ATEN-PE-CFG Table View

Table-centric layout grouping table, row, and column objects.

Tables
22
Rows
22
Columns
160

usrListTable

table
.1.3.6.1.4.1.21317.1.3.2.2.1.1 · 1 row entry · 47 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk usrListTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::usrListTable'
A list of user. The number of user is
given by the value of usrcfgNumber.
usrListEntry row .1.3.6.1.4.1.21317.1.3.2.2.1.1.1
Status and parameter values for a pe8208 user.
Indexes
Column Syntax OID
The value of usrIndex for the user. We have 1 administrator and 8 users.
The index 9 will be the administrator.
Integer32
Constraints:
range: 1-9
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.1
The user's type.
Enumeration
Enumerated Values:
1administrator
2user
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.2
A textual string containing name of the user.
string length: 1~16
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.3
A textual string containing password of the user.
string length: 1~16
OctetStringr/w
Constraints:
range: 1-16
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.4
Display or set this user's outlet 1 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.5
Display or set this user's outlet 2 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.6
Display or set this user's outlet 3 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.7
Display or set this user's outlet 4 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.8
Display or set this user's outlet 5 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.9
Dispaly or set this user's outlet 6 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.10
Display or set this user's outlet 7 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.11
Display or set this user's outlet 8 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.12
Display or set this user's outlet 9 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.13
Display or set this user's outlet 10 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.14
Display or set this user's outlet 11 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.15
Display or set this user's outlet 12 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.16
Display or set this user's outlet 13 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.17
Display or set this user's outlet 14 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.18
Display or set this user's outlet 15 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.19
Display or set this user's outlet 16 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.20
Display or set this user's outlet 17 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.21
Display or set this user's outlet 18 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.22
Display or set this user's outlet 19 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.23
Display or set this user's outlet 20 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.24
Display or set this user's outlet 21 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.25
Display or set this user's outlet 22 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.26
Display or set this user's outlet 23 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.27
Display or set this user's outlet 24 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.28
Display or set this user's outlet 25 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.29
Display or set this user's outlet 26 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.30
Display or set this user's outlet 27 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.31
Display or set this user's outlet 28 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.32
Display or set this user's outlet 29 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.33
Display or set this user's outlet 30 authority.
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.34
Display or set this user's outlet 31 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.35
Display or set this user's outlet 32 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.36
Display or set this user's outlet 33 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.37
Display or set this user's outlet 34 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.38
Display or set this user's outlet 35 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.39
Display or set this user's outlet 36 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.40
Display or set this user's outlet 37 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.41
Display or set this user's outlet 38 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.42
Display or set this user's outlet 39 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.43
Display or set this user's outlet 40 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.44
Display or set this user's outlet 41 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.45
Display or set this user's outlet 42 authority
Port in the pe of series represents outlet.
Port in the Energy monitor of series represents a bank or a pdu.
Enumerationr/w
Enumerated Values:
1disable
2view
3modify
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.46
Display or set this user is enable or not
Enumerationr/w
Enumerated Values:
1disable
2enable
.1.3.6.1.4.1.21317.1.3.2.2.1.1.1.47
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3 · 1 row entry · 9 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk deviceValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::deviceValueTable'
Device value table. This table displays device's current, voltage, power and
power dissipation.
deviceValueEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1
Single deviceValue entry containing device info.
Column Syntax OID
Index of deviceValue.
Integer32
Constraints:
range: 1-1
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.1
Device electric current value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.2
Device voltage value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.3
Device power value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.4
Device power dissipation value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.5
Device input Voltage value. unit:(V)
If the device does not support this OID, we show value 0.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.6
Device input Current value. unit:(A)
If the device does not support this OID, we show value 0.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.7
Device power Capacity value.unit:(VA)
If the device does not support this OID, we show value 0.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.8
Device power Factor value.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.1.3.1.9
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk sensorValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::sensorValueTable'
Device's sensor value table. This table displays sensor's temperature, humidity and
pressure.
sensorValueEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1
Single device's sensor value entry containing device info.
Column Syntax OID
Index of sensor number.
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.1
Sensor's Temperature value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.2
Sensor's Humidity value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.3
Sensor's Pressure value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.4
Sensor's Property.
Enumeration
Enumerated Values:
1intake
2exhaust
3floor
.1.3.6.1.4.1.21317.1.3.2.2.2.1.4.1.5
.1.3.6.1.4.1.21317.1.3.2.2.2.1.5 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk deviceOutletStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::deviceOutletStatusTable'
Device outlet status value table.
deviceOutletStatusEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1
Single deviceOutletStatus entry containing device info.
Column Syntax OID
Index of deviceOutletStatus
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.1
Display outlet status.
Enumeration
Enumerated Values:
1off
2on
3pending
4fault
5noauth
6not-support
7pop
.1.3.6.1.4.1.21317.1.3.2.2.2.1.5.1.2
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6 · 1 row entry · 8 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk deviceConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::deviceConfigTable'
Device configuration table
deviceConfigEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1
Single deviceConfig entry containing device info.
Column Syntax OID
Index of deviceConfig
Integer32
Constraints:
range: 1-1
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.1
Display or set device minimum electric current measurement threshold.
Example: range 0.0~32.0 represents 0~320.
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does …
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.2
Display or set device maximum electric current measurement threshold.
Example: range 0.0~32.0 represents 0~320
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device doe…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.3
Display or set device minimum voltage measurement threshold.
Exapmple: range 90.0~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not…
Integer32r/w
Constraints:
range: 900-2600
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.4
Display or set device maximum voltage measurement threshold.
Example: range 90.0~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not …
Integer32r/w
Constraints:
range: 900-2600
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.5
Display or set device minimum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not s…
Integer32r/w
Constraints:
range: 0-99999
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.6
Display or set device maximum power measurement threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not s…
Integer32r/w
Constraints:
range: 0-99999
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.7
Display or set device maximum power dissipation measurement threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the dev…
Integer32r/w
Constraints:
range: 0-999990
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.6.1.8
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7 · 1 row entry · 7 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk deviceSensorTresholdTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::deviceSensorTresholdTable'
Device environment value table
deviceSensorTresholdEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1
Device's sensor Environment entry containing sensor info.
Column Syntax OID
Index of sensor number
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.1
Display or set sensor minimum temperature measurement threshold.
Example: range -20.0 ~ 60.0 represents -200~600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device doe…
Integer32r/w
Constraints:
range: -200-600
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.2
Display or set sensor maximum temperature measurement threshold.
Example: range -20.0 ~ 60.0 represents -200~600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device doe…
Integer32r/w
Constraints:
range: -200-600
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.3
Display or set sensor minimum humidity measurement threshold.
Example: range 10.0 ~ 95.0 represents 100~950
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not…
Integer32r/w
Constraints:
range: 100-950
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.4
Display or set sensor maximum humidity measurement threshold.
Example: range 10.0 ~ 95.0 represents 100~950
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not…
Integer32r/w
Constraints:
range: -3000--3000
range: 100-950
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.5
Display or set sensor minimum pressure measurement threshold.
Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device …
Integer32r/w
Constraints:
range: -2500-2500
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.6
Display or set sensor maximum pressure measurement threshold.
Example: range -250.0 ~ 250.0 represents -2500 ~ 2500
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device …
Integer32r/w
Constraints:
range: -2500-2500
range: -3000--3000
.1.3.6.1.4.1.21317.1.3.2.2.2.1.7.1.7
.1.3.6.1.4.1.21317.1.3.2.2.2.1.15 · 1 row entry · 3 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk dryContactTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::dryContactTable'
Device's Dry Contact table.
dryContactEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.1.15.1
Single device's dry contact value entry containing device info.
Indexes
Column Syntax OID
Index of dry contact number.
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.21317.1.3.2.2.2.1.15.1.1
Display dry contact status.
close(0) represents door close.
open(1) represents door open.
not-attached(2) represents door sensor don't attach to device.
Enumeration
Enumerated Values:
0close
1open
2not-attached
10not-support
.1.3.6.1.4.1.21317.1.3.2.2.2.1.15.1.2
Dry contact Type Selection
Enumerationr/w
Enumerated Values:
0notinstalled
1photo
2inductiveproximity
3reed
10not-support
.1.3.6.1.4.1.21317.1.3.2.2.2.1.15.1.3
.1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletCAPTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::outletCAPTable'
Outlet CAP table
outletCAPEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1
Outlet CAP entry containing CAP info.
Indexes
Column Syntax OID
Index of outlet's CAP configuration
Integer32
Constraints:
range: 1-40
.1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.1
Display or set the CAP Priority of outlet.
Priority 0 means this outlet does not support this OID.
Integer32r/w
Constraints:
range: 0-99
.1.3.6.1.4.1.21317.1.3.2.2.2.1.18.2.1.2
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk deviceIntegerValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::deviceIntegerValueTable'
Device value table. This table displays device's current, voltage, power and
power dissipation.
deviceIntegerValueEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1
Single deviceValue entry containing device info.
Column Syntax OID
Index of deviceValue.
Integer32
Constraints:
range: 1-1
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.1
Device electric current value.
This value indicates that 1,000 times.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.2
Device voltage value.
This value indicates that 1,000 times.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.3
Device power value.
This value indicates that 1,000 times.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.4
Device power dissipation value.
This value indicates that 1,000 times.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.99.1.5
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100 · 1 row entry · 4 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk sensorIntegerValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::sensorIntegerValueTable'
Device's sensor value table. This table displays sensor's temperature, humidity and
pressure.
sensorIntegerValueEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1
Single device's sensor value entry containing device info.
Column Syntax OID
Index of sensor number.
Integer32
Constraints:
range: 1-6
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.1
Sensor's Temperature value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.2
Sensor's Humidity value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.3
Sensor's Pressure value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.1.100.1.4
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1 · 1 row entry · 7 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::outletValueTable'
Display total outlet value table
outletValueEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1
Single outletValue entry containing outlet info.
Column Syntax OID
Index of outlet number
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.1
Outlet electric current value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.2
Outlet voltage value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.3
Outlet power value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.4
Outlet power dissipation value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.5
Outlet Max Current value. unit: (A).
If the device does not support this OID, we show value 0.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.6
Outlet Power Factor value.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.2.1.1.7
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10 · 1 row entry · 16 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::outletConfigTable'
Outlet configuration table
outletConfigEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1
Outlet Config entry containing outlet info.
Column Syntax OID
Index of outlet number
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.1
Display or set the name of outlet.
If the device does not support this OID, we show n/a.
string length: 0~48
NOTE: Input string as /empty to set this object to NULL.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.2
Display or set the confirmation of outlet.
Enumerationr/w
Enumerated Values:
1no
2yes
3noauth
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.3
Display or set the ON delay time of outlet.
When this model does not support the OID, we show value -1.
Integer32r/w
Constraints:
range: -1-999
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.4
Display or set the OFF delay time of outlet.
When this model does not support the OID, we show value -1.
Integer32r/w
Constraints:
range: -1-999
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.5
Display or set the shutdown mehtod of outlet.
Enumerationr/w
Enumerated Values:
1kill-the-power
2wake-on-lan
3after-ac-back
4not-support
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.6
Display or set the MAC address of ShutdownMethod.
If the device does not support this OID, we show n/a.
string length: 12
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.7
Display or set the outlet minimum electric current measurment threshold.
Example: range 0.0 ~16.0 rerpresnts 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device d…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.8
Display or set the outlet maximum electric current measurment threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device d…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.9
Display or set the outlet minimum voltage measurment threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does …
Integer32r/w
Constraints:
range: 900-2600
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.10
Display or set the outlet maximum voltage measurment threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does …
Integer32r/w
Constraints:
range: 900-2600
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.11
Display or set the outlet minimum power measurment threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not…
Integer32r/w
Constraints:
range: 0-99999
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.12
Display or set the outlet maximum power measurment threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not…
Integer32r/w
Constraints:
range: 0-99999
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.13
Display or set the outlet maximum power dissipation measurment threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the d…
Integer32r/w
Constraints:
range: 0-999990
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.14
Whether local access of Outlet is locked by remote or not.
Enumerationr/w
Enumerated Values:
1unlocked
2locked
3not-support
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.15
Whether the outlet is always ON or not.
Enumerationr/w
Enumerated Values:
1no
2yes
3not-support
.1.3.6.1.4.1.21317.1.3.2.2.2.2.10.1.16
.1.3.6.1.4.1.21317.1.3.2.2.2.2.70 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletSwitchableTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::outletSwitchableTable'
outletSwitchableEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1
Column Syntax OID
Index of outlet number.
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.1
Enumeration
Enumerated Values:
1no
2yes
.1.3.6.1.4.1.21317.1.3.2.2.2.2.70.1.2
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk outletIntegerValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::outletIntegerValueTable'
Display total outlet value table
outletIntegerValueEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1
Single outletValue entry containing outlet info.
Column Syntax OID
Index of outlet number.
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.1
Outlet electric current value.
This value indicates that 1,000 times.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.2
Outlet voltage value.
This value indicates that 1,000 times.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.3
Outlet power value.
This value indicates that 1,000 times.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.4
Outlet power dissipation value.
This value indicates that 1,000 times.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.2.99.1.5
.1.3.6.1.4.1.21317.1.3.2.2.2.3.1 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk breakerStatusTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::breakerStatusTable'
Display total bank value table
breakerStatusEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1
Single bankValue entry containing bank info.
Column Syntax OID
Index of breaker number.
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.1
Breaker status.
Enumeration
Enumerated Values:
1off
2on
3not-support
.1.3.6.1.4.1.21317.1.3.2.2.2.3.1.1.2
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2 · 1 row entry · 8 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk bankValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::bankValueTable'
Display total bank value table
bankValueEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1
Single bankValue entry containing bank info.
Indexes
Column Syntax OID
Index of bank number
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.1
Bank electric current value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.2
Bank voltage value.
We put this OID to write access type for user to set the reference voltage on EC1000 model.
And the setting should be the numbers. You can set 0 to clear the setting.
If this measurement value is not…
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.3
Bank power value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.4
Bank power dissipation value.
If this measurement value is not available, it returns: N/A.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.5
The Bank Max Current value. unit: (A)
EC1000:0A~320A
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.6
The status of Energy sensor Bank attached status.
Enumeration
Enumerated Values:
1noattached
2attached
3error
4noexisted
.1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.7
Bank Power Factor value.
If the device does not support this OID, it returns: not-support.
RFC1213-MIBDisplayString .1.3.6.1.4.1.21317.1.3.2.2.2.3.2.1.8
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3 · 1 row entry · 9 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk bankConfigTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::bankConfigTable'
Bank configuration table
bankConfigEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1
Bank Config entry containing Bank info.
Indexes
Column Syntax OID
Index of bank number
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.1
Display or set the name of bank.
When this model does not support the OID, we show n/a.
string length: 0~15
NOTE: Input string as /empty to set this object to NULL.
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.2
Display or set the outlet minimum electric current measurment threshold.
Example: range 0.0 ~16.0 rerpresnts 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device d…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.3
Display or set the outlet maximum electric current measurment threshold.
Example: range 0.0 ~16.0 represents 0~160
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device d…
Integer32r/w
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.4
Display or set the outlet minimum voltage measurment threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does …
Integer32r/w
Constraints:
range: 900-2600
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.5
Display or set the outlet maximum voltage measurment threshold.
Example: range 90.0 ~260.0 represents 900~2600
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does …
Integer32r/w
Constraints:
range: 900-2600
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.6
Display or set the outlet minimum power measurment threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not…
Integer32r/w
Constraints:
range: 0-99999
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.7
Display or set the outlet maximum power measurment threshold.
Example: range 0.0 ~ 9999.9 represents 0~99999
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the device does not…
Integer32r/w
Constraints:
range: 0-99999
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.8
Display or set the outlet maximum power dissipation measurment threshold.
Example: range 0.0 ~ 99999.0 represents 0~999990
NOTICE: Minimum threshold should be smaller than maximum threshold.
Empty value: -3000.
If the d…
Integer32r/w
Constraints:
range: 0-999990
range: -3000--3000
range: -2000000--2000000
.1.3.6.1.4.1.21317.1.3.2.2.2.3.3.1.9
.1.3.6.1.4.1.21317.1.3.2.2.2.3.4 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk bankControlTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::bankControlTable'
Bank Control table
bankControlEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1
Bank control entry.
Column Syntax OID
Index of bank number
Integer32
Constraints:
range: 1-4
.1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.1
This function is used for outlet control of bank.
Set off(1) to turn off for outlet control of bank.
Set on(2) to turn on for all outlet control of bank.
Set reboot(3) to turn on for outlet control of bank.
Get this obj…
Enumerationr/w
Enumerated Values:
1off
2on
3reboot
4nostatus
5not-support
.1.3.6.1.4.1.21317.1.3.2.2.2.3.4.1.2
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99 · 1 row entry · 5 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk bankIntegerValueTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::bankIntegerValueTable'
Display total bank value table
bankIntegerValueEntry row .1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1
Single bankValue entry containing bank info.
Column Syntax OID
Index of bank number.
Integer32
Constraints:
range: 1-30
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.1
Bank electric current value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.2
Bank voltage value.
This value indicates that 1,000 times.

We put this OID to write access type for user to set the reference voltage on EC1000 model.
And the setting should be the numbers. You can set 0…
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.3
Bank power value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.4
Bank power dissipation value.
This value indicates that 1,000 times.
If this measurement value is not available, it returns value -1000000.
If the device does not support this OID, it returns value -2000000.
Integer32
Type Constraints:
range: -2147483648..2147483647
.1.3.6.1.4.1.21317.1.3.2.2.2.3.99.1.5
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3 · 1 row entry · 7 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk snmpTrapTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::snmpTrapTable'
PE SNMP agent trap setup table. If users want to use trap, 
they must set enable trap, ip and community first.
snmpTrapEntry row .1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1
Single trap entry containing trap receiver info.
Column Syntax OID
Index of trap receiver
Integer32
Constraints:
range: 1-2
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.1
Trap receiver IP address
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.2
NMS trap port to be used by agent to send trap
Integer32r/w
Constraints:
range: 1-65535
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.3
If use SNMPv1/v2c to receive trap should set this Community string.
MAX string length: 20
NOTE: Input string as /empty to set this object to NULL.
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.4
If use SNMPv3 to receive trap should set this string.
NOTE: Input string as /empty to set this object to NULL.
MAX string length: 20
OctetStringr/w
Constraints:
range: 0-20
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.5
If use SNMPv3 to receive trap should set this string.
MAX string length: 20
NOTE: Input string as /empty to set this object to NULL.
OctetStringr/w
Constraints:
range: 8-20
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.6
If use SNMPv3 to receive trap should set this string.
MAX string length: 20
NOTE: Input string as /empty to set this object to NULL.
OctetStringr/w
Constraints:
range: 8-20
.1.3.6.1.4.1.21317.1.3.2.2.3.4.7.1.3.1.7
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3 · 1 row entry · 3 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk ipFilterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::ipFilterTable'
A list of restricted ip.
ipFilterEntry row .1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1
Status and parameter values for a PE's restricted IP.
Indexes
Column Syntax OID
The value of index for the ip filter.
Integer32
Constraints:
range: 1-5
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.1
A set of restricted ip.
ex. 192.168.0.1

Note: Users must follow in order to set the ip address.
Note: To clear the settings to set the ip 0.0.0.0
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.2
A set of restricted ip.
ex. 192.168.0.255

Note: Users must follow in order to set the ip address.
Note: To clear the settings to set the ip 0.0.0.0
RFC1155-SMIIpAddressr/w
Type Constraints:
range: 4
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.2.3.1.3
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3 · 1 row entry · 2 columns
Uses the aten variant from /opt/observium/mibs/aten.
Command help
Walk macFilterTable
/usr/bin/snmpbulkwalk -v2c -c '<community>' -Pud -Ir -OQUs -m 'ATEN-PE-CFG' -M '/opt/observium/mibs/aten:/opt/observium/mibs/rfc:/opt/observium/mibs/net-snmp' 'udp:<hostname>:161' 'ATEN-PE-CFG::macFilterTable'
A list of restricted mac.
macFilterEntry row .1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1
Status and parameter values for a PE's restricted MAC.
Indexes
Column Syntax OID
The value of index for the mac filter.
Integer32
Constraints:
range: 1-5
.1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.1
A set of restricted mac.
string length: 12
ex. 004854655511

Note: Users must follow in order to set the MAC address.
Note: To clear the settings to set the MAC 000000000000
RFC1213-MIBDisplayStringr/w .1.3.6.1.4.1.21317.1.3.2.2.3.5.4.3.3.1.2