DeltaEMS-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
2
Rows
2
Columns
31

demsMonitorTable

table mandatory
.1.3.6.1.4.1.2254.2.501.1.1 · 1 row entry · 13 columns
Uses the delta variant from /opt/observium/mibs/delta.
Command help
Walk demsMonitorTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DeltaEMS-MIB' -M '/opt/observium/mibs/delta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DeltaEMS-MIB::demsMonitorTable'
A list of EMS1000 information table entries.
demsMonitorEntry row .1.3.6.1.4.1.2254.2.501.1.1.1
An entry containing EMS1000 information.
Indexes
Column Syntax OID
demsDeviceIDmandatory
The EMS1000 device ID.
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.2254.2.501.1.1.1.1
demsEnablemandatory
Eanble/Disble EMS1000 Device.
Enumeration
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2254.2.501.1.1.1.2
The communication status.Enumeration
Enumerated Values:
1disconnect
2connect
.1.3.6.1.4.1.2254.2.501.1.1.1.3
The ambient environmental temperature.0.1 degrees CentigradeInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.1.1.1.4
demsHumiditymandatory
The environmental humidity.
percentageInteger32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.1.1.1.5
Does the environment over warning temperature?Enumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2254.2.501.1.1.1.6
Does the environment over warning humidity?Enumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2254.2.501.1.1.1.7
Does the environment over alarm temperature?Enumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2254.2.501.1.1.1.8
Does the environment over alarm humidity?Enumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2254.2.501.1.1.1.9
Get EMS1000 relay 1 statusEnumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2254.2.501.1.1.1.10
Get EMS1000 relay 2 statusEnumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2254.2.501.1.1.1.11
Get EMS1000 relay 3 statusEnumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2254.2.501.1.1.1.12
Get EMS1000 relay 4 statusEnumeration
Enumerated Values:
1on
2off
.1.3.6.1.4.1.2254.2.501.1.1.1.13

demsConfigureTable

table mandatory
.1.3.6.1.4.1.2254.2.501.2.1 · 1 row entry · 18 columns
Uses the delta variant from /opt/observium/mibs/delta.
Command help
Walk demsConfigureTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DeltaEMS-MIB' -M '/opt/observium/mibs/delta:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DeltaEMS-MIB::demsConfigureTable'
A list of EMS1000 Configuration table entries.
demsConfigureEntry row .1.3.6.1.4.1.2254.2.501.2.1.1
An entry containing EMS1000 configuration information.
Indexes
Column Syntax OID
The EMS1000 device ID.Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.2254.2.501.2.1.1.1
demsSetEnablemandatory
Eanble/Disble EMS1000 Device.
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.2254.2.501.2.1.1.2
Warning demsOverWarnTemperature on when the environmental
temperature over the value.
0.1 degrees CentigradeInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.2.1.1.3
Warning demsOverWarnHumidity on when the environmental
humidity over the value.
percentageInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.2.1.1.4
Alarm demsOverAlarmTemperature on when the environmental
temperature over the value.
0.1 degrees CentigradeInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.2.1.1.5
Alarm demsOverAlarmHumidity on when the environmental
humidity over the value.
percentageInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.2.1.1.6
Get/Set the recovery from Warning Temperature value.0.1 degrees CentigradeInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.2.1.1.11
Get/Set the recovery from Warning Humidity value.Degrees CentigradeInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.2.1.1.12
Get/Set the recovery from alarm Temperature value.0.1 degrees CentigradeInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.2.1.1.13
Get/Set the recovery from alarm Humidity value.Degrees CentigradeInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.2254.2.501.2.1.1.14
Get/Set the EMS1000 device title.RFC1213-MIBDisplayStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2254.2.501.2.1.1.15
Get/Set relay1 title.RFC1213-MIBDisplayStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2254.2.501.2.1.1.16
Get/Set relay2 title.RFC1213-MIBDisplayStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2254.2.501.2.1.1.17
Get/Set relay3 title.RFC1213-MIBDisplayStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2254.2.501.2.1.1.18
Get/Set relay3 title.RFC1213-MIBDisplayStringr/w
Constraints:
range: 0-32
.1.3.6.1.4.1.2254.2.501.2.1.1.19
Get/Set device temperature offset0.1TInteger32r/w
Constraints:
range: 0-1000
.1.3.6.1.4.1.2254.2.501.2.1.1.24
Get/Set device humidity offset%Integer32r/w
Constraints:
range: 0-200
.1.3.6.1.4.1.2254.2.501.2.1.1.25
Get/Set device temperature unitEnumerationr/w
Enumerated Values:
1celsius
2fahrenheit
.1.3.6.1.4.1.2254.2.501.2.1.1.26