Baytech-MIB-401-4 Table View
Table-centric layout grouping table, row, and column objects.
Tables
11
Rows
11
Columns
116
.1.3.6.1.4.1.4779.1.2.8.4
·
1 row entry
·
2 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sBTANetworkConfigSNMPTrapReceiverTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sBTANetworkConfigSNMPTrapReceiverTable'
A list of managers to send traps to. The number of entries is given by the value of sBTANetworkConfigSNMPNumTrapReceivers. Maximum number of Trap Receivers is four.
Table of managers to send traps to.
Indexes
| Column | Syntax | OID |
|---|---|---|
trapIndexmandatory The index to a trap receiver entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.2.8.4.1.1 |
receiverAddressmandatory The IP address of the manager to send traps to. | RFC1155-SMIIpAddressr/w Type Constraints: range: 4 | .1.3.6.1.4.1.4779.1.2.8.4.1.2 |
.1.3.6.1.4.1.4779.1.3.5.2
·
1 row entry
·
24 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sBTAModulesRPCTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sBTAModulesRPCTable'
Allows for control of individual outlets and individual RPC modules.
The RPCs to control and get status on.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
sBTAModulesRPCIndexmandatory The index into the RPC table. Indexes for rpcs attached to ds74 modules are calculate with the following formula:((module - 2) * 4) + port. For example module 3 port 1 = index 5. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.1 | ||||||||||||||
sBTAModulesRPCNamemandatory The name (unit id) of the rpc. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.4779.1.3.5.2.1.2 | ||||||||||||||
sBTAModulesRPCFirmwareVersionmandatory The firware version of the rpc. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.4779.1.3.5.2.1.3 | ||||||||||||||
sBTAModulesRPCCurrentmandatory The current reading for the power strip.If current measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.4 | ||||||||||||||
sBTAModulesRPCMaxCurrentmandatory The maximum detected current reading for the power strip.If current measurement is not installed this value will always read 0. Setting this value to 0 will clear the maximum current detected. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.5 | ||||||||||||||
sBTAModulesRPCVoltagemandatory The voltage reading for the power strip.If voltage measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.6 | ||||||||||||||
sBTAModulesRPCPowermandatory The power reading for the power strip.If power measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.7 | ||||||||||||||
sBTAModulesRPCTemperaturemandatory The temperature reading for the power strip. Readings are in degrees C.If temperature measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.8 | ||||||||||||||
sBTAModulesRPCRebootTimeoutmandatory The length of off time for automatic reboot sequences.Currently a read-only value set to the fixed reboot timeout. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.9 | ||||||||||||||
sBTAModulesRPCAllOutletsCmdmandatory Turns all outlets on, off or reboot.0 = off 1 = on 2 = reboot A get will return unknown (6). | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.4779.1.3.5.2.1.10 | ||||||||||||||
sBTAModulesRPCAllOutletsStatusmandatory Reports status of outlets in a comma deliminated string.0 = off 1 = on 2 = reboot 3 = locked on 4 = locked off | RFC1213-MIBDisplayString | .1.3.6.1.4.1.4779.1.3.5.2.1.11 | ||||||||||||||
sBTAModulesRPCCurrentAlarmThresholdmandatory The current alarm threshold level *10. A value of 105 will set the level to 10.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.12 | ||||||||||||||
sBTAModulesRPCOverVoltageThresholdmandatory The over voltage alarm threshold level *10. A value of 105 will set the level to 10.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.13 | ||||||||||||||
sBTAModulesRPCUnderVoltageThresholdmandatory The under voltage alarm threshold level *10. A value of 105 will set the level to 10.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.14 | ||||||||||||||
sBTAModulesRPCNumberOfOutletsmandatory Number of outlets for this RPC.This will be the size of outlet table for this RPC index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.15 | ||||||||||||||
sBTAModulesRPCCircuitBreakermandatory Status of circuit breaker in power strip. 0=off 1=on. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.4779.1.3.5.2.1.16 | ||||||||||||||
sBTAModulesRPCOverTempThresholdmandatory The over temperature alarm threshold level *10. A value of 505 will set the level to 50.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.17 | ||||||||||||||
sBTAModulesRPCUnitVAmandatory Total Volt-Amps for this RPC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.18 | ||||||||||||||
sBTAModulesRPCNumberOfBreakersmandatory Number of breakers for this RPC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.19 | ||||||||||||||
sBTAModulesRPCLowCurrentThresholdmandatory Low current threshold for this RPC. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.20 | ||||||||||||||
sBTAModulesRPCVoltageSourcemandatory Voltage source for this RPC. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.21 | ||||||||||||||
sBTAModulesRPCSourceSwitchCountmandatory Count of Voltage Source Switches for this RPC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.22 | ||||||||||||||
sBTAModulesRPCNumberOfSensorsmandatory Number of environmental sensors for this RPC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.2.1.23 | ||||||||||||||
sBTAModulesRPCTypemandatory The type of RPC installed at the indexed location. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.4779.1.3.5.2.1.24 |
.1.3.6.1.4.1.4779.1.3.5.3
·
1 row entry
·
4 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sBTAModulesRPCOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sBTAModulesRPCOutletTable'
Allows for control of individual outlets. The number of entries is contained in the sBTAModulesRPCOutletTableSize OID.
The outlets to control and get status on.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
sBTAModulesRPCOutletModuleIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.3.1.1 | ||||||||||||||
sBTAModulesRPCOutletIndexmandatory The index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.3.1.2 | ||||||||||||||
sBTAModulesRPCOutletStatemandatory Getting this variable will return the state of the outlet.Valid return states are unknown, on, off, lockon, lockoff. 0 = off 1 = on 2 = reboot 3 = lockon (outlet is on and no changes are allowed) 4 = lockoff (outlet is… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.4779.1.3.5.3.1.3 | ||||||||||||||
sBTAModulesRPCOutletNamemandatory The name of the outlet. Maximum size is 16 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.4779.1.3.5.3.1.4 |
.1.3.6.1.4.1.4779.1.3.5.5
·
1 row entry
·
25 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sBTAModulesRPCModPortTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sBTAModulesRPCModPortTable'
Allows for control of individual outlets and individual RPC modules. The number of entries is contained in the sBTAModulesNumberOfRPCModules OID.
The RPCs to control and get status on.
Indexes
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
sRPCModuleIndexmandatory The module number index into the RPC table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.1 | ||||||||||||||
sRPCPortIndexmandatory The port number index into the RPC table. In the case of ds30 modules this number is always 1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.2 | ||||||||||||||
sRPCTypemandatory Type of RPC at the module, port index. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.4779.1.3.5.5.1.3 | ||||||||||||||
sRPCNamemandatory The name (unit id) of the rpc module. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.4779.1.3.5.5.1.4 | ||||||||||||||
sRPCFirmwareVersionmandatory The firware version of the rpc module. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.4779.1.3.5.5.1.5 | ||||||||||||||
sRPCCurrentmandatory The current reading for the power strip.If current measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.6 | ||||||||||||||
sRPCMaxCurrentmandatory The maximum detected current reading for the power strip.If current measurement is not installed this value will always read 0. Setting this value to 0 will clear the maximum current detected. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.7 | ||||||||||||||
sRPCVoltagemandatory The voltage reading for the power strip.If voltage measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.8 | ||||||||||||||
sRPCPowermandatory The power reading for the power strip.If power measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.9 | ||||||||||||||
sRPCTemperaturemandatory The temperature reading for the power strip. Readings are in degrees C.If temperature measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.10 | ||||||||||||||
sRPCRebootTimeoutmandatory The length of off time for automatic reboot sequences.Currently a read-only value set to the fixed reboot timeout. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.11 | ||||||||||||||
sRPCAllOutletsCmdmandatory Turns all outlets on, off or reboot.0 = off 1 = on 2 = reboot 3 = lockon (will lock outlets to on state) 4 = lockoff (will lock outlets to off state) 5 = unlock (will unlock all outlets) A get will retur… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.4779.1.3.5.5.1.12 | ||||||||||||||
sRPCAllOutletsStatusmandatory Reports status of outlets in a comma deliminated string.0 = off 1 = on 2 = reboot 3 = locked on 4 = locked off | RFC1213-MIBDisplayString | .1.3.6.1.4.1.4779.1.3.5.5.1.13 | ||||||||||||||
sRPCCurrentAlarmThresholdmandatory The current alarm threshold level *10. A value of 105 will set the level to 10.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.14 | ||||||||||||||
sRPCOverVoltageThresholdmandatory The over voltage alarm threshold level *10. A value of 105 will set the level to 10.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.15 | ||||||||||||||
sRPCUnderVoltageThresholdmandatory The under voltage alarm threshold level *10. A value of 105 will set the level to 10.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.16 | ||||||||||||||
sRPCNumberOfOutletsmandatory Number of outlets for this RPC.This will be the size of outlet table for this RPC index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.17 | ||||||||||||||
sRPCCircuitBreakermandatory Status of circuit breaker in power strip. 0=off 1=on. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.4779.1.3.5.5.1.18 | ||||||||||||||
sRPCOverTempThresholdmandatory The over temperature alarm threshold level *10. A value of 505 will set the level to 50.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.19 | ||||||||||||||
sRPCUnitVAmandatory Number of outlets for this RPC.This will be the size of outlet table for this RPC index. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.20 | ||||||||||||||
sRPCNumberOfBreakersmandatory Number of breakers for this RPC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.21 | ||||||||||||||
sRPCLowCurrentThresholdmandatory Low current threshold for this RPC. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.22 | ||||||||||||||
sRPCVoltageSourcemandatory Voltage source for this RPC. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.23 | ||||||||||||||
sRPCSourceSwitchCountmandatory Voltage source switch count for this RPC. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.24 | ||||||||||||||
sRPCNumberOfSensorsmandatory Number of sensors for this RPC. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.5.1.25 |
.1.3.6.1.4.1.4779.1.3.5.6
·
1 row entry
·
5 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sBTAModulesRPCModPortOutletTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sBTAModulesRPCModPortOutletTable'
Allows for control of individual outlets. The number of entries is contained in the sBTAModulesRPCOutletTableSize OID.
The outlets to control and get status on.
| Column | Syntax | OID | ||||||||||||||
|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|---|
sRPCOutletModuleIndexmandatory The module index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.6.1.1 | ||||||||||||||
sRPCOutletPortIndexmandatory The port index to the outlet entry. In the case of ds30s this number is always 1. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.6.1.2 | ||||||||||||||
sRPCOutletIndexmandatory The outlet index to the outlet entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.6.1.3 | ||||||||||||||
sRPCOutletStatemandatory Getting this variable will return the state of the outlet.Valid return states are unknown, on, off, lockon, lockoff. 0 = off 1 = on 2 = reboot 3 = lockon (outlet is on and no changes are allowed) 4 = lockoff (outlet is… | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.4779.1.3.5.6.1.4 | ||||||||||||||
sRPCOutletNamemandatory The name of the outlet. Maximum size is 16 characters. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.4779.1.3.5.6.1.5 |
.1.3.6.1.4.1.4779.1.3.5.8
·
1 row entry
·
5 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sBTAModulesRPCCurrentGroupsCurrentTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sBTAModulesRPCCurrentGroupsCurrentTable'
A list of total current for RPCs in each current group
Table of total current measurement by group
Indexes
| Column | Syntax | OID |
|---|---|---|
groupCurrentIndexmandatory The index to a group total current. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.8.1.1 |
groupCurrentmandatory Current total for all RPCs in group. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.8.1.2 |
rpcGroupmandatory A character string listing the RPCs, by port index, that will beincluded in a measurement of total current. For each group, a sum will be periodically computed of currents of all listed RPCs, which will be compared to… | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.4779.1.3.5.8.1.3 |
warningThresholdmandatory The current level, in tenths of an amp, that will cause a CurrentLevel Warning trap to be sent if the total current for the associated group if exceeded. Conversely, a Current Level Warning Clear trap will be sent w… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.8.1.4 |
emergencyThresholdmandatory The current level, in tenths of an amp, that will cause a CurrentLevel Emergency trap to be sent if the total current for the associated group if exceeded. Conversely, a Current Level Emergeny Clear trap will be sen… | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.8.1.5 |
.1.3.6.1.4.1.4779.1.3.5.9
·
1 row entry
·
9 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sBTAModulesRPCBreakersTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sBTAModulesRPCBreakersTable'
Allows monitoring of individual outlet strips on RPCs.
Status organization by breaker.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sBTAModulesRPCBreakersModulesIndexmandatory The index into the RPC table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.9.1.1 | ||||
sBTAModulesRPCBreakersBreakersIndexmandatory The index into the RPC breaker table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.9.1.2 | ||||
sBTAModulesRPCBreakersCircuitBreakermandatory Status of circuit breaker in power strip. 0=off 1=on. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.4779.1.3.5.9.1.3 | ||||
sBTAModulesRPCBreakersCurrentmandatory The detected current reading for the power strip.If current measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.9.1.4 | ||||
sBTAModulesRPCBreakersMaxCurrentmandatory The maximum detected current reading for the power strip.If current measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.9.1.5 | ||||
sBTAModulesRPCBreakersVoltagemandatory The voltage reading for the power strip.If voltage measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.9.1.6 | ||||
sBTAModulesRPCBreakersPowermandatory The power reading for the power strip.If voltage measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.9.1.7 | ||||
sBTAModulesRPCBreakersVAmandatory The volt-amps reading for the power strip.If voltage measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.9.1.8 | ||||
| The current alarm threshold level *10. A value of 105 will set the level to 10.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.9.1.9 |
.1.3.6.1.4.1.4779.1.3.5.10
·
1 row entry
·
10 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sRPCModPortBreakersTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sRPCModPortBreakersTable'
Allows monitoring of individual outlet strips on RPCs.
Status organization by breaker.
| Column | Syntax | OID | ||||
|---|---|---|---|---|---|---|
sRPCBreakersModIndexmandatory The module index into the RPC breaker table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.10.1.1 | ||||
sRPCBreakersPortIndexmandatory The port index into the RPC breaker table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.10.1.2 | ||||
sRPCBreakersBreakersIndexmandatory The breaker index into the RPC breaker table. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.10.1.3 | ||||
sRPCBreakersCircuitBreakermandatory Status of circuit breaker in power strip. 0=off 1=on. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.4779.1.3.5.10.1.4 | ||||
sRPCBreakersCurrentmandatory The detected current reading for the power strip.If current measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.10.1.5 | ||||
sRPCBreakersMaxCurrentmandatory The maximum detected current reading for the power strip.If current measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.10.1.6 | ||||
sRPCBreakersVoltagemandatory The voltage reading for the power strip.If voltage measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.10.1.7 | ||||
sRPCBreakersPowermandatory The power reading for the power strip.If voltage measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.10.1.8 | ||||
sRPCBreakersVAmandatory The volt-amps reading for the power strip.If voltage measurement is not installed this value will always read 0. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.10.1.9 | ||||
sRPCBreakersCurrentAlarmThresholdmandatory The current alarm threshold level x10. A value of 105 will set the level to 10.5. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.3.5.10.1.10 |
.1.3.6.1.4.1.4779.1.4.4
·
1 row entry
·
7 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sBTAControlUserTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sBTAControlUserTable'
A list of users and user information. The number of entries is contained in the sBTAControlNumOfLoggedUsers OID.
The users to get status on.
Indexes
| Column | Syntax | OID | ||||||||
|---|---|---|---|---|---|---|---|---|---|---|
sBTAControlUserIndexmandatory The index to the user entry. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.4.4.1.1 | ||||||||
sBTAControlUserNamemandatory The username of the user. | RFC1213-MIBDisplayString | .1.3.6.1.4.1.4779.1.4.4.1.2 | ||||||||
sBTAControlUserAddressmandatory The IP address of the user. | RFC1155-SMIIpAddress Type Constraints: range: 4 | .1.3.6.1.4.1.4779.1.4.4.1.3 | ||||||||
sBTAControlUserConnectionmandatory Type of connection.If unknown, user is logging out or the connection is invalid. | Enumeration Enumerated Values:
| .1.3.6.1.4.1.4779.1.4.4.1.4 | ||||||||
sBTAControlUserConnModulemandatory If the user is connected to a module, this value willreport the module number connected to. If the value is 0 the user is not connected to a module. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.4.4.1.5 | ||||||||
sBTAControlUserConnPortmandatory The port number with in a module that the user is connected to.This usually only applies to connections to DS74 serial modules. Intelligent modules connections are always made on port 1. If value is 0 the user is not c… | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.4.4.1.6 | ||||||||
sBTAControlUserTerminateUsermandatory Settings this OID to anything but 0 will terminate (log out) the user.A get of this OID will return 0. | Enumerationr/w Enumerated Values:
| .1.3.6.1.4.1.4779.1.4.4.1.7 |
.1.3.6.1.4.1.4779.1.6.1
·
1 row entry
·
12 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sBTAModulesEnvironmentalObjectsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sBTAModulesEnvironmentalObjectsTable'
Allows monitoring of individual outlet strips on RPCs.
Status organization by sensor.
| Column | Syntax | OID |
|---|---|---|
sBTAModulesEnvironmentalModulesIndexmandatory Module Index for Environemntal table | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.1 |
sBTAModulesEnvironmentalSensorsIndexmandatory Sensor Index for Environemntal table | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.2 |
sBTAModulesEnvironmentalTypemandatory Environmental Object Type. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.3 |
sBTAModulesEnvironmentalNamemandatory The name for the environmental object. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.4779.1.6.1.1.4 |
sBTAModulesEnvironmentalMeasurementmandatory The measurement or state for the object. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.5 |
sBTAModulesEnvironmentalHiThresholdmandatory Hi threshold for object. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.6 |
sBTAModulesEnvironmentalLoThresholdmandatory Lo threshold for object. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.7 |
sBTAModulesEnvironmentalMaxmandatory Max value recorded for object since last reset. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.8 |
sBTAModulesEnvironmentalMinmandatory Min value recorded for object since last reset. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.9 |
| Hi threshold enable for object. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.10 |
| Lo threshold enable for object. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.11 |
sBTAModulesEnvironmentalStateTrapEnmandatory Trap enable for environmental sensors with contacts. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.1.1.12 |
.1.3.6.1.4.1.4779.1.6.2
·
1 row entry
·
13 columns
Uses the baytech variant from
Command help
/opt/observium/mibs/baytech.
Walk sRPCEnvironmentalObjectsTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'Baytech-MIB-401-4' -M '/opt/observium/mibs/baytech:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'Baytech-MIB-401-4::sRPCEnvironmentalObjectsTable'
Allows monitoring of individual outlet strips on RPCs.
Status organization by sensor.
Indexes
sBTAEnvironmentalModuleIndex sBTAEnvironmentalPortIndex sBTAEnvironmentalSensorsIndex
| Column | Syntax | OID |
|---|---|---|
sRPCEnvironmentalModuleIndexmandatory Module Index for Environemntal table | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.1 |
sRPCEnvironmentalPortIndexmandatory Port Index for Environemntal table | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.2 |
sRPCEnvironmentalSensorsIndexmandatory Sensor Index for Environemntal table | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.3 |
sRPCEnvironmentalTypemandatory Environmental Object Type. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.4 |
sRPCEnvironmentalNamemandatory The name for the environmental object. | RFC1213-MIBDisplayStringr/w | .1.3.6.1.4.1.4779.1.6.2.1.5 |
sRPCEnvironmentalMeasurementmandatory The measurement or state for the object. | Integer32 Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.6 |
sRPCEnvironmentalHiThresholdmandatory Hi threshold for object. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.7 |
sRPCEnvironmentalLoThresholdmandatory Lo threshold for object. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.8 |
sRPCEnvironmentalMaxmandatory Max value recorded for object since last reset. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.9 |
sRPCEnvironmentalMinmandatory Min value recorded for object since last reset. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.10 |
sRPCEnvironmentalHiThresholdEnmandatory Hi threshold enable for object. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.11 |
sRPCEnvironmentalLoThresholdEnmandatory Lo threshold enable for object. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.12 |
sRPCEnvironmentalStateTrapEnmandatory Trap enable for environmental sensors with contacts. | Integer32r/w Type Constraints: range: -2147483648..2147483647 | .1.3.6.1.4.1.4779.1.6.2.1.13 |