Power Chain Device.
Alarm and source information are contained in the OBJECTS.
powerChainCautionaryAlarm.1.3.6.1.4.1.534.8.1.0.8
A Cautionary Alarm has occurred in a Power Chain Device.
Alarm and source information are contained in the OBJECTS.
powerChainAlarmAcknowledged.1.3.6.1.4.1.534.8.1.0.9
A user has Acknowledged a Critical or Cautionary Alarm.
This does NOT clear or 'close' a latched Alarm.
Alarm and source information are contained in the OBJECTS.