unitTable
table.1.3.6.1.4.1.534.6.6.7.1.2
·
1 row entry
·
22 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk unitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::unitTable'
A list of units. In most cases this list will only contain one entry. However, some units have a 'strapping' feature which allow units to be daisy-chained together such that all of them can be accessed through the SNMP interface of the master. If strapping is enabled, the strapping indexes of the units that can be accessed will be listed in the unitsPresent object.
An entry for a PDU.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| strappingIndexFor units that support 'strapping' functionality, this will be a unique value for each unit. If units do not support 'strapping', this will always be '0'. | Integer32 Constraints: range: 0-23 | .1.3.6.1.4.1.534.6.6.7.1.2.1.1 | ||||||||||||||
| productNameName of the product. | OctetString Constraints: range: 1-127 | .1.3.6.1.4.1.534.6.6.7.1.2.1.2 | ||||||||||||||
| partNumberPart number of the unit. | OctetString | .1.3.6.1.4.1.534.6.6.7.1.2.1.3 | ||||||||||||||
| serialNumberSerial number of the unit. | OctetString | .1.3.6.1.4.1.534.6.6.7.1.2.1.4 | ||||||||||||||
| firmwareVersionFirmware version. | OctetString | .1.3.6.1.4.1.534.6.6.7.1.2.1.5 | ||||||||||||||
| unitNameDescriptive name for the unit. | OctetStringr/w Constraints: range: 1-63 | .1.3.6.1.4.1.534.6.6.7.1.2.1.6 | ||||||||||||||
| lcdControlControl the local LCD. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.1.2.1.7 | ||||||||||||||
| clockValueClock value. This could be from either a real-time clock (in which case it is likely writeable) or from a time server via NTP (probably read-only). | SNMPv2-TCDateAndTimer/w Type Constraints: range: 8range: 11Description: A date-time specification. field octets contents range ----- ------ -------- ----- 1 1-2 year* 0..65536 2 3 month … | .1.3.6.1.4.1.534.6.6.7.1.2.1.8 | ||||||||||||||
| temperatureScaleScale used to return temperature objects. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.1.2.1.9 | ||||||||||||||
| unitTypeTechnical capabilities of the PDU. Functionality is as follows: Monitored (MI) - input and usually section/group monitoring. Advanced Monitored (AM) - input, section/group, and outlet monitoring. Switched (SW) - input … | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.1.2.1.10 | ||||||||||||||
| systemTypeArchitecture of the ePDU electronic. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.1.2.1.11 | ||||||||||||||
| inputCountNumber of inputs on this ePDU. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.1.2.1.20 | ||||||||||||||
| groupCountNumber of groups on this ePDU. Groups include breakers, outlet sections, and user-defined groups. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.1.2.1.21 | ||||||||||||||
| outletCountNumber of outlets on this ePDU. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.1.2.1.22 | ||||||||||||||
| temperatureCountMax number of temperature measurements on this ePDU. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.1.2.1.23 | ||||||||||||||
| humidityCountMax number of humidity measurements on this ePDU. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.1.2.1.24 | ||||||||||||||
| contactCountMax number of contact sensors on this ePDU. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.1.2.1.25 | ||||||||||||||
| communicationStatusStatus of the internal communication with the PDU. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.1.2.1.30 | ||||||||||||||
| internalStatusStatus of the internal failure inside the PDU. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.1.2.1.31 | ||||||||||||||
| strappingStatusStatus of the external communication with a strapping unit. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.1.2.1.32 | ||||||||||||||
| userNameUsername used to log into the PDU. | OctetString Constraints: range: 0-31 | .1.3.6.1.4.1.534.6.6.7.1.2.1.40 | ||||||||||||||
| commInterfaceCommunications interface used to log into the PDU. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.1.2.1.41 |
unitControlTable
table.1.3.6.1.4.1.534.6.6.7.1.3
·
1 row entry
·
2 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk unitControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::unitControlTable'
A list of units that have controllable outlets.
An entry for a PDU which has controllable outlets.
Indexes
| Column | Syntax | OID |
|---|---|---|
| unitControlOffCmdUnit-level outlet control command. Once the command is issued, outlets will turn Off. 0-n : Time in seconds until the outlet Sequence Off command is issued -1 : Cancel a pending unit-level Off command … | Integer32r/w Constraints: range: -1-99999 | .1.3.6.1.4.1.534.6.6.7.1.3.1.2 |
| unitControlOnCmdUnit-level outlet control command. Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value. 0-n : Time in seconds until the outlet Sequence On command is issue… | Integer32r/w Constraints: range: -1-99999 | .1.3.6.1.4.1.534.6.6.7.1.3.1.3 |
inputTable
table.1.3.6.1.4.1.534.6.6.7.3.1
·
1 row entry
·
10 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputTable'
List of inputs to the PDU.
An entry for a particular input.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| inputIndexA unique value for each input. Its value ranges from 1 to inputCount. | Integer32 Constraints: range: 1-2 | .1.3.6.1.4.1.534.6.6.7.3.1.1.1 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| inputTypeType of input - single phase, split phase, three phase delta, or three phase wye. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.3.1.1.2 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| inputFrequencyUnits are 0.1 Hz; divide by ten to get Hz. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.1.1.3 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| inputFrequencyStatusStatus of the measured input frequency relative to the nominal frequency and the admitted tolerance. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.3.1.1.4 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| inputVoltageCountNumber of input voltage measurements on this ePDU. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.1.1.5 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| inputCurrentCountNumber of input current measurements on this ePDU. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.1.1.6 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| inputPowerCountNumber of rows in the inputPowerTable. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.1.1.7 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| inputPlugTypeIdentifies which plug is on the input. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.3.1.1.8 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| inputFeedColorColor code of the input feed. | Unsigned32r/w Constraints: range: 0-16777215 | .1.3.6.1.4.1.534.6.6.7.3.1.1.9 | ||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||||
| inputFeedNameA descriptive name for the input. | OctetStringr/w Constraints: range: 1-31 | .1.3.6.1.4.1.534.6.6.7.3.1.1.10 |
inputVoltageTable
table.1.3.6.1.4.1.534.6.6.7.3.2
·
1 row entry
·
8 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputVoltageTable'
A list of input voltage measurements. The number of entries is given by inputVoltageCount.
An entry for a particular input voltage measurement.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| inputVoltageIndexA unique value for each input voltage measurement. Its value ranges from 1 to inputVoltageCount. | Integer32 Constraints: range: 1-3 | .1.3.6.1.4.1.534.6.6.7.3.2.1.1 | ||||||||||||||
| inputVoltageMeasTypeValue indicates what input voltage is being measured in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, or phase 3 to phase 1. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.3.2.1.2 | ||||||||||||||
| inputVoltageAn input voltage measurement value. Units are millivolts. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.2.1.3 | ||||||||||||||
| inputVoltageThStatusStatus of the measured input voltage relative to the configured thresholds. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.3.2.1.4 | ||||||||||||||
| inputVoltageThLowerWarningLower warning threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.3.2.1.5 | ||||||||||||||
| inputVoltageThLowerCriticalLower critical threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.3.2.1.6 | ||||||||||||||
| inputVoltageThUpperWarningUpper warning threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.3.2.1.7 | ||||||||||||||
| inputVoltageThUpperCriticalUpper critical threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.3.2.1.8 |
inputCurrentTable
table.1.3.6.1.4.1.534.6.6.7.3.3
·
1 row entry
·
12 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputCurrentTable'
A list of input current measurements. The number of entries is given by inputCurrentCount.
An entry for a particular input current measurement.
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| inputCurrentIndexA unique value for each input current measurement. Its value ranges from 1 to inputCurrentCount. | Integer32 Constraints: range: 1-4 | .1.3.6.1.4.1.534.6.6.7.3.3.1.1 | ||||||||||
| inputCurrentMeasTypeWhich input wire is being measured in this table row - single phase, neutral, phase 1, phase 2, or phase 3. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.3.3.1.2 | ||||||||||
| inputCurrentCapacityRated current capacity of the input. A negative value indicates that the hardware current capacity is unknown. Units are milliamps. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.3.1.3 | ||||||||||
| inputCurrentAn input current measurement value. Units are milliamps. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.3.1.4 | ||||||||||
| inputCurrentThStatusStatus of the measured input current relative to the configured thresholds. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.3.3.1.5 | ||||||||||
| inputCurrentThLowerWarningLower warning threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.3.3.1.6 | ||||||||||
| inputCurrentThLowerCriticalLower critical threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.3.3.1.7 | ||||||||||
| inputCurrentThUpperWarningUpper warning threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.3.3.1.8 | ||||||||||
| inputCurrentThUpperCriticalUpper critical threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.3.3.1.9 | ||||||||||
| inputCurrentCrestFactorCurrent crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.3.1.10 | ||||||||||
| inputCurrentPercentLoadCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.3.1.11 | ||||||||||
| inputPhaseDesignatorAlphanumeric physical name for the input. | OctetString Constraints: range: 2-4 | .1.3.6.1.4.1.534.6.6.7.3.3.1.12 |
inputPowerTable
table.1.3.6.1.4.1.534.6.6.7.3.4
·
1 row entry
·
8 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputPowerTable'
A list of input power measurements. The number of entries is given by inputPowerCount.
An entry for an input power measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| inputPowerIndexA unique value for each input power measurement. Its value ranges from 1 to inputPowerCount. | Integer32 Constraints: range: 1-12 | .1.3.6.1.4.1.534.6.6.7.3.4.1.1 | ||||||||||
| inputPowerMeasTypeValue indicates what is being measured in this table row. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.3.4.1.2 | ||||||||||
| inputVAAn input VA value. Units are VA. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.4.1.3 | ||||||||||
| inputWattsAn input Watts value. Units are Watts. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.4.1.4 | ||||||||||
| inputWhUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well. | Unsigned32r/w Constraints: range: 0-4294967295 | .1.3.6.1.4.1.534.6.6.7.3.4.1.5 | ||||||||||
| inputWhTimerTimestamp of when input Watt-hours (inputWh) was last reset. | UnixTimeStamp | .1.3.6.1.4.1.534.6.6.7.3.4.1.6 | ||||||||||
| inputPowerFactorAn input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.4.1.7 | ||||||||||
| inputVARAn input VAR value. Units are VAR. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.4.1.8 |
inputTotalPowerTable
table.1.3.6.1.4.1.534.6.6.7.3.5
·
1 row entry
·
7 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk inputTotalPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputTotalPowerTable'
A list of total input power measurements.
An entry for a total input power measurement.
Indexes
| Column | Syntax | OID |
|---|---|---|
| inputTotalVAAn input VA value. Units are VA. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.5.1.3 |
| inputTotalWattsAn input Watts value. Units are Watts. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.5.1.4 |
| inputTotalWhUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTimer will be reset updated as well. | Unsigned32r/w Constraints: range: 0-4294967295 | .1.3.6.1.4.1.534.6.6.7.3.5.1.5 |
| inputTotalWhTimerTimestamp of when input Watt-hours (inputWh) was last reset. | UnixTimeStamp | .1.3.6.1.4.1.534.6.6.7.3.5.1.6 |
| inputTotalPowerFactorAn input PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.5.1.7 |
| inputTotalVARAn input VAR value. Units are VAR. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.5.1.8 |
| inputPowerCapacityTypical power capacity of the input. A negative value indicates that the hardware current capacity is unknown. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.3.5.1.9 |
groupTable
table.1.3.6.1.4.1.534.6.6.7.5.1
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupTable'
A list of groups. The number of entries is given by groupCount.
An entry for a particular group.
Indexes
| Column | Syntax | OID | ||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| groupIndexA unique value for each group. Its value ranges from 1 to groupCount. | Integer32 Constraints: range: 1-64 | .1.3.6.1.4.1.534.6.6.7.5.1.1.1 | ||||||||||||
| groupIDAlphanumeric designator for the group. This value may be written on the face of the unit. | OctetString Constraints: range: 2-4 | .1.3.6.1.4.1.534.6.6.7.5.1.1.2 | ||||||||||||
| groupNameA descriptive name for the group. | OctetStringr/w Constraints: range: 1-31 | .1.3.6.1.4.1.534.6.6.7.5.1.1.3 | ||||||||||||
| groupTypeThe type of the group. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.5.1.1.4 | ||||||||||||
| groupBreakerStatusOnly applicable to breaker-groups. Indicates whether a breaker is turned off or on. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.5.1.1.5 | ||||||||||||
| groupChildCountNumber of children for this group. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.1.1.6 | ||||||||||||
| groupColorBackground color code of the group. Color codes are decimal values. | Unsigned32 Constraints: range: 0-16777215 | .1.3.6.1.4.1.534.6.6.7.5.1.1.7 | ||||||||||||
| groupDesignatorAlphanumeric physical name for the group. This value may be written on the face of the unit. | OctetString Constraints: range: 2-4 | .1.3.6.1.4.1.534.6.6.7.5.1.1.8 | ||||||||||||
| groupInputIndexIdentifies the input on which the group is connected. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.1.1.9 |
groupChildTable
table.1.3.6.1.4.1.534.6.6.7.5.2
·
1 row entry
·
3 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupChildTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupChildTable'
A list of children for this group. For example, this table will link to all of the outlets that are contained in a particular group.
An entry for a particular child.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| groupChildIndexA unique value for each child. Its value ranges from 1 to groupChildCount. | Integer32 Constraints: range: 1-32 | .1.3.6.1.4.1.534.6.6.7.5.2.1.1 | ||||||||
| groupChildTypeThe type of the child. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.5.2.1.2 | ||||||||
| groupChildOIDObject ID of a child object. | ObjectIdentifier | .1.3.6.1.4.1.534.6.6.7.5.2.1.3 |
groupVoltageTable
table.1.3.6.1.4.1.534.6.6.7.5.3
·
1 row entry
·
7 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupVoltageTable'
A list of group voltage measurements. There can be only one voltage measurement for each group.
An entry for a group voltage measurement.
Indexes
| Column | Syntax | OID | ||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| groupVoltageMeasTypeValue indicates what voltage is being measured in this table row. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.5.3.1.2 | ||||||||||||||||
| groupVoltageUnits are millivolts. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.3.1.3 | ||||||||||||||||
| groupVoltageThStatusStatus of the measured group voltage relative to the configured thresholds. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.5.3.1.4 | ||||||||||||||||
| groupVoltageThLowerWarningLower warning threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.5.3.1.5 | ||||||||||||||||
| groupVoltageThLowerCriticalLower critical threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.5.3.1.6 | ||||||||||||||||
| groupVoltageThUpperWarningUpper warning threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.5.3.1.7 | ||||||||||||||||
| groupVoltageThUpperCriticalUpper critical threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.5.3.1.8 |
groupCurrentTable
table.1.3.6.1.4.1.534.6.6.7.5.4
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupCurrentTable'
A list of group current measurements. There can be only one current measurement for each group.
An entry for a group current measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| groupCurrentCapacityRated current capacity of the group. Units are milliamps. A negative value indicates that the hardware current capacity is unknown (it will always be unknown for custom groups). | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.4.1.2 | ||||||||||
| groupCurrentA group current measurement value. Units are milliamps. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.4.1.3 | ||||||||||
| groupCurrentThStatusStatus of the measured group current relative to the configured thresholds. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.5.4.1.4 | ||||||||||
| groupCurrentThLowerWarningLower warning threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.5.4.1.5 | ||||||||||
| groupCurrentThLowerCriticalLower critical threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.5.4.1.6 | ||||||||||
| groupCurrentThUpperWarningUpper warning threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.5.4.1.7 | ||||||||||
| groupCurrentThUpperCriticalUpper critical threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.5.4.1.8 | ||||||||||
| groupCurrentCrestFactorCurrent crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.4.1.9 | ||||||||||
| groupCurrentPercentLoadCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.4.1.10 |
groupPowerTable
table.1.3.6.1.4.1.534.6.6.7.5.5
·
1 row entry
·
6 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupPowerTable'
A list of group power measurements. There can be only one power measurement for each group.
An entry for a group power measurement.
Indexes
| Column | Syntax | OID |
|---|---|---|
| groupVAA group VA value. Units are VA. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.5.1.2 |
| groupWattsA group Watts value. Units are Watts. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.5.1.3 |
| groupWhUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well. | Unsigned32r/w Constraints: range: 0-4294967295 | .1.3.6.1.4.1.534.6.6.7.5.5.1.4 |
| groupWhTimerTimestamp of when group Watt-hours (groupWh) was last reset. | UnixTimeStamp | .1.3.6.1.4.1.534.6.6.7.5.5.1.5 |
| groupPowerFactorA group PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.5.1.6 |
| groupVARA group VAR value. Units are VAR. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.5.5.1.7 |
groupControlTable
table.1.3.6.1.4.1.534.6.6.7.5.6
·
1 row entry
·
4 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk groupControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupControlTable'
A list of controllable groups.
An entry for a controllable group.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| groupControlStatusCurrent state of a controlled group. A value of 'mixed' means that that the outlets within the group have differing states. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.5.6.1.2 | ||||||||
| groupControlOffCmdGroup-level outlet control command. Once the command is issued, the outlets in the group will turn Off immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-leve… | Integer32r/w Constraints: range: -1-99999 | .1.3.6.1.4.1.534.6.6.7.5.6.1.3 | ||||||||
| groupControlOnCmdGroup-level outlet control command. Once the command is issued, the outlets in the group will turn On immediately. 0-n : Time in seconds until the group command is issued -1 : Cancel a pending group-level… | Integer32r/w Constraints: range: -1-99999 | .1.3.6.1.4.1.534.6.6.7.5.6.1.4 | ||||||||
| groupControlRebootCmdGroup-level outlet control command. For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and… | Integer32r/w Constraints: range: -1-0 | .1.3.6.1.4.1.534.6.6.7.5.6.1.5 |
outletTable
table.1.3.6.1.4.1.534.6.6.7.6.1
·
1 row entry
·
7 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletTable'
A list of outlets. The number of entries is given by outletCount.
An entry for a particular outlet.
Indexes
| Column | Syntax | OID | ||||||||||||||||||||||||||||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
| outletIndexA unique value for each outlet. its value ranges from 1 to outletCount. | Integer32 Constraints: range: 1-64 | .1.3.6.1.4.1.534.6.6.7.6.1.1.1 | ||||||||||||||||||||||||||||||||||||||||
| outletIDAlphanumeric designator for the outlet. | OctetString Constraints: range: 2-4 | .1.3.6.1.4.1.534.6.6.7.6.1.1.2 | ||||||||||||||||||||||||||||||||||||||||
| outletNameA descriptive name for the outlet. | OctetStringr/w Constraints: range: 1-31 | .1.3.6.1.4.1.534.6.6.7.6.1.1.3 | ||||||||||||||||||||||||||||||||||||||||
| outletParentCountNumber of parents for this outlet. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.1.1.4 | ||||||||||||||||||||||||||||||||||||||||
| outletTypeThe physical type of outlet. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.6.1.1.5 | ||||||||||||||||||||||||||||||||||||||||
| outletDesignatorAlphanumeric physical name for the outlet. | OctetString Constraints: range: 2-4 | .1.3.6.1.4.1.534.6.6.7.6.1.1.6 | ||||||||||||||||||||||||||||||||||||||||
| outletPhaseIDValue indicates which phases are connected to each outlet in this table row - single phase voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2, phase 2 to phase 3, phase 3 to phase 1,… | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.6.1.1.7 |
outletParentTable
table.1.3.6.1.4.1.534.6.6.7.6.2
·
1 row entry
·
3 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletParentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletParentTable'
A list of parents for this outlet. For example, this table will link to all of the groups that have this outlet as a child.
An entry for a particular parent.
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| outletParentIndexA unique value for each parent. Its value ranges from 1 to outletParentCount. | Integer32 Constraints: range: 1-32 | .1.3.6.1.4.1.534.6.6.7.6.2.1.1 | ||||||||
| outletParentTypeThe type of the parent. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.6.2.1.2 | ||||||||
| outletParentOIDObject ID of a parent object. | ObjectIdentifier | .1.3.6.1.4.1.534.6.6.7.6.2.1.3 |
outletVoltageTable
table.1.3.6.1.4.1.534.6.6.7.6.3
·
1 row entry
·
6 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletVoltageTable'
A list of outlet voltage measurements.
An entry for an outlet voltage measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| outletVoltageUnits are millivolts. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.3.1.2 | ||||||||||
| outletVoltageThStatusStatus of the measured outlet voltage relative to the configured thresholds. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.6.3.1.3 | ||||||||||
| outletVoltageThLowerWarningLower warning threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.6.3.1.4 | ||||||||||
| outletVoltageThLowerCriticalLower critical threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.6.3.1.5 | ||||||||||
| outletVoltageThUpperWarningUpper warning threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.6.3.1.6 | ||||||||||
| outletVoltageThUpperCriticalUpper critical threshold. Units are millivolts. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-500000 | .1.3.6.1.4.1.534.6.6.7.6.3.1.7 |
outletCurrentTable
table.1.3.6.1.4.1.534.6.6.7.6.4
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletCurrentTable'
A list of outlet current measurements.
An entry for an outlet current measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| outletCurrentCapacityRated current capacity of the outlet. Units are milliamps. A negative value indicates that the hardware current capacity is unknown. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.4.1.2 | ||||||||||
| outletCurrentAn outlet current measurement value. Units are milliamps. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.4.1.3 | ||||||||||
| outletCurrentThStatusStatus of the measured outlet current relative to the configured thresholds. A negative value indicates that this object is not available. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.6.4.1.4 | ||||||||||
| outletCurrentThLowerWarningLower warning threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.6.4.1.5 | ||||||||||
| outletCurrentThLowerCriticalLower critical threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.6.4.1.6 | ||||||||||
| outletCurrentThUpperWarningUpper warning threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.6.4.1.7 | ||||||||||
| outletCurrentThUpperCriticalUpper critical threshold. Units are milliamps. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-100000 | .1.3.6.1.4.1.534.6.6.7.6.4.1.8 | ||||||||||
| outletCurrentCrestFactorCurrent crest factor. Units are in milli, for example a crest factor of 1.414 will be returned as 1414. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.4.1.9 | ||||||||||
| outletCurrentPercentLoadCurrent percent load, based on the rated current capacity. Units are percentage, for example 80% will be returned as 80. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.4.1.10 |
outletPowerTable
table.1.3.6.1.4.1.534.6.6.7.6.5
·
1 row entry
·
6 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletPowerTable'
A list of outlet power measurements.
An entry for an outlet power measurement.
Indexes
| Column | Syntax | OID |
|---|---|---|
| outletVAAn outlet VA value. Units are VA. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.5.1.2 |
| outletWattsAn outlet Watts value. Units are Watts. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.5.1.3 |
| outletWhUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is written to, the inputWhTotalTimer will be reset to 0 as well. | Unsigned32r/w Constraints: range: 0-4294967295 | .1.3.6.1.4.1.534.6.6.7.6.5.1.4 |
| outletWhTimerTimestamp of when outlet Watt-hours (outletWh) was last reset. | UnixTimeStamp | .1.3.6.1.4.1.534.6.6.7.6.5.1.5 |
| outletPowerFactorAn outlet PF value. Units are in thousandths, for example a power factor of 0.958 would be returned as 958, and 0.92 would be returned as 920. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.5.1.6 |
| outletVARAn outlet VAR value. Units are VAR. A negative value indicates that this object is not available. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.6.5.1.7 |
outletControlTable
table.1.3.6.1.4.1.534.6.6.7.6.6
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletControlTable'
A list of controllable outlets.
An entry for a controllable outlet.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
| outletControlStatusCurrent state of a controlled outlet. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.6.6.1.2 | ||||||||
| outletControlOffCmdOutlet control command. Once the command is issued, the outlet will turn Off immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet Off command … | Integer32r/w Constraints: range: -1-99999 | .1.3.6.1.4.1.534.6.6.7.6.6.1.3 | ||||||||
| outletControlOnCmdOutlet control command. Once the command is issued, the outlet will turn On immediately. 0-n : Time in seconds until the outlet command is issued -1 : Cancel a pending outlet On command Wh… | Integer32r/w Constraints: range: -1-99999 | .1.3.6.1.4.1.534.6.6.7.6.6.1.4 | ||||||||
| outletControlRebootCmdOutlet control command. For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is issued, remain Off for outletControlRebootOffTime seconds, and then turn … | Integer32r/w Constraints: range: -1-99999 | .1.3.6.1.4.1.534.6.6.7.6.6.1.5 | ||||||||
| outletControlPowerOnStateDetermines the outlet state when power is applied to the unit. 0 : not restart at device startup 1 : should sequence back ON in line with outletControlSequenceTime 2 : should take the state the outlet had when power was… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.6.6.1.6 | ||||||||
| outletControlSequenceDelayTime delay in seconds from when a Global Sequence On command is issued to when the command is executed on this outlet. This delay is also used as a power-on delay. Set to -1 to exclude this outlet from Global Sequence … | Integer32r/w Constraints: range: -1-99999 | .1.3.6.1.4.1.534.6.6.7.6.6.1.7 | ||||||||
| outletControlRebootOffTimeTime delay in seconds that the outlet should remain in the Off state when executing a Reboot command. | Integer32r/w Constraints: range: 1-99999 | .1.3.6.1.4.1.534.6.6.7.6.6.1.8 | ||||||||
| outletControlSwitchableDetermines the outlet capability to be controlled On/Off from the communication channels. 1 : control On/Off enabled 2 : control On/Off disabled. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.6.6.1.9 | ||||||||
| outletControlShutoffDelayTime delay in seconds that could be taken in account before shutting of the outlet. An application which need to shutoff properly an outlet will read this parameter first then write it to the command outletControlOffCmd. | Integer32r/w Constraints: range: -1-99999 | .1.3.6.1.4.1.534.6.6.7.6.6.1.10 |
outletGlobalTable
table.1.3.6.1.4.1.534.6.6.7.6.7
·
1 row entry
·
1 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk outletGlobalTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletGlobalTable'
A list of globlal configuration on all outlets.
An entry for a global variable on all outlets.
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
| outletAutomaticShutoffDetermines the state of all outlets when the unit is power off: 0 : not applicable (read only) 1 : Keep the outlet relays in the current position when the PDU is powered down 2 : Makes the outlet relays go to the positi… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.6.7.1.2 |
temperatureTable
table.1.3.6.1.4.1.534.6.6.7.7.1
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk temperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::temperatureTable'
A list of temperature probe measurements. The number of entries is given by temperatureCount.
An entry for a temperature measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| temperatureIndexA unique value for each temperature probe measurement. Its value ranges from 1 to temperatureCount. | Integer32 Constraints: range: 1-2 | .1.3.6.1.4.1.534.6.6.7.7.1.1.1 | ||||||||||
| temperatureNameA descriptive name for the temperature probe. | OctetStringr/w Constraints: range: 1-31 | .1.3.6.1.4.1.534.6.6.7.7.1.1.2 | ||||||||||
| temperatureProbeStatusIndicates whether a probe is connected or not. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.7.1.1.3 | ||||||||||
| temperatureValueUnits are in tenths of a degree according to the scale specified by temperatureScale (either Fahrenheit or Celsius). Divide by ten to get degrees. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.7.1.1.4 | ||||||||||
| temperatureThStatusStatus of the measured temperature relative to the configured thresholds. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.7.1.1.5 | ||||||||||
| temperatureThLowerWarningLower warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-150000 | .1.3.6.1.4.1.534.6.6.7.7.1.1.6 | ||||||||||
| temperatureThLowerCriticalLower critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-150000 | .1.3.6.1.4.1.534.6.6.7.7.1.1.7 | ||||||||||
| temperatureThUpperWarningUpper warning threshold. Units are tenths of a degree. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-150000 | .1.3.6.1.4.1.534.6.6.7.7.1.1.8 | ||||||||||
| temperatureThUpperCriticalUpper critical threshold. Units are tenths of a degree. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-150000 | .1.3.6.1.4.1.534.6.6.7.7.1.1.9 |
humidityTable
table.1.3.6.1.4.1.534.6.6.7.7.2
·
1 row entry
·
9 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk humidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::humidityTable'
A list of humidity probe measurements. The number of entries is given by humidityCount.
An entry for a humidity measurement.
Indexes
| Column | Syntax | OID | ||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|
| humidityIndexA unique value for each humidity probe measurement. Its value ranges from 1 to humidityCount. | Integer32 Constraints: range: 1-2 | .1.3.6.1.4.1.534.6.6.7.7.2.1.1 | ||||||||||
| humidityNameA descriptive name for the humidity probe. | OctetStringr/w Constraints: range: 1-31 | .1.3.6.1.4.1.534.6.6.7.7.2.1.2 | ||||||||||
| humidityProbeStatusIndicates whether a probe is connected or not. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.7.2.1.3 | ||||||||||
| humidityValueUnits are tenths of a percent relative humidity. Divide the value by 10 to get %RH. | SNMPv2-SMIInteger32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.534.6.6.7.7.2.1.4 | ||||||||||
| humidityThStatusStatus of the measured humidity relative to the configured thresholds. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.7.2.1.5 | ||||||||||
| humidityThLowerWarningLower warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-1000 | .1.3.6.1.4.1.534.6.6.7.7.2.1.6 | ||||||||||
| humidityThLowerCriticalLower critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-1000 | .1.3.6.1.4.1.534.6.6.7.7.2.1.7 | ||||||||||
| humidityThUpperWarningUpper warning threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-1000 | .1.3.6.1.4.1.534.6.6.7.7.2.1.8 | ||||||||||
| humidityThUpperCriticalUpper critical threshold. Units are 0.1 %RH. A negative value indicates that this object is not available. | Integer32r/w Constraints: range: -1-1000 | .1.3.6.1.4.1.534.6.6.7.7.2.1.9 |
contactTable
table.1.3.6.1.4.1.534.6.6.7.7.3
·
1 row entry
·
4 columns
Uses the eaton variant from
Command help
/opt/observium/mibs/eaton.
Walk contactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::contactTable'
A list of contact sensors. The number of entries is given by contactCount.
An entry for a contact sensor
Indexes
| Column | Syntax | OID | ||||||
|---|---|---|---|---|---|---|---|---|
| contactIndexA unique value for each contact sensor. Its value ranges from 1 to contactCount. | Integer32 Constraints: range: 1-3 | .1.3.6.1.4.1.534.6.6.7.7.3.1.1 | ||||||
| contactNameA descriptive name for the contact sensor. | OctetStringr/w Constraints: range: 1-31 | .1.3.6.1.4.1.534.6.6.7.7.3.1.2 | ||||||
| contactProbeStatusIndicates whether a probe is connected or not. Will not be returned if the contact sensor is internal to the ePDU, in that case only contactState should be read. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.7.3.1.3 | ||||||
| contactStateThe state of the contact sensor. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.534.6.6.7.7.3.1.4 |