A ciscoEnvMonShutdownNotification is sent if the environmental
monitor detects a testpoint reaching a critical state
and is about to initiate a shutdown. This notification
contains no objects so that it may be encoded and sent in the
shortest amount of time possible. Even so, management
applications should not rely on receiving such a notification
as it may not be sent before the shutdown completes.
ciscoEnvMonVoltageNotification
.1.3.6.1.4.1.9.9.13.3.0.2
A ciscoEnvMonVoltageNotification is sent if the voltage
measured at a given testpoint is outside the normal range
for the testpoint (i.e. is at the warning, critical, or
shutdown stage). Since such a notification is usually
generated before the shutdown state is reached, it can
convey more data and has a better chance of being sent
than does the ciscoEnvMonShutdownNotification.
This notification is deprecated in favour of
ciscoEnvMonVoltStatusChangeNotif.
ciscoEnvMonTemperatureNotification
.1.3.6.1.4.1.9.9.13.3.0.3
A ciscoEnvMonTemperatureNotification is sent if the
temperature measured at a given testpoint is outside
the normal range for the testpoint (i.e. is at the warning,
critical, or shutdown stage). Since such a Notification
is usually generated before the shutdown state is reached,
it can convey more data and has a better chance of being
sent than does the ciscoEnvMonShutdownNotification.
This notification is deprecated in favour of
ciscoEnvMonTempStatusChangeNotif.
ciscoEnvMonFanNotification
.1.3.6.1.4.1.9.9.13.3.0.4
A ciscoEnvMonFanNotification is sent if any one of
the fans in the fan array (where extant) fails.
Since such a notification is usually generated before
the shutdown state is reached, it can convey more
data and has a better chance of being sent
than does the ciscoEnvMonShutdownNotification.
This notification is deprecated in favour of
ciscoEnvMonFanStatusChangeNotif.
ciscoEnvMonRedundantSupplyNotification
.1.3.6.1.4.1.9.9.13.3.0.5
A ciscoEnvMonRedundantSupplyNotification is sent if
the redundant power supply (where extant) fails.
Since such a notification is usually generated before
the shutdown state is reached, it can convey more
data and has a better chance of being sent
than does the ciscoEnvMonShutdownNotification.
This notification is deprecated in favour of
ciscoEnvMonSuppStatusChangeNotif.
ciscoEnvMonVoltStatusChangeNotif
.1.3.6.1.4.1.9.9.13.3.0.6
A ciscoEnvMonVoltStatusChangeNotif is sent if there is
change in the state of a device being monitored
by ciscoEnvMonVoltageState.
ciscoEnvMonTempStatusChangeNotif
.1.3.6.1.4.1.9.9.13.3.0.7
A ciscoEnvMonTempStatusChangeNotif is sent if there
is change in the state of a device being monitored
by ciscoEnvMonTemperatureState.
ciscoEnvMonFanStatusChangeNotif
.1.3.6.1.4.1.9.9.13.3.0.8
A ciscoEnvMonFanStatusChangeNotif is sent if there
is change in the state of a device being monitored
by ciscoEnvMonFanState.
ciscoEnvMonSuppStatusChangeNotif
.1.3.6.1.4.1.9.9.13.3.0.9
A ciscoEnvMonSupplyStatChangeNotif is sent if there
is change in the state of a device being monitored
by ciscoEnvMonSupplyState.