EATON-EPDU-MIB Table View
Table-centric layout grouping table, row, and column objects.
Tables
23
Rows
23
Columns
170
unitTable
table.1.3.6.1.4.1.534.6.6.7.1.2
·
1 row entry
·
22 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk unitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::unitTable'
A list of units. In most cases this list will only contain one entry. However, some units have a 'strapping' feature which allow units to be daisy-chained together such that all of them can be accessed through the SNMP interface of the master. If strapping is enabled, the strapping indexes of the units that can be accessed will be listed in the unitsPresent object.
An entry for a PDU.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
For units that support 'strapping' functionality, this will be a unique
value for each unit. If units do not support 'strapping', this will always be '0'. |
Integer32 Constraints: range: 0-23 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.1 |
||||||||||||||
|
Name of the product.
|
OctetString Constraints: range: 1-127 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.2 |
||||||||||||||
|
Part number of the unit.
|
OctetString | .1.3.6.1.4.1.534.6.6.7.1.2.1.3 |
||||||||||||||
|
Serial number of the unit.
|
OctetString | .1.3.6.1.4.1.534.6.6.7.1.2.1.4 |
||||||||||||||
|
Firmware version.
|
OctetString | .1.3.6.1.4.1.534.6.6.7.1.2.1.5 |
||||||||||||||
|
Descriptive name for the unit.
|
OctetStringr/w Constraints: range: 1-63 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.6 |
||||||||||||||
|
Control the local LCD.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.7 |
||||||||||||||
|
Clock value. This could be from either a real-time clock (in which case
it is likely writeable) or from a time server via NTP (probably read-only). |
SNMPv2-TCDateAndTimer/w Type Constraints: range: 8range: 11Description: A date-time specification. field octets contents range ----- ------ -------- ----- 1 1-2 year* 0..65536 2 3 month … |
.1.3.6.1.4.1.534.6.6.7.1.2.1.8 |
||||||||||||||
|
Scale used to return temperature objects.
|
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.9 |
||||||||||||||
|
Technical capabilities of the PDU. Functionality is as follows:
Monitored (MI) - input and usually section/group monitoring. Advanced Monitored (AM) - input, section/group, and outlet monitoring. Switched (SW) - input … |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.10 |
||||||||||||||
|
Architecture of the ePDU electronic.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.11 |
||||||||||||||
|
Number of inputs on this ePDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.20 |
||||||||||||||
|
Number of groups on this ePDU. Groups include breakers, outlet sections,
and user-defined groups. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.21 |
||||||||||||||
|
Number of outlets on this ePDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.22 |
||||||||||||||
|
Max number of temperature measurements on this ePDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.23 |
||||||||||||||
|
Max number of humidity measurements on this ePDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.24 |
||||||||||||||
|
Max number of contact sensors on this ePDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.25 |
||||||||||||||
|
Status of the internal communication with the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.30 |
||||||||||||||
|
Status of the internal failure inside the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.31 |
||||||||||||||
|
Status of the external communication with a strapping unit.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.32 |
||||||||||||||
|
Username used to log into the PDU.
|
OctetString Constraints: range: 0-31 |
.1.3.6.1.4.1.534.6.6.7.1.2.1.40 |
||||||||||||||
|
Communications interface used to log into the PDU.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.1.2.1.41 |
unitControlTable
table.1.3.6.1.4.1.534.6.6.7.1.3
·
1 row entry
·
2 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk unitControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::unitControlTable'
A list of units that have controllable outlets.
An entry for a PDU which has controllable outlets.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
Unit-level outlet control command.
Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 : Cancel a pending unit-level Off command … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.1.3.1.2 |
|
Unit-level outlet control command.
Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value. 0-n : Time in seconds until the outlet Sequence On command is issue… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.1.3.1.3 |
inputTable
table.1.3.6.1.4.1.534.6.6.7.3.1
·
1 row entry
·
10 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputTable'
List of inputs to the PDU.
An entry for a particular input.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each input. Its value ranges from 1 to inputCount.
|
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.1 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Type of input - single phase, split phase, three phase delta, or three
phase wye. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.1.1.2 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Units are 0.1 Hz; divide by ten to get Hz.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.3 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Status of the measured input frequency relative to the nominal frequency and the admitted tolerance.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.1.1.4 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Number of input voltage measurements on this ePDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.5 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Number of input current measurements on this ePDU.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.6 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Number of rows in the inputPowerTable.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.7 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Identifies which plug is on the input.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.1.1.8 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
Color code of the input feed.
|
Unsigned32r/w Constraints: range: 0-16777215 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.9 |
||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|
A descriptive name for the input.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.3.1.1.10 |
inputVoltageTable
table.1.3.6.1.4.1.534.6.6.7.3.2
·
1 row entry
·
8 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputVoltageTable'
A list of input voltage measurements. The number of entries is given by inputVoltageCount.
An entry for a particular input voltage measurement.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each input voltage measurement. Its value ranges
from 1 to inputVoltageCount. |
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.1 |
||||||||||||||
|
Value indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.2.1.2 |
||||||||||||||
|
An input voltage measurement value. Units are millivolts.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.3 |
||||||||||||||
|
Status of the measured input voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.2.1.4 |
||||||||||||||
|
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.5 |
||||||||||||||
|
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.6 |
||||||||||||||
|
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.7 |
||||||||||||||
|
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.3.2.1.8 |
inputCurrentTable
table.1.3.6.1.4.1.534.6.6.7.3.3
·
1 row entry
·
12 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputCurrentTable'
A list of input current measurements. The number of entries is given by inputCurrentCount.
An entry for a particular input current measurement.
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each input current measurement. Its value ranges
from 1 to inputCurrentCount. |
Integer32 Constraints: range: 1-4 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.1 |
||||||||||
|
Which input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.3.1.2 |
||||||||||
|
Rated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are milliamps. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.3 |
||||||||||
|
An input current measurement value. Units are milliamps.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.4 |
||||||||||
|
Status of the measured input current relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.3.1.5 |
||||||||||
|
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.6 |
||||||||||
|
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.7 |
||||||||||
|
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.8 |
||||||||||
|
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.9 |
||||||||||
|
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.10 |
||||||||||
|
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.11 |
||||||||||
|
Alphanumeric physical name for the input.
|
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.3.3.1.12 |
inputPowerTable
table.1.3.6.1.4.1.534.6.6.7.3.4
·
1 row entry
·
8 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputPowerTable'
A list of input power measurements. The number of entries is given by inputPowerCount.
An entry for an input power measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each input power measurement. Its value ranges
from 1 to inputPowerCount. |
Integer32 Constraints: range: 1-12 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.1 |
||||||||||
|
Value indicates what is being measured in this table row.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.3.4.1.2 |
||||||||||
|
An input VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.3 |
||||||||||
|
An input Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.4 |
||||||||||
|
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTimer will be reset updated as well. |
Unsigned32r/w Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.5 |
||||||||||
|
Timestamp of when input Watt-hours (inputWh) was last reset.
|
UnixTimeStamp | .1.3.6.1.4.1.534.6.6.7.3.4.1.6 |
||||||||||
|
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.7 |
||||||||||
|
An input VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.4.1.8 |
inputTotalPowerTable
table.1.3.6.1.4.1.534.6.6.7.3.5
·
1 row entry
·
7 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputTotalPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputTotalPowerTable'
A list of total input power measurements.
An entry for a total input power measurement.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
An input VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.3 |
|
An input Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.4 |
|
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTimer will be reset updated as well. |
Unsigned32r/w Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.5 |
|
Timestamp of when input Watt-hours (inputWh) was last reset.
|
UnixTimeStamp | .1.3.6.1.4.1.534.6.6.7.3.5.1.6 |
|
An input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.7 |
|
An input VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.8 |
|
Typical power capacity of the input. A negative value indicates that
the hardware current capacity is unknown. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.3.5.1.9 |
groupTable
table.1.3.6.1.4.1.534.6.6.7.5.1
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupTable'
A list of groups. The number of entries is given by groupCount.
An entry for a particular group.
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each group. Its value ranges from 1 to groupCount.
|
Integer32 Constraints: range: 1-64 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.1 |
||||||||||||
|
Alphanumeric designator for the group. This value may be written
on the face of the unit. |
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.2 |
||||||||||||
|
A descriptive name for the group.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.3 |
||||||||||||
|
The type of the group.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.1.1.4 |
||||||||||||
|
Only applicable to breaker-groups. Indicates whether a breaker is turned
off or on. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.1.1.5 |
||||||||||||
|
Number of children for this group.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.6 |
||||||||||||
|
Background color code of the group. Color codes are decimal values.
|
Unsigned32 Constraints: range: 0-16777215 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.7 |
||||||||||||
|
Alphanumeric physical name for the group. This value may be written
on the face of the unit. |
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.8 |
||||||||||||
|
Identifies the input on which the group is connected.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.1.1.9 |
groupChildTable
table.1.3.6.1.4.1.534.6.6.7.5.2
·
1 row entry
·
3 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupChildTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupChildTable'
A list of children for this group. For example, this table will link to all of the outlets that are contained in a particular group.
An entry for a particular child.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each child. Its value ranges from 1 to groupChildCount.
|
Integer32 Constraints: range: 1-32 |
.1.3.6.1.4.1.534.6.6.7.5.2.1.1 |
||||||||
|
The type of the child.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.2.1.2 |
||||||||
|
Object ID of a child object.
|
ObjectIdentifier | .1.3.6.1.4.1.534.6.6.7.5.2.1.3 |
groupVoltageTable
table.1.3.6.1.4.1.534.6.6.7.5.3
·
1 row entry
·
7 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupVoltageTable'
A list of group voltage measurements. There can be only one voltage measurement for each group.
An entry for a group voltage measurement.
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Value indicates what voltage is being measured in this table row.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.3.1.2 |
||||||||||||||||
|
Units are millivolts.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.3 |
||||||||||||||||
|
Status of the measured group voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.3.1.4 |
||||||||||||||||
|
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.5 |
||||||||||||||||
|
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.6 |
||||||||||||||||
|
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.7 |
||||||||||||||||
|
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.5.3.1.8 |
groupCurrentTable
table.1.3.6.1.4.1.534.6.6.7.5.4
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupCurrentTable'
A list of group current measurements. There can be only one current measurement for each group.
An entry for a group current measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Rated current capacity of the group. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups). |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.2 |
||||||||||
|
A group current measurement value. Units are milliamps.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.3 |
||||||||||
|
Status of the measured group current relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.4.1.4 |
||||||||||
|
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.5 |
||||||||||
|
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.6 |
||||||||||
|
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.7 |
||||||||||
|
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.8 |
||||||||||
|
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.9 |
||||||||||
|
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.4.1.10 |
groupPowerTable
table.1.3.6.1.4.1.534.6.6.7.5.5
·
1 row entry
·
6 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupPowerTable'
A list of group power measurements. There can be only one power measurement for each group.
An entry for a group power measurement.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
A group VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.2 |
|
A group Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.3 |
|
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTotalTimer will be reset to 0 as well. |
Unsigned32r/w Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.4 |
|
Timestamp of when group Watt-hours (groupWh) was last reset.
|
UnixTimeStamp | .1.3.6.1.4.1.534.6.6.7.5.5.1.5 |
|
A group PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.6 |
|
A group VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.5.5.1.7 |
groupControlTable
table.1.3.6.1.4.1.534.6.6.7.5.6
·
1 row entry
·
4 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupControlTable'
A list of controllable groups.
An entry for a controllable group.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
Current state of a controlled group. A value of 'mixed' means that
that the outlets within the group have differing states. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.5.6.1.2 |
||||||||
|
Group-level outlet control command.
Once the command is issued, the outlets in the group will turn Off immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-leve… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.5.6.1.3 |
||||||||
|
Group-level outlet control command.
Once the command is issued, the outlets in the group will turn On immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-level… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.5.6.1.4 |
||||||||
|
Group-level outlet control command.
For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and… |
Integer32r/w Constraints: range: -1-0 |
.1.3.6.1.4.1.534.6.6.7.5.6.1.5 |
outletTable
table.1.3.6.1.4.1.534.6.6.7.6.1
·
1 row entry
·
7 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletTable'
A list of outlets. The number of entries is given by outletCount.
An entry for a particular outlet.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each outlet. its value ranges from 1 to outletCount.
|
Integer32 Constraints: range: 1-64 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.1 |
||||||||||||||||||||||||||||||||||||||||
|
Alphanumeric designator for the outlet.
|
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.2 |
||||||||||||||||||||||||||||||||||||||||
|
A descriptive name for the outlet.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.3 |
||||||||||||||||||||||||||||||||||||||||
|
Number of parents for this outlet.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.4 |
||||||||||||||||||||||||||||||||||||||||
|
The physical type of outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.1.1.5 |
||||||||||||||||||||||||||||||||||||||||
|
Alphanumeric physical name for the outlet.
|
OctetString Constraints: range: 2-4 |
.1.3.6.1.4.1.534.6.6.7.6.1.1.6 |
||||||||||||||||||||||||||||||||||||||||
|
Value indicates which phases are connected to each outlet in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, phase 3 to phase 1,… |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.1.1.7 |
outletParentTable
table.1.3.6.1.4.1.534.6.6.7.6.2
·
1 row entry
·
3 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletParentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletParentTable'
A list of parents for this outlet. For example, this table will link to all of the groups that have this outlet as a child.
An entry for a particular parent.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each parent. Its value ranges from 1 to outletParentCount.
|
Integer32 Constraints: range: 1-32 |
.1.3.6.1.4.1.534.6.6.7.6.2.1.1 |
||||||||
|
The type of the parent.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.2.1.2 |
||||||||
|
Object ID of a parent object.
|
ObjectIdentifier | .1.3.6.1.4.1.534.6.6.7.6.2.1.3 |
outletVoltageTable
table.1.3.6.1.4.1.534.6.6.7.6.3
·
1 row entry
·
6 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletVoltageTable'
A list of outlet voltage measurements.
An entry for an outlet voltage measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Units are millivolts.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.2 |
||||||||||
|
Status of the measured outlet voltage relative to the configured thresholds.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.3.1.3 |
||||||||||
|
Lower warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.4 |
||||||||||
|
Lower critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.5 |
||||||||||
|
Upper warning threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.6 |
||||||||||
|
Upper critical threshold. Units are millivolts. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-500000 |
.1.3.6.1.4.1.534.6.6.7.6.3.1.7 |
outletCurrentTable
table.1.3.6.1.4.1.534.6.6.7.6.4
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletCurrentTable'
A list of outlet current measurements.
An entry for an outlet current measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
Rated current capacity of the outlet. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.2 |
||||||||||
|
An outlet current measurement value. Units are milliamps.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.3 |
||||||||||
|
Status of the measured outlet current relative to the configured thresholds.
A negative value indicates that this object is not available. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.4.1.4 |
||||||||||
|
Lower warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.5 |
||||||||||
|
Lower critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.6 |
||||||||||
|
Upper warning threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.7 |
||||||||||
|
Upper critical threshold. Units are milliamps. A negative value indicates
that this object is not available. |
Integer32r/w Constraints: range: -1-100000 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.8 |
||||||||||
|
Current crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.9 |
||||||||||
|
Current percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.4.1.10 |
outletPowerTable
table.1.3.6.1.4.1.534.6.6.7.6.5
·
1 row entry
·
6 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletPowerTable'
A list of outlet power measurements.
An entry for an outlet power measurement.
Indexes
| Column | Syntax | OID |
|---|---|---|
|
An outlet VA value. Units are VA. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.2 |
|
An outlet Watts value. Units are Watts. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.3 |
|
Units are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTotalTimer will be reset to 0 as well. |
Unsigned32r/w Constraints: range: 0-4294967295 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.4 |
|
Timestamp of when outlet Watt-hours (outletWh) was last reset.
|
UnixTimeStamp | .1.3.6.1.4.1.534.6.6.7.6.5.1.5 |
|
An outlet PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.6 |
|
An outlet VAR value. Units are VAR. A negative value indicates
that this object is not available. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.6.5.1.7 |
outletControlTable
table.1.3.6.1.4.1.534.6.6.7.6.6
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletControlTable'
A list of controllable outlets.
An entry for a controllable outlet.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
|
Current state of a controlled outlet.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.6.1.2 |
||||||||
|
Outlet control command.
Once the command is issued, the outlet will turn Off immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet Off command … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.3 |
||||||||
|
Outlet control command.
Once the command is issued, the outlet will turn On immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet On command Wh… |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.4 |
||||||||
|
Outlet control command.
For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.5 |
||||||||
|
Determines the outlet state when power is applied to the unit.
0 : not restart at device startup 1 : should sequence back ON in line with outletControlSequenceTime 2 : should take the state the outlet had when power was… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.6.1.6 |
||||||||
|
Time delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on delay. Set to -1 to exclude this outlet from Global Sequence … |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.7 |
||||||||
|
Time delay in seconds that the outlet should remain in the Off state when executing a Reboot command.
|
Integer32r/w Constraints: range: 1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.8 |
||||||||
|
Determines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled 2 : control On/Off disabled. |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.6.1.9 |
||||||||
|
Time delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first then write it to the command outletControlOffCmd. |
Integer32r/w Constraints: range: -1-99999 |
.1.3.6.1.4.1.534.6.6.7.6.6.1.10 |
outletGlobalTable
table.1.3.6.1.4.1.534.6.6.7.6.7
·
1 row entry
·
1 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletGlobalTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletGlobalTable'
A list of globlal configuration on all outlets.
An entry for a global variable on all outlets.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
Determines the state of all outlets when the unit is power off:
0 : not applicable (read only) 1 : Keep the outlet relays in the current position when the PDU is powered down 2 : Makes the outlet relays go to the positi… |
Enumerationr/w Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.6.7.1.2 |
temperatureTable
table.1.3.6.1.4.1.534.6.6.7.7.1
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk temperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::temperatureTable'
A list of temperature probe measurements. The number of entries is given by temperatureCount.
An entry for a temperature measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.1 |
||||||||||
|
A descriptive name for the temperature probe.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.2 |
||||||||||
|
Indicates whether a probe is connected or not.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.1.1.3 |
||||||||||
|
Units are in tenths of a degree according to the scale specified by
temperatureScale (either Fahrenheit or Celsius). Divide by ten to get degrees. |
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.4 |
||||||||||
|
Status of the measured temperature relative to the configured
thresholds. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.1.1.5 |
||||||||||
|
Lower warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-150000 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.6 |
||||||||||
|
Lower critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-150000 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.7 |
||||||||||
|
Upper warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-150000 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.8 |
||||||||||
|
Upper critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-150000 |
.1.3.6.1.4.1.534.6.6.7.7.1.1.9 |
humidityTable
table.1.3.6.1.4.1.534.6.6.7.7.2
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk humidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::humidityTable'
A list of humidity probe measurements. The number of entries is given by humidityCount.
An entry for a humidity measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
|
A unique value for each humidity probe measurement. Its value
ranges from 1 to humidityCount. |
Integer32 Constraints: range: 1-2 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.1 |
||||||||||
|
A descriptive name for the humidity probe.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.2 |
||||||||||
|
Indicates whether a probe is connected or not.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.2.1.3 |
||||||||||
|
Units are tenths of a percent relative humidity. Divide the value by 10 to get %RH.
|
SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.4 |
||||||||||
|
Status of the measured humidity relative to the configured
thresholds. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.2.1.5 |
||||||||||
|
Lower warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-1000 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.6 |
||||||||||
|
Lower critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-1000 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.7 |
||||||||||
|
Upper warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-1000 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.8 |
||||||||||
|
Upper critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available. |
Integer32r/w Constraints: range: -1-1000 |
.1.3.6.1.4.1.534.6.6.7.7.2.1.9 |
contactTable
table.1.3.6.1.4.1.534.6.6.7.7.3
·
1 row entry
·
4 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk contactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::contactTable'
A list of contact sensors. The number of entries is given by contactCount.
An entry for a contact sensor
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
|
A unique value for each contact sensor. Its value ranges from 1 to
contactCount. |
Integer32 Constraints: range: 1-3 |
.1.3.6.1.4.1.534.6.6.7.7.3.1.1 |
||||||
|
A descriptive name for the contact sensor.
|
OctetStringr/w Constraints: range: 1-31 |
.1.3.6.1.4.1.534.6.6.7.7.3.1.2 |
||||||
|
Indicates whether a probe is connected or not.
Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be read. |
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.3.1.3 |
||||||
|
The state of the contact sensor.
|
Enumeration Enumerated Values:
|
.1.3.6.1.4.1.534.6.6.7.7.3.1.4 |