EATON-EPDU-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
23
Rows
23
Columns
170

unitTable

table
.1.3.6.1.4.1.534.6.6.7.1.2 · 1 row entry · 22 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk unitTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::unitTable'
A list of units.  In most cases this list will only contain one entry.
However, some units have a 'strapping' feature which allow units to be
daisy-chained together such that all of them can be accessed through
the SNMP interface of the master.  If strapping is enabled, the 
strapping indexes of the units that can be accessed will be listed in the
unitsPresent object.
unitEntry row .1.3.6.1.4.1.534.6.6.7.1.2.1
An entry for a PDU.
Indexes
Column Syntax OID
strappingIndexFor units that support 'strapping' functionality, this will be a unique
value for each unit. If units do not support 'strapping', this will
always be '0'.
Integer32
Constraints:
range: 0-23
.1.3.6.1.4.1.534.6.6.7.1.2.1.1
productNameName of the product.OctetString
Constraints:
range: 1-127
.1.3.6.1.4.1.534.6.6.7.1.2.1.2
partNumberPart number of the unit.OctetString.1.3.6.1.4.1.534.6.6.7.1.2.1.3
serialNumberSerial number of the unit.OctetString.1.3.6.1.4.1.534.6.6.7.1.2.1.4
firmwareVersionFirmware version.OctetString.1.3.6.1.4.1.534.6.6.7.1.2.1.5
unitNameDescriptive name for the unit.OctetStringr/w
Constraints:
range: 1-63
.1.3.6.1.4.1.534.6.6.7.1.2.1.6
lcdControlControl the local LCD.Enumerationr/w
Enumerated Values:
0notApplicable
1lcdScreenOff
2lcdKeyLock
3lcdScreenOffAndKeyLock
.1.3.6.1.4.1.534.6.6.7.1.2.1.7
clockValueClock value. This could be from either a real-time clock (in which case
it is likely writeable) or from a time server via NTP (probably read-only).
SNMPv2-TCDateAndTimer/w
Type Constraints:
range: 8
range: 11
Description:
A date-time specification.

field octets contents range
----- ------ -------- -----
1 1-2 year* 0..65536
2 3 month …
.1.3.6.1.4.1.534.6.6.7.1.2.1.8
temperatureScaleScale used to return temperature objects.Enumerationr/w
Enumerated Values:
0celsius
1fahrenheit
.1.3.6.1.4.1.534.6.6.7.1.2.1.9
unitTypeTechnical capabilities of the PDU. Functionality is as follows:
Monitored (MI) - input and usually section/group monitoring.
Advanced Monitored (AM) - input, section/group, and outlet monitoring.
Switched (SW) - input …
Enumeration
Enumerated Values:
0unknown
1switched
2advancedMonitored
3managed
4monitored
5basic
6inlineMonitored
.1.3.6.1.4.1.534.6.6.7.1.2.1.10
systemTypeArchitecture of the ePDU electronic.Enumeration
Enumerated Values:
0unknown
1g3ePDU
2g3HDePDU
.1.3.6.1.4.1.534.6.6.7.1.2.1.11
inputCountNumber of inputs on this ePDU.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.20
groupCountNumber of groups on this ePDU. Groups include breakers, outlet sections,
and user-defined groups.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.21
outletCountNumber of outlets on this ePDU.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.22
temperatureCountMax number of temperature measurements on this ePDU.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.23
humidityCountMax number of humidity measurements on this ePDU.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.24
contactCountMax number of contact sensors on this ePDU.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.1.2.1.25
communicationStatusStatus of the internal communication with the PDU.Enumeration
Enumerated Values:
0good
1communicationLost
.1.3.6.1.4.1.534.6.6.7.1.2.1.30
internalStatusStatus of the internal failure inside the PDU.Enumeration
Enumerated Values:
0good
1internalFailure
.1.3.6.1.4.1.534.6.6.7.1.2.1.31
strappingStatusStatus of the external communication with a strapping unit.Enumeration
Enumerated Values:
0good
1communicationLost
.1.3.6.1.4.1.534.6.6.7.1.2.1.32
userNameUsername used to log into the PDU.OctetString
Constraints:
range: 0-31
.1.3.6.1.4.1.534.6.6.7.1.2.1.40
commInterfaceCommunications interface used to log into the PDU.Enumeration
Enumerated Values:
0serial
1usb
2telnet
3web
4ftp
5xml
.1.3.6.1.4.1.534.6.6.7.1.2.1.41
.1.3.6.1.4.1.534.6.6.7.1.3 · 1 row entry · 2 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk unitControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::unitControlTable'
A list of units that have controllable outlets.
unitControlEntry row .1.3.6.1.4.1.534.6.6.7.1.3.1
An entry for a PDU which has controllable outlets.
Indexes
Column Syntax OID
unitControlOffCmdUnit-level outlet control command.

Once the command is issued, outlets will turn Off.
0-n : Time in seconds until the outlet Sequence Off command is issued
-1 : Cancel a pending unit-level Off command
…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.1.3.1.2
unitControlOnCmdUnit-level outlet control command.

Once the command is issued, outlets will turn On according to their outletControlSequenceDelay value.
0-n : Time in seconds until the outlet Sequence On command is issue…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.1.3.1.3

inputTable

table
.1.3.6.1.4.1.534.6.6.7.3.1 · 1 row entry · 10 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk inputTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputTable'
List of inputs to the PDU.
inputEntry row .1.3.6.1.4.1.534.6.6.7.3.1.1
An entry for a particular input.
Column Syntax OID
inputIndexA unique value for each input. Its value ranges from 1 to inputCount.Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.6.7.3.1.1.1
inputTypeType of input - single phase, split phase, three phase delta, or three
phase wye.
Enumeration
Enumerated Values:
1singlePhase
2splitPhase
3threePhaseDelta
4threePhaseWye
.1.3.6.1.4.1.534.6.6.7.3.1.1.2
inputFrequencyUnits are 0.1 Hz; divide by ten to get Hz.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.1.1.3
inputFrequencyStatusStatus of the measured input frequency relative to the nominal frequency and the admitted tolerance.Enumeration
Enumerated Values:
0good
1outOfRange
.1.3.6.1.4.1.534.6.6.7.3.1.1.4
inputVoltageCountNumber of input voltage measurements on this ePDU.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.1.1.5
inputCurrentCountNumber of input current measurements on this ePDU.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.1.1.6
inputPowerCountNumber of rows in the inputPowerTable.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.1.1.7
inputPlugTypeIdentifies which plug is on the input.Enumeration
Enumerated Values:
100other1Phase
101iecC14Inlet
102iecC20Inlet
103iec316P6
104iec332P6
105iec363P6
106iecC14Plug
107iecC20Plug
120nema515
121nemaL515
122nema520
123nemaL520
124nema615
125nemaL615
126nemaL530
127nema620
128nemaL620
129nemaL630
130cs8265
131nemaL2530
140other208V2P3W
141other230V1P3W
150french
151schuko
152uk
160field208V2P3W
161field230V1P3W
200other2Phase
201nemaL1420
202nemaL1430
300other3Phase
301iec516P6
302iec460P9
303iec560P9
304iec532P6
306iec563P6
307iec4100P9
320nemaL1520
321nemaL2120
322nemaL1530
323nemaL2130
324cs8365
325nemaL2220
326nemaL2230
327nemaL2630
340other208V3P4W
341other208V3P5W
342other400V3P5W
343other480V3P5W
350bladeUps208V
351bladeUps400V
360field208V3P4W
361field400V3P5W
400universalUTP8pin
.1.3.6.1.4.1.534.6.6.7.3.1.1.8
inputFeedColorColor code of the input feed.Unsigned32r/w
Constraints:
range: 0-16777215
.1.3.6.1.4.1.534.6.6.7.3.1.1.9
inputFeedNameA descriptive name for the input.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.3.1.1.10
.1.3.6.1.4.1.534.6.6.7.3.2 · 1 row entry · 8 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk inputVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputVoltageTable'
A list of input voltage measurements.  The number of entries
is given by inputVoltageCount.
inputVoltageEntry row .1.3.6.1.4.1.534.6.6.7.3.2.1
An entry for a particular input voltage measurement.
Column Syntax OID
inputVoltageIndexA unique value for each input voltage measurement. Its value ranges
from 1 to inputVoltageCount.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.534.6.6.7.3.2.1.1
inputVoltageMeasTypeValue indicates what input voltage is being measured in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, or phase 3 to phase 1.
Enumeration
Enumerated Values:
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
.1.3.6.1.4.1.534.6.6.7.3.2.1.2
inputVoltageAn input voltage measurement value. Units are millivolts.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.2.1.3
inputVoltageThStatusStatus of the measured input voltage relative to the configured thresholds.Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.3.2.1.4
inputVoltageThLowerWarningLower warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.3.2.1.5
inputVoltageThLowerCriticalLower critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.3.2.1.6
inputVoltageThUpperWarningUpper warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.3.2.1.7
inputVoltageThUpperCriticalUpper critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.3.2.1.8
.1.3.6.1.4.1.534.6.6.7.3.3 · 1 row entry · 12 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk inputCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputCurrentTable'
A list of input current measurements.  The number of entries
is given by inputCurrentCount.
inputCurrentEntry row .1.3.6.1.4.1.534.6.6.7.3.3.1
An entry for a particular input current measurement.
Column Syntax OID
inputCurrentIndexA unique value for each input current measurement. Its value ranges
from 1 to inputCurrentCount.
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.534.6.6.7.3.3.1.1
inputCurrentMeasTypeWhich input wire is being measured in this table row - single phase, neutral, phase 1,
phase 2, or phase 3.
Enumeration
Enumerated Values:
1singlePhase
2neutral
3phase1
4phase2
5phase3
.1.3.6.1.4.1.534.6.6.7.3.3.1.2
inputCurrentCapacityRated current capacity of the input. A negative value indicates that
the hardware current capacity is unknown. Units are milliamps.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.3.1.3
inputCurrentAn input current measurement value. Units are milliamps.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.3.1.4
inputCurrentThStatusStatus of the measured input current relative to the configured thresholds.Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.3.3.1.5
inputCurrentThLowerWarningLower warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.3.3.1.6
inputCurrentThLowerCriticalLower critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.3.3.1.7
inputCurrentThUpperWarningUpper warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.3.3.1.8
inputCurrentThUpperCriticalUpper critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.3.3.1.9
inputCurrentCrestFactorCurrent crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.3.1.10
inputCurrentPercentLoadCurrent percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.3.1.11
inputPhaseDesignatorAlphanumeric physical name for the input.OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.3.3.1.12
.1.3.6.1.4.1.534.6.6.7.3.4 · 1 row entry · 8 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk inputPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputPowerTable'
A list of input power measurements.  The number of entries
is given by inputPowerCount.
inputPowerEntry row .1.3.6.1.4.1.534.6.6.7.3.4.1
An entry for an input power measurement.
Column Syntax OID
inputPowerIndexA unique value for each input power measurement. Its value ranges
from 1 to inputPowerCount.
Integer32
Constraints:
range: 1-12
.1.3.6.1.4.1.534.6.6.7.3.4.1.1
inputPowerMeasTypeValue indicates what is being measured in this table row.Enumeration
Enumerated Values:
0unknown
1phase1
2phase2
3phase3
4total
.1.3.6.1.4.1.534.6.6.7.3.4.1.2
inputVAAn input VA value. Units are VA. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.4.1.3
inputWattsAn input Watts value. Units are Watts. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.4.1.4
inputWhUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTimer will be reset updated as well.
Unsigned32r/w
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.534.6.6.7.3.4.1.5
inputWhTimerTimestamp of when input Watt-hours (inputWh) was last reset.UnixTimeStamp.1.3.6.1.4.1.534.6.6.7.3.4.1.6
inputPowerFactorAn input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not
available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.4.1.7
inputVARAn input VAR value. Units are VAR. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.4.1.8
.1.3.6.1.4.1.534.6.6.7.3.5 · 1 row entry · 7 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk inputTotalPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::inputTotalPowerTable'
A list of total input power measurements.
inputTotalPowerEntry row .1.3.6.1.4.1.534.6.6.7.3.5.1
An entry for a total input power measurement.
Column Syntax OID
inputTotalVAAn input VA value. Units are VA. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.3
inputTotalWattsAn input Watts value. Units are Watts. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.4
inputTotalWhUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTimer will be reset updated as well.
Unsigned32r/w
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.534.6.6.7.3.5.1.5
inputTotalWhTimerTimestamp of when input Watt-hours (inputWh) was last reset.UnixTimeStamp.1.3.6.1.4.1.534.6.6.7.3.5.1.6
inputTotalPowerFactorAn input PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not
available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.7
inputTotalVARAn input VAR value. Units are VAR. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.8
inputPowerCapacityTypical power capacity of the input. A negative value indicates that
the hardware current capacity is unknown.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.3.5.1.9

groupTable

table
.1.3.6.1.4.1.534.6.6.7.5.1 · 1 row entry · 9 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk groupTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupTable'
A list of groups.  The number of entries is given by groupCount.
groupEntry row .1.3.6.1.4.1.534.6.6.7.5.1.1
An entry for a particular group.
Column Syntax OID
groupIndexA unique value for each group. Its value ranges from 1 to groupCount.Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.534.6.6.7.5.1.1.1
groupIDAlphanumeric designator for the group. This value may be written
on the face of the unit.
OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.5.1.1.2
groupNameA descriptive name for the group.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.5.1.1.3
groupTypeThe type of the group.Enumeration
Enumerated Values:
0unknown
1breaker1pole
2breaker2pole
3breaker3pole
4outletSection
5userDefined
.1.3.6.1.4.1.534.6.6.7.5.1.1.4
groupBreakerStatusOnly applicable to breaker-groups. Indicates whether a breaker is turned
off or on.
Enumeration
Enumerated Values:
0notApplicable
1breakerOn
2breakerOff
.1.3.6.1.4.1.534.6.6.7.5.1.1.5
groupChildCountNumber of children for this group.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.1.1.6
groupColorBackground color code of the group. Color codes are decimal values.Unsigned32
Constraints:
range: 0-16777215
.1.3.6.1.4.1.534.6.6.7.5.1.1.7
groupDesignatorAlphanumeric physical name for the group. This value may be written
on the face of the unit.
OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.5.1.1.8
groupInputIndexIdentifies the input on which the group is connected.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.1.1.9
.1.3.6.1.4.1.534.6.6.7.5.2 · 1 row entry · 3 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk groupChildTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupChildTable'
A list of children for this group.  For example, this table will link
to all of the outlets that are contained in a particular group.
groupChildEntry row .1.3.6.1.4.1.534.6.6.7.5.2.1
An entry for a particular child.
Column Syntax OID
groupChildIndexA unique value for each child. Its value ranges from 1 to groupChildCount.Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.534.6.6.7.5.2.1.1
groupChildTypeThe type of the child.Enumeration
Enumerated Values:
0unknown
2section
3custom
4outlet
.1.3.6.1.4.1.534.6.6.7.5.2.1.2
groupChildOIDObject ID of a child object.ObjectIdentifier.1.3.6.1.4.1.534.6.6.7.5.2.1.3
.1.3.6.1.4.1.534.6.6.7.5.3 · 1 row entry · 7 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk groupVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupVoltageTable'
A list of group voltage measurements.  There can be only one voltage
measurement for each group.
groupVoltageEntry row .1.3.6.1.4.1.534.6.6.7.5.3.1
An entry for a group voltage measurement.
Column Syntax OID
groupVoltageMeasTypeValue indicates what voltage is being measured in this table row.Enumeration
Enumerated Values:
0unknown
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
.1.3.6.1.4.1.534.6.6.7.5.3.1.2
groupVoltageUnits are millivolts.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.3.1.3
groupVoltageThStatusStatus of the measured group voltage relative to the configured thresholds.Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.5.3.1.4
groupVoltageThLowerWarningLower warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.5.3.1.5
groupVoltageThLowerCriticalLower critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.5.3.1.6
groupVoltageThUpperWarningUpper warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.5.3.1.7
groupVoltageThUpperCriticalUpper critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.5.3.1.8
.1.3.6.1.4.1.534.6.6.7.5.4 · 1 row entry · 9 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk groupCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupCurrentTable'
A list of group current measurements.  There can be only one current
measurement for each group.
groupCurrentEntry row .1.3.6.1.4.1.534.6.6.7.5.4.1
An entry for a group current measurement.
Column Syntax OID
groupCurrentCapacityRated current capacity of the group. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown (it
will always be unknown for custom groups).
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.4.1.2
groupCurrentA group current measurement value. Units are milliamps.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.4.1.3
groupCurrentThStatusStatus of the measured group current relative to the configured thresholds.Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.5.4.1.4
groupCurrentThLowerWarningLower warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.5.4.1.5
groupCurrentThLowerCriticalLower critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.5.4.1.6
groupCurrentThUpperWarningUpper warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.5.4.1.7
groupCurrentThUpperCriticalUpper critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.5.4.1.8
groupCurrentCrestFactorCurrent crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.4.1.9
groupCurrentPercentLoadCurrent percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.4.1.10
.1.3.6.1.4.1.534.6.6.7.5.5 · 1 row entry · 6 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk groupPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupPowerTable'
A list of group power measurements.  There can be only one power
measurement for each group.
groupPowerEntry row .1.3.6.1.4.1.534.6.6.7.5.5.1
An entry for a group power measurement.
Column Syntax OID
groupVAA group VA value. Units are VA. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.5.1.2
groupWattsA group Watts value. Units are Watts. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.5.1.3
groupWhUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTotalTimer will be reset to 0 as well.
Unsigned32r/w
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.534.6.6.7.5.5.1.4
groupWhTimerTimestamp of when group Watt-hours (groupWh) was last reset.UnixTimeStamp.1.3.6.1.4.1.534.6.6.7.5.5.1.5
groupPowerFactorA group PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.5.1.6
groupVARA group VAR value. Units are VAR. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.5.5.1.7
.1.3.6.1.4.1.534.6.6.7.5.6 · 1 row entry · 4 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk groupControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::groupControlTable'
A list of controllable groups.
groupControlEntry row .1.3.6.1.4.1.534.6.6.7.5.6.1
An entry for a controllable group.
Column Syntax OID
groupControlStatusCurrent state of a controlled group. A value of 'mixed' means that
that the outlets within the group have differing states.
Enumeration
Enumerated Values:
0off
1on
2rebooting
3mixed
.1.3.6.1.4.1.534.6.6.7.5.6.1.2
groupControlOffCmdGroup-level outlet control command.

Once the command is issued, the outlets in the group will turn Off immediately.
0-n : Time in seconds until the group command is issued
-1 : Cancel a pending group-leve…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.5.6.1.3
groupControlOnCmdGroup-level outlet control command.

Once the command is issued, the outlets in the group will turn On immediately.
0-n : Time in seconds until the group command is issued
-1 : Cancel a pending group-level…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.5.6.1.4
groupControlRebootCmdGroup-level outlet control command.

For outlets that are On prior to the Reboot command, they will switch Off immediately when the command is
issued, remain Off for outletControlRebootOffTime seconds, and…
Integer32r/w
Constraints:
range: -1-0
.1.3.6.1.4.1.534.6.6.7.5.6.1.5

outletTable

table
.1.3.6.1.4.1.534.6.6.7.6.1 · 1 row entry · 7 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk outletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletTable'
A list of outlets.  The number of entries is given by outletCount.
outletEntry row .1.3.6.1.4.1.534.6.6.7.6.1.1
An entry for a particular outlet.
Column Syntax OID
outletIndexA unique value for each outlet. its value ranges from 1 to outletCount.Integer32
Constraints:
range: 1-64
.1.3.6.1.4.1.534.6.6.7.6.1.1.1
outletIDAlphanumeric designator for the outlet.OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.6.1.1.2
outletNameA descriptive name for the outlet.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.6.1.1.3
outletParentCountNumber of parents for this outlet.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.1.1.4
outletTypeThe physical type of outlet.Enumeration
Enumerated Values:
0unknown
1iecC13
2iecC19
3comboC39
10uk
11french
12schuko
20nema515
21nema51520
22nema520
23nemaL520
24nemaL530
25nema615
26nema620
27nemaL620
28nemaL630
29nemaL715
30rf203p277
31sdg300
32sdg400
.1.3.6.1.4.1.534.6.6.7.6.1.1.5
outletDesignatorAlphanumeric physical name for the outlet.OctetString
Constraints:
range: 2-4
.1.3.6.1.4.1.534.6.6.7.6.1.1.6
outletPhaseIDValue indicates which phases are connected to each outlet in this table row - single phase
voltage, phase 1 to neutral, phase 2 to neutral, phase 3 to neutral, phase 1 to phase 2,
phase 2 to phase 3, phase 3 to phase 1,…
Enumeration
Enumerated Values:
1singlePhase
2phase1toN
3phase2toN
4phase3toN
5phase1to2
6phase2to3
7phase3to1
8phase12N
9phase23N
10phase31N
11phase123
12phase123N
.1.3.6.1.4.1.534.6.6.7.6.1.1.7
.1.3.6.1.4.1.534.6.6.7.6.2 · 1 row entry · 3 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk outletParentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletParentTable'
A list of parents for this outlet.  For example, this table will link
to all of the groups that have this outlet as a child.
outletParentEntry row .1.3.6.1.4.1.534.6.6.7.6.2.1
An entry for a particular parent.
Column Syntax OID
outletParentIndexA unique value for each parent. Its value ranges from 1 to outletParentCount.Integer32
Constraints:
range: 1-32
.1.3.6.1.4.1.534.6.6.7.6.2.1.1
outletParentTypeThe type of the parent.Enumeration
Enumerated Values:
0unknown
1breaker
2section
3custom
.1.3.6.1.4.1.534.6.6.7.6.2.1.2
outletParentOIDObject ID of a parent object.ObjectIdentifier.1.3.6.1.4.1.534.6.6.7.6.2.1.3
.1.3.6.1.4.1.534.6.6.7.6.3 · 1 row entry · 6 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk outletVoltageTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletVoltageTable'
A list of outlet voltage measurements.
outletVoltageEntry row .1.3.6.1.4.1.534.6.6.7.6.3.1
An entry for an outlet voltage measurement.
Column Syntax OID
outletVoltageUnits are millivolts.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.3.1.2
outletVoltageThStatusStatus of the measured outlet voltage relative to the configured thresholds.Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.6.3.1.3
outletVoltageThLowerWarningLower warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.6.3.1.4
outletVoltageThLowerCriticalLower critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.6.3.1.5
outletVoltageThUpperWarningUpper warning threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.6.3.1.6
outletVoltageThUpperCriticalUpper critical threshold. Units are millivolts. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-500000
.1.3.6.1.4.1.534.6.6.7.6.3.1.7
.1.3.6.1.4.1.534.6.6.7.6.4 · 1 row entry · 9 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk outletCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletCurrentTable'
A list of outlet current measurements.
outletCurrentEntry row .1.3.6.1.4.1.534.6.6.7.6.4.1
An entry for an outlet current measurement.
Column Syntax OID
outletCurrentCapacityRated current capacity of the outlet. Units are milliamps. A negative
value indicates that the hardware current capacity is unknown.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.4.1.2
outletCurrentAn outlet current measurement value. Units are milliamps.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.4.1.3
outletCurrentThStatusStatus of the measured outlet current relative to the configured thresholds.
A negative value indicates that this object is not available.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.6.4.1.4
outletCurrentThLowerWarningLower warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.6.4.1.5
outletCurrentThLowerCriticalLower critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.6.4.1.6
outletCurrentThUpperWarningUpper warning threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.6.4.1.7
outletCurrentThUpperCriticalUpper critical threshold. Units are milliamps. A negative value indicates
that this object is not available.
Integer32r/w
Constraints:
range: -1-100000
.1.3.6.1.4.1.534.6.6.7.6.4.1.8
outletCurrentCrestFactorCurrent crest factor. Units are in milli, for example a crest factor of
1.414 will be returned as 1414. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.4.1.9
outletCurrentPercentLoadCurrent percent load, based on the rated current capacity. Units are
percentage, for example 80% will be returned as 80. A negative
value indicates that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.4.1.10
.1.3.6.1.4.1.534.6.6.7.6.5 · 1 row entry · 6 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk outletPowerTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletPowerTable'
A list of outlet power measurements.
outletPowerEntry row .1.3.6.1.4.1.534.6.6.7.6.5.1
An entry for an outlet power measurement.
Column Syntax OID
outletVAAn outlet VA value. Units are VA. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.5.1.2
outletWattsAn outlet Watts value. Units are Watts. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.5.1.3
outletWhUnits are Watt-hours. This object is writable so that it can be reset to 0. When it is
written to, the inputWhTotalTimer will be reset to 0 as well.
Unsigned32r/w
Constraints:
range: 0-4294967295
.1.3.6.1.4.1.534.6.6.7.6.5.1.4
outletWhTimerTimestamp of when outlet Watt-hours (outletWh) was last reset.UnixTimeStamp.1.3.6.1.4.1.534.6.6.7.6.5.1.5
outletPowerFactorAn outlet PF value. Units are in thousandths, for example a power factor
of 0.958 would be returned as 958, and 0.92 would be returned
as 920. A negative value indicates that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.5.1.6
outletVARAn outlet VAR value. Units are VAR. A negative value indicates
that this object is not available.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.6.5.1.7
.1.3.6.1.4.1.534.6.6.7.6.6 · 1 row entry · 9 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk outletControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletControlTable'
A list of controllable outlets.
outletControlEntry row .1.3.6.1.4.1.534.6.6.7.6.6.1
An entry for a controllable outlet.
Column Syntax OID
outletControlStatusCurrent state of a controlled outlet.Enumeration
Enumerated Values:
0off
1on
2pendingOff
3pendingOn
.1.3.6.1.4.1.534.6.6.7.6.6.1.2
outletControlOffCmdOutlet control command.

Once the command is issued, the outlet will turn Off immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pending outlet Off command

…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.3
outletControlOnCmdOutlet control command.

Once the command is issued, the outlet will turn On immediately.
0-n : Time in seconds until the outlet command is issued
-1 : Cancel a pending outlet On command

Wh…
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.4
outletControlRebootCmdOutlet control command.

For outlets that are On prior to this Reboot command, they will switch Off immediately when the command is
issued, remain Off for outletControlRebootOffTime seconds, and then turn …
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.5
outletControlPowerOnStateDetermines the outlet state when power is applied to the unit.
0 : not restart at device startup
1 : should sequence back ON in line with outletControlSequenceTime
2 : should take the state the outlet had when power was…
Enumerationr/w
Enumerated Values:
0off
1on
2lastState
.1.3.6.1.4.1.534.6.6.7.6.6.1.6
outletControlSequenceDelayTime delay in seconds from when a Global Sequence On command is issued to
when the command is executed on this outlet. This delay is also used as a power-on
delay. Set to -1 to exclude this outlet from Global Sequence …
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.7
outletControlRebootOffTimeTime delay in seconds that the outlet should remain in the Off state when executing a Reboot command.Integer32r/w
Constraints:
range: 1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.8
outletControlSwitchableDetermines the outlet capability to be controlled On/Off from the communication channels.
1 : control On/Off enabled
2 : control On/Off disabled.
Enumerationr/w
Enumerated Values:
1switchable
2notSwitchable
.1.3.6.1.4.1.534.6.6.7.6.6.1.9
outletControlShutoffDelayTime delay in seconds that could be taken in account before shutting of the outlet.
An application which need to shutoff properly an outlet will read this parameter first
then write it to the command outletControlOffCmd.
Integer32r/w
Constraints:
range: -1-99999
.1.3.6.1.4.1.534.6.6.7.6.6.1.10
.1.3.6.1.4.1.534.6.6.7.6.7 · 1 row entry · 1 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk outletGlobalTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::outletGlobalTable'
A list of globlal configuration on all outlets.
outletGlobalEntry row .1.3.6.1.4.1.534.6.6.7.6.7.1
An entry for a global variable on all outlets.
Indexes
Column Syntax OID
outletAutomaticShutoffDetermines the state of all outlets when the unit is power off:
0 : not applicable (read only)
1 : Keep the outlet relays in the current position when the PDU is powered down
2 : Makes the outlet relays go to the positi…
Enumerationr/w
Enumerated Values:
0notApplicable
1keepTheCurrentPosition
2shutoffTheOutlets
.1.3.6.1.4.1.534.6.6.7.6.7.1.2
.1.3.6.1.4.1.534.6.6.7.7.1 · 1 row entry · 9 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk temperatureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::temperatureTable'
A list of temperature probe measurements.  The number of entries is
given by temperatureCount.
temperatureEntry row .1.3.6.1.4.1.534.6.6.7.7.1.1
An entry for a temperature measurement.
Column Syntax OID
temperatureIndexA unique value for each temperature probe measurement. Its value
ranges from 1 to temperatureCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.6.7.7.1.1.1
temperatureNameA descriptive name for the temperature probe.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.7.1.1.2
temperatureProbeStatusIndicates whether a probe is connected or not.Enumeration
Enumerated Values:
-1bad
0disconnected
1connected
.1.3.6.1.4.1.534.6.6.7.7.1.1.3
temperatureValueUnits are in tenths of a degree according to the scale specified by
temperatureScale (either Fahrenheit or Celsius). Divide by ten to get
degrees.
SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.7.1.1.4
temperatureThStatusStatus of the measured temperature relative to the configured
thresholds.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.7.1.1.5
temperatureThLowerWarningLower warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-150000
.1.3.6.1.4.1.534.6.6.7.7.1.1.6
temperatureThLowerCriticalLower critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-150000
.1.3.6.1.4.1.534.6.6.7.7.1.1.7
temperatureThUpperWarningUpper warning threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-150000
.1.3.6.1.4.1.534.6.6.7.7.1.1.8
temperatureThUpperCriticalUpper critical threshold. Units are tenths of a degree. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-150000
.1.3.6.1.4.1.534.6.6.7.7.1.1.9
.1.3.6.1.4.1.534.6.6.7.7.2 · 1 row entry · 9 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk humidityTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::humidityTable'
A list of humidity probe measurements.  The number of entries is
given by humidityCount.
humidityEntry row .1.3.6.1.4.1.534.6.6.7.7.2.1
An entry for a humidity measurement.
Column Syntax OID
humidityIndexA unique value for each humidity probe measurement. Its value
ranges from 1 to humidityCount.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.534.6.6.7.7.2.1.1
humidityNameA descriptive name for the humidity probe.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.7.2.1.2
humidityProbeStatusIndicates whether a probe is connected or not.Enumeration
Enumerated Values:
-1bad
0disconnected
1connected
.1.3.6.1.4.1.534.6.6.7.7.2.1.3
humidityValueUnits are tenths of a percent relative humidity. Divide the value by 10 to get %RH.SNMPv2-SMIInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.534.6.6.7.7.2.1.4
humidityThStatusStatus of the measured humidity relative to the configured
thresholds.
Enumeration
Enumerated Values:
0good
1lowWarning
2lowCritical
3highWarning
4highCritical
.1.3.6.1.4.1.534.6.6.7.7.2.1.5
humidityThLowerWarningLower warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-1000
.1.3.6.1.4.1.534.6.6.7.7.2.1.6
humidityThLowerCriticalLower critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-1000
.1.3.6.1.4.1.534.6.6.7.7.2.1.7
humidityThUpperWarningUpper warning threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-1000
.1.3.6.1.4.1.534.6.6.7.7.2.1.8
humidityThUpperCriticalUpper critical threshold. Units are 0.1 %RH. A negative value
indicates that this object is not available.
Integer32r/w
Constraints:
range: -1-1000
.1.3.6.1.4.1.534.6.6.7.7.2.1.9

contactTable

table
.1.3.6.1.4.1.534.6.6.7.7.3 · 1 row entry · 4 columns
Uses the eaton variant from /opt/observium/mibs/eaton.
Command help
Walk contactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'EATON-EPDU-MIB' -M '/opt/observium/mibs/eaton:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'EATON-EPDU-MIB::contactTable'
A list of contact sensors.  The number of entries is
given by contactCount.
contactEntry row .1.3.6.1.4.1.534.6.6.7.7.3.1
An entry for a contact sensor
Column Syntax OID
contactIndexA unique value for each contact sensor. Its value ranges from 1 to
contactCount.
Integer32
Constraints:
range: 1-3
.1.3.6.1.4.1.534.6.6.7.7.3.1.1
contactNameA descriptive name for the contact sensor.OctetStringr/w
Constraints:
range: 1-31
.1.3.6.1.4.1.534.6.6.7.7.3.1.2
contactProbeStatusIndicates whether a probe is connected or not.
Will not be returned if the contact sensor is internal to the ePDU,
in that case only contactState should be read.
Enumeration
Enumerated Values:
-1bad
0disconnected
1connected
.1.3.6.1.4.1.534.6.6.7.7.3.1.3
contactStateThe state of the contact sensor.Enumeration
Enumerated Values:
-1contactBad
0contactOpen
1contactClosed
.1.3.6.1.4.1.534.6.6.7.7.3.1.4