DCMCU3000-MIB Table View

Table-centric layout grouping table, row, and column objects.

Tables
3
Rows
3
Columns
20
.1.3.6.1.4.1.27383.6.1.2.12 · 1 row entry · 4 columns
Uses the benning variant from /opt/observium/mibs/benning.
Command help
Walk dcPowerSystemClientSpecificMeasurementTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DCMCU3000-MIB' -M '/opt/observium/mibs/benning:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DCMCU3000-MIB::dcPowerSystemClientSpecificMeasurementTable'
A list of client specific measurement entries.
dcPowerSystemClientSpecificMeasurementEntry row .1.3.6.1.4.1.27383.6.1.2.12.1
An entry containing information applicable to a particular client
specific measurement entry.
Column Syntax OID
dcPowerSystemClientSpecificMeasurementIdA unique identifier for a client specific measurement value.
This value must remain constant.
PositiveInteger
Type Constraints:
range: 1..2147483647
Description:
This data type is a non-zero and non-negative value.
.1.3.6.1.4.1.27383.6.1.2.12.1.1
dcPowerSystemClientSpecificMeasurementDescriptionThe client specific measurement decscription.SNMPv2-TCDisplayString
Constraints:
range: 0-63
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.27383.6.1.2.12.1.2
dcPowerSystemClientSpecificMeasurementValueThis value shows the current client specifc measurement value.FixedPointNumber
Type Constraints:
range: -2147483648..2147483647
Description:
This data type is a fixed point value with
two decimal places.
.1.3.6.1.4.1.27383.6.1.2.12.1.3
dcPowerSystemClientSpecificMeasurementUnitA description of the client specific measurement unit.SNMPv2-TCDisplayString
Constraints:
range: 0-8
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.27383.6.1.2.12.1.4
.1.3.6.1.4.1.27383.6.1.4.2 · 1 row entry · 11 columns
Uses the benning variant from /opt/observium/mibs/benning.
Command help
Walk dcRectifierTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DCMCU3000-MIB' -M '/opt/observium/mibs/benning:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DCMCU3000-MIB::dcRectifierTable'
A list of rectifier table entries.
The number of entries is given by the value of dcRectifierNumRectifiers.
dcRectifierEntry row .1.3.6.1.4.1.27383.6.1.4.2.1
An entry containing information applicable to a particular rectifier.
Column Syntax OID
dcRectifierIndexThe rectifier identifier.PositiveInteger
Type Constraints:
range: 1..2147483647
Description:
This data type is a non-zero and non-negative value.
.1.3.6.1.4.1.27383.6.1.4.2.1.1
dcRectifierFirmwareVersionThe rectifier's firmware version.SNMPv2-TCDisplayString
Constraints:
range: 0-15
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.27383.6.1.4.2.1.2
dcRectifierStatusThe current state of the rectifier. Rectifiers can be on or off.Enumeration
Enumerated Values:
1off
2on
.1.3.6.1.4.1.27383.6.1.4.2.1.3
dcRectifierModuleFaultThe current state of the retifier module fault.Enumeration
Enumerated Values:
1true
2false
.1.3.6.1.4.1.27383.6.1.4.2.1.4
dcRectifierFanFaultThe current state of the retifier fan fault.Enumeration
Enumerated Values:
1true
2false
.1.3.6.1.4.1.27383.6.1.4.2.1.5
dcRectifierMainsFaultThe current state of the retifier mains fault.Enumeration
Enumerated Values:
1true
2false
.1.3.6.1.4.1.27383.6.1.4.2.1.6
dcRectifierVoltageThe magnitude of the rectifier voltage.Volt DCFixedPointNumber
Type Constraints:
range: -2147483648..2147483647
Description:
This data type is a fixed point value with
two decimal places.
.1.3.6.1.4.1.27383.6.1.4.2.1.7
dcRectifierCurrentThe magnitude of the present rectifier current.Amp DCFixedPointNumber
Type Constraints:
range: -2147483648..2147483647
Description:
This data type is a fixed point value with
two decimal places.
.1.3.6.1.4.1.27383.6.1.4.2.1.8
dcRectifierAddressThe address of the rectifier in the system.NonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.27383.6.1.4.2.1.9
dcRectifierSerialNumberThe rectifier's serial number.SNMPv2-TCDisplayString
Constraints:
range: 0-15
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.27383.6.1.4.2.1.10
dcRectifierOperatingHoursThe operating hours of the rectifier.hoursNonNegativeInteger
Type Constraints:
range: 0..2147483647
Description:
This data type is a non-negative value.
.1.3.6.1.4.1.27383.6.1.4.2.1.11

dcAlarmTable

table
.1.3.6.1.4.1.27383.6.1.11.2 · 1 row entry · 5 columns
Uses the benning variant from /opt/observium/mibs/benning.
Command help
Walk dcAlarmTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'DCMCU3000-MIB' -M '/opt/observium/mibs/benning:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'DCMCU3000-MIB::dcAlarmTable'
A list of alarm entries.
dcAlarmEntry row .1.3.6.1.4.1.27383.6.1.11.2.1
An entry containing information applicable to a particular alarm.
Indexes
Column Syntax OID
dcAlarmIdA unique identifier for an alarm condition. This value must remain constant.PositiveInteger
Type Constraints:
range: 1..2147483647
Description:
This data type is a non-zero and non-negative value.
.1.3.6.1.4.1.27383.6.1.11.2.1.1
dcAlarmWellKnownDescriptionA reference to an alarm description object. The object referenced should not be
accessible, but rather be used to provide a unique description of the alarm condition.
SNMPv2-TCAutonomousType
Description:
Represents an independently extensible type identification
value. It may, for example, indicate a particular sub-tree
with further MIB definitions, or define a particular type of
protocol or hardware.
.1.3.6.1.4.1.27383.6.1.11.2.1.2
dcAlarmTimeThe value of sysUpTime when the alarm condition was detected. If the alarm
condition was detected at the time of agent startup and presumably existed before
agent startup, the value of dcAlarmTime shall equal 0.
SNMPv2-TCTimeStamp
Based On: SNMPv2-SMITimeTicks
Description:
The value of the sysUpTime object at which a specific
occurrence happened. The specific occurrence must be

defined in the description of any object defined using this
type.

If sysUpTime is reset t…
.1.3.6.1.4.1.27383.6.1.11.2.1.3
dcAlarmStateThis value shows the current alarm state.AlarmState
Type Values:
1notActive
2active
3notPresent
Description:
This data type indicates the state of an alarm.
.1.3.6.1.4.1.27383.6.1.11.2.1.4
dcAlarmDescriptionA description of the alarm condition.SNMPv2-TCDisplayString
Constraints:
range: 0-63
Description:
Represents textual information taken from the NVT ASCII

character set, as defined in pages 4, 10-11 of RFC 854.

To summarize RFC 854, the NVT ASCII repertoire specifies:

- the use of c…
.1.3.6.1.4.1.27383.6.1.11.2.1.5