DKSF-57-1-X-X-1 Table View

Table-centric layout grouping table, row, and column objects.

Tables
8
Rows
8
Columns
52

npRelayTable

table
.1.3.6.1.4.1.25728.5500.5 · 1 row entry · 6 columns
Uses the netping variant from /opt/observium/mibs/netping.
Command help
Walk npRelayTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DKSF-57-1-X-X-1' -M '/opt/observium/mibs/netping:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DKSF-57-1-X-X-1::npRelayTable'
Relay control table
npRelayEntry row .1.3.6.1.4.1.25728.5500.5.1
Relay/outlet table row
Indexes
Column Syntax OID
The N of output relay
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.25728.5500.5.1.1
Control of relay:
-1 - flip between on(1) and off(0)
0 - switch off
1 - switch on
Enumerationr/w
Enumerated Values:
-1flip
0off
1on
.1.3.6.1.4.1.25728.5500.5.1.2
Write 1 to start reset (switch relay off for some time)
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.25728.5500.5.1.3
Relay memo
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.5500.5.1.6
Write -1 to flip between manual on and manual off states of relay
Enumerationr/w
Enumerated Values:
-1flip
.1.3.6.1.4.1.25728.5500.5.1.14
Actual relay state at the moment,
regardless of source of control.
0 - relay is off
1 - relay is on
Enumeration
Enumerated Values:
0off
1on
.1.3.6.1.4.1.25728.5500.5.1.15
.1.3.6.1.4.1.25728.5800.3 · 1 row entry · 4 columns
Uses the netping variant from /opt/observium/mibs/netping.
Command help
Walk npPwrWdogTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DKSF-57-1-X-X-1' -M '/opt/observium/mibs/netping:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DKSF-57-1-X-X-1::npPwrWdogTable'
Watchdog Control Table
npPwrWdogEntry row .1.3.6.1.4.1.25728.5800.3.1
Watchdog Control Table Row
Column Syntax OID
The N of watchdog/power channel
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.25728.5800.3.1.1
Counter of watchdog resets
Write 0 to clear.
Integer32r/w
Constraints:
range: 0-65535
.1.3.6.1.4.1.25728.5800.3.1.4
Counter of continous failed
watchdog resets
Integer32
Constraints:
range: 0-65535
.1.3.6.1.4.1.25728.5800.3.1.5
Watchdog channel memo
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.5800.3.1.6
.1.3.6.1.4.1.25728.8400.1 · 1 row entry · 10 columns
Uses the netping variant from /opt/observium/mibs/netping.
Command help
Walk npRelHumTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DKSF-57-1-X-X-1' -M '/opt/observium/mibs/netping:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DKSF-57-1-X-X-1::npRelHumTable'
Humidity+Temperature Sensors Table
npRelHumEntry row .1.3.6.1.4.1.25728.8400.1.1
Humidity+Temperature Sensors Table Row
Indexes
Column Syntax OID
Index of Humidity+Temperature sensor, 1 to max supported
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.25728.8400.1.1.1
Relative humidity value, %
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.25728.8400.1.1.2
Status of Relative Humiduty
Enumeration
Enumerated Values:
0sensorFailed
1belowSafeRange
2inSafeRange
3aboveSafeRange
.1.3.6.1.4.1.25728.8400.1.1.3
Sensor temperature, deg.C
Integer32
Constraints:
range: -60-200
.1.3.6.1.4.1.25728.8400.1.1.4
Status of Relative Humiduty
Enumeration
Enumerated Values:
0sensorFailed
1belowSafeRange
2inSafeRange
3aboveSafeRange
.1.3.6.1.4.1.25728.8400.1.1.5
Sensor Memo/Location
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.8400.1.1.6
Relative Humidity safe range, top margin, %RH
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.25728.8400.1.1.7
Relative Humidity safe range, bottom margin, %RH
Integer32
Constraints:
range: 0-100
.1.3.6.1.4.1.25728.8400.1.1.8
Temperature safe range, top margin, deg.C
Integer32
Constraints:
range: -55-150
.1.3.6.1.4.1.25728.8400.1.1.9
Temperature safe range, bottom margin, deg.C
Integer32
Constraints:
range: -55-150
.1.3.6.1.4.1.25728.8400.1.1.10
.1.3.6.1.4.1.25728.8800.1 · 1 row entry · 7 columns
Uses the netping variant from /opt/observium/mibs/netping.
Command help
Walk npThermoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DKSF-57-1-X-X-1' -M '/opt/observium/mibs/netping:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DKSF-57-1-X-X-1::npThermoTable'
Thermo Sensors Table
npThermoEntry row .1.3.6.1.4.1.25728.8800.1.1
Thermo Sensors Table Row
Indexes
Column Syntax OID
The id of temperature sensor, 1 to 8
Integer32
Constraints:
range: 1-8
.1.3.6.1.4.1.25728.8800.1.1.1
Temperature, deg.C
Integer32
Constraints:
range: -60-280
.1.3.6.1.4.1.25728.8800.1.1.2
Temperature status (0=fault, 1=underheat, 2=normal, 3=overheat)
Enumeration
Enumerated Values:
0failed
1low
2norm
3high
.1.3.6.1.4.1.25728.8800.1.1.3
Bottom margin of normal temperature range, deg.C
Integer32
Constraints:
range: -60-280
.1.3.6.1.4.1.25728.8800.1.1.4
Top margin of normal temperature range, deg.C
Integer32
Constraints:
range: -60-280
.1.3.6.1.4.1.25728.8800.1.1.5
T channel memo
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.8800.1.1.6
Temperature, deg.C, with fractional part 3 digits after point
FixedPoint1000 .1.3.6.1.4.1.25728.8800.1.1.7

npIoTable

table
.1.3.6.1.4.1.25728.8900.1 · 1 row entry · 8 columns
Uses the netping variant from /opt/observium/mibs/netping.
Command help
Walk npIoTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DKSF-57-1-X-X-1' -M '/opt/observium/mibs/netping:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DKSF-57-1-X-X-1::npIoTable'
Digital Input/output Table
npIoEntry row .1.3.6.1.4.1.25728.8900.1.1
Digital Input/output Table Row
Indexes
Column Syntax OID
Number of IO line, from 1 to max supported
Integer32
Constraints:
range: 1-20
.1.3.6.1.4.1.25728.8900.1.1.1
Input level, 0 or 1
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.25728.8900.1.1.2
Output level, 0 or 1.
Write -1 to flip output.
Enumerationr/w
Enumerated Values:
-1flip
0low
1high
.1.3.6.1.4.1.25728.8900.1.1.3
IO line memo
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.8900.1.1.6
Legend for current logic level on the IO line
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.8900.1.1.7
Pulse Counter on IO input line (counts positive fronts)
Write 0 to reset.
SNMPv2-SMICounter32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.8900.1.1.9
Set duration of single pulse on IO output line,
100ms to 25500ms, min. step is 100ms
Integer32r/w
Constraints:
range: 100-25500
.1.3.6.1.4.1.25728.8900.1.1.12
Write 1 to start single pulse on IO output.
Output will be inverted for time, specified by npIoSinglePulseDuration
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.25728.8900.1.1.13

npInTable

table
.1.3.6.1.4.1.25728.8910.1 · 1 row entry · 5 columns
Uses the netping variant from /opt/observium/mibs/netping.
Command help
Walk npInTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DKSF-57-1-X-X-1' -M '/opt/observium/mibs/netping:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DKSF-57-1-X-X-1::npInTable'
Discrete Inputs Table
npInEntry row .1.3.6.1.4.1.25728.8910.1.1
Discrete Inputs Table Row
Indexes
Column Syntax OID
Number of the Input, from 1 to max supported
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.25728.8910.1.1.1
Input level, 0 or 1
Integer32
Constraints:
range: 0-1
.1.3.6.1.4.1.25728.8910.1.1.2
Input memo
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.8910.1.1.6
Legend for current logic level on the Input
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.8910.1.1.7
Pulse Counter on the Input (counts positive fronts)
Write 0 to reset.
SNMPv2-SMICounter32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.8910.1.1.9

npOutTable

table
.1.3.6.1.4.1.25728.8920.1 · 1 row entry · 7 columns
Uses the netping variant from /opt/observium/mibs/netping.
Command help
Walk npOutTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DKSF-57-1-X-X-1' -M '/opt/observium/mibs/netping:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DKSF-57-1-X-X-1::npOutTable'
Discrete Output Table
npOutEntry row .1.3.6.1.4.1.25728.8920.1.1
Discrete Output Table Row
Indexes
Column Syntax OID
Number of the Output, from 1 to max supported
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.25728.8920.1.1.1
Output level, 0 or 1.
Write -1 to flip output.
Enumerationr/w
Enumerated Values:
-1flip
0low
1high
.1.3.6.1.4.1.25728.8920.1.1.3
Output line memo
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.8920.1.1.6
Legend for current logic level on the Output
SNMPv2-TCDisplayString
Type Constraints:
range: 0..255
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.25728.8920.1.1.7
Pulse Counter on the Output line (counts positive fronts)
Write 0 to reset.
SNMPv2-SMICounter32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.8920.1.1.9
Set duration of single pulse on the Output line,
100ms to 25500ms, min. step is 100ms
Integer32r/w
Constraints:
range: 100-25500
.1.3.6.1.4.1.25728.8920.1.1.12
Write 1 to start single pulse on the Output.
Output will be inverted for time, specified by npOutSinglePulseDuration
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.25728.8920.1.1.13

npElecTable

table
.1.3.6.1.4.1.25728.9700.1 · 1 row entry · 5 columns
Uses the netping variant from /opt/observium/mibs/netping.
Command help
Walk npElecTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DKSF-57-1-X-X-1' -M '/opt/observium/mibs/netping:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DKSF-57-1-X-X-1::npElecTable'
Electricity Meter Table
npElecEntry row .1.3.6.1.4.1.25728.9700.1.1
Electricity Meter Table Table Row
Indexes
Column Syntax OID
Number of elec.meter, associated with IO line
Integer32
Constraints:
range: 1-16
.1.3.6.1.4.1.25728.9700.1.1.1
Pulses on IO line input per 1 kWh of consumed energy
SNMPv2-SMIInteger32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.25728.9700.1.1.2
Power, Watts, based on pulse rate/interval, 5 minute average
SNMPv2-SMIGauge32
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.9700.1.1.3
Energy counter, kWh, based on pulse count
SNMPv2-SMICounter32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.9700.1.1.4
Energy counter, kWh*100, based on pulse count
SNMPv2-SMICounter32r/w
Type Constraints:
range: 0..4294967295
.1.3.6.1.4.1.25728.9700.1.1.5